1) UO ENABLE 80 BO ENABLE AI AI
FAULT 81 BI CSR
CSR BI
TYP 2
ENERGY RECOVER VENTILATOR
l< M201 SCALE: NONE
NOTES:
CONTROL COMPONENT PROVIDED AND FACTORY INSTALLED BY EQUIPMENT MANUFACTURER,
wo
al
AIR CLEANING
SYSTEM
HPS
HPR
11 PIRTAIN
TO SYSTEM TO SYSTEM
CONTROLLER CONTROLLER
L
...............
El - - - - - - - - - - - - - - TS-Al
ISOLATION SOLENOID VALVE L- - - - - -.W.- - - HS HS-Al
2HOR
SPA
3 HEAT PUMP WITH REHEAT (GSHP)
lM2 SCALE: NONE
NOTES:
1. TWO WAY ISOLATION SOLENOID VALVE FURNISHED BY BAS CONTRACTOR, INSTALLED BY MECH CONTRACTOR
2. WALL TEMPERATURE AND HUMIDITY SENSORS FURNISHED AND FIELD INSTALLED BY BAS CONTRACTOR.
3. PROVIDE CONDENSATE WATER LEVEL DETECTION DEVICE FOR ALL HORIZONTAL UNITS LOCATED OVER FINISH
SPACES.
4. REHEAT CSR FURNISHED AND FIELD INSTALLED BY BAS CONTRACTOR.
5. AIR CLEANINNG SYSTEM SHALL BE HARD -WIRE INTERLOCKED TO GSHP BLOWER MOTOR OPERATION,
■
mom
GSHP
FILTER HEAT PUMP
L MPC I
B _YU UM TO TO SYSTEM
I CONTROLLER
HPS I L - - - - - - - - - J
HPR
ISOLATION SOLENOID VALVE L 2HOR
SPA
BO
HEAT PUMP WITHOUT REHEAT (GSHP)
I<J�M211 SCALE: NONE
NOTES:
1. TWO-WAY ISOLATION SOLENOID VALVE FURNISHED BY BAS CONTRACTOR, INSTALLED BY MECH CONTRACTOR.
2. WALL TEMPERATURE SENSORS FURNISHED AND FIELD INSTALLED BY BAS CONTRACTOR.
3. PROVIDE CONDENSATE WATER LEVEL ,DETECTION DEVICE FOR ALL HORIZONTAL UNITS LOCATED OVER FINISHED
SPACES.
EXHAUST OUTSIDE
AIR AIR
FROM ERV FROM ERV
MODULATE AID
CSR BI :Al CSR Bf Al
TS
CSR BI GSHP
FILTER HEAT PUMP Ts TS
I t I
Cl
AIR CLEANING
REHEAT MPC ELEC HEATING COIL
SYSTEM T T BY UM TO SYSTEM TO SYSTEM
I CONTROLLER CONTROLLER
HPS L - - - - - - - - -
HPR
- - - - - - - - - - --- - - I TS-Al
ISOLATION SOLENOID VALVE L_ - - - - - - - - HS HS-Al
2HOR
SPA
I
am ml,
4 GSHP-3
SCALE: NONE
NgTES-,
1. TWO-WAY ISOLATION SOLENOID VALVE FURNISHED BY BAS CONTRACTOR, INSTALLED BY MECH CONTRACTOR.
2. WALL TEMPERATURE AND HUMIDITY SENSORS FURNISHED AND FIELD INSTALLED BY BAS CONTRACTOR.
3. PROVIDE CONDENSATE WATER LEVEL DETECTION DEVICE FOR ALL HORIZONTAL UNITS LOCATED OVER FINISHED
SPACES.
4. REHEAT CSR FURNISHED AND FIELD INSTALLED BY BAS CONTRACTOR.
5. AIR CLEANINNG SYSTEM SHALL BE HARD -ORE INTERLOCKED TO GSHP BLOWER MOTOR OPERATION.
----------------------------------------------------------
MAKE-UP AIR
DAMPER
EF--
L
LINE VOLTAGE D
THERMOSTAT
ELECTRICAL SERVICE MONITORING
EQUIPMENT
SALLY PORT
L-.-_---_-__-----------_---- _---_ _-_. -_--_...__.--__--- ---j'
5 SALLYPORT EXHAUST FAN (EF-1BUILDING POWER MONITORING
f-1/1) SCALE: NONE QM2)11 SCALE: NONE
NOTES: KM
1. LINE VOLTAGE THERMOSTAT FURNISHED AND FIELD INSTALLED BY BAS CONTRACTOR. COORDINATE WITH 1. COORDINATE PULSE METER INTERFACE WITH UTILITY AND ELEC CONTRACTOR.
OTHER TRADES AS REQUIRED.
SEQUENCE OF OPERATIONS
ENERGY RECOVERY VENTILATOR (ERV) - 1/M201
1. EACH ERV SHALL HAVE A MICROPROCESSOR -BASED CONTROLLER WHICH SHALL MONITOR AND CONTROL THE UNIT IN A STAND-ALONE MODE OR AS DIRECTED BY THE BAS. THE
ERV SHALL OPERATE IN OCCUPIED AND UNOCCUPIED MODE ACCORDING TO BAS SCHEDULING. OCCUPIED OVERRIDE ACTIVATED AT A HEAT PUMP THERMOSTAT SHALL INITIATE THE
ERV OCCUPIED MODE FOR DURATION OF 2 HOURS. THE ERVS SHALL OPERATE IN OCCUPIED MODE CONTINUOUSLY UNLESS REQUESTED BY THE OWNER.
2. OCCUPIED MODE: THE SUPPLY AND EXHAUST FANS SHALL START, AND THE OUTSIDE AIR AND EXHAUST AIR DAMPERS SHALL OPEN.
3. ENTHALPY NEEL ECONOMIZER: THE ENTHALPY WHEEL SHALL BE LOCKED OUT WHEN THE OUTDOOR AIR TEMPERATURE IS BETWEEN 55' AND 75' DB.
4. UNOCCUPIED MODE: WHEN THE BAS INMATES THE UNOCCUPIED MODE, THE UNIT SHALL TURN OFF AND CLOSE ITS OUTSIDE AND EXHAUST AIR DAMPERS.
5. SYSTEM GRAPHIC DISPLAY:
a. ERV ON/OFF OVERRIDE SWITCH.
b. OUTSIDE AIR TEMPERATURE AND RELATIVE HUMIDITY.
c. EXHAUST AIR TEMPERATURES, ENTERING AND LEAVING.
d. EXHAUST AIR RELATIVE HUMIDITY, ENTERING AND LEAVING.
e. SUPPLY AIR TEMPERATURE AND RELATIVE HUMIDITY.
C NEEL ENABLE.
g. NEEL ECONOMIZER SET POINTS.
h. WHEEL ROTATION STATUS.
L DAMPER POSITIONS.
j. FAN ENABLE, SUPPLY AND EXHAUST.
k. FAN STATUS, SUPPLY AND EXHAUST.
HEAT PUMPS (GSHP) - 2/M20113/M20114/M201
1. EACH HEAT PUMP SHALL BE PROVIDED WITH ITS OWN COMMUNICATING MPC, SEE THE HEAT PUMP SPECIFICATION FOR MORE DESCRIPTION. THE BAS SHALL BE RESPONSIBLE FOR
COMMUNICATING WITH THAT MPC AND PROVIDING STATUS AND DIAGNOSTICS OF THE UNIT TO THE OPERATOR.
2. ALL SPACE TEMPERATURE SENSORS SHALL HAVE TIMED OVERRIDE BUTTONS. OCCUPANT INITIATED OVERRIDE SHALL BE LIMITED TO 2 HOURS MAXIMUM. THE HEAT PUMPS SERVING
ANIMAL AREAS SHALL OPERATE IN OCCUPIED MODE CONTINUOUSLY UNLESS REQUESTED BY THE OWNER.
3. SOME OF THE HP'S SHALL BE PROVIDED WITH REHEAT TO PROVIDE DEHUMIDIFICATION. REFER TO THE MECHANICAL SCHEDULES AND DRAWINGS. THE HEAT PUMP CONTROLLER
SHALL INITIATE THE DEHUMIDIFICATION MODE WHEN THE RELATIVE HUMIDITY SET POINT OF 50% IS EXCEEDED AND THE TEMPERATURE SET POINT IS SATISFIED.
4. OCCUPIED MODE: WHEN THE SYSTEM IS CONTROLLED TO THE OCCUPIED MODE, ALL UNIT FUNCTIONS SHALL BE ENABLED. THE SYSTEM SHALL OPERATE IN SPACE TEMPERATURE
CONTROL MODE,
a. UNITS WITH DUCTED VENTILATION AIR: THE UNIT SUPPLY FAN SHALL RUN CONTINUOUSLY.
b. GSHP-3: THE ELECTRIC DUCT HEATER SHALL MODULATE TO MAINTAIN DISCHARGE AIR TEMPERATURE DOWNSTREAM OF HEATER OF DRY BULB SET POINT OF 66" F DIRECTLY
DOWNSTREAM OF THE HEATER. HEATER SHALL BE ENABLED WHEN THE OUTDOOR AIR TEMPERATURE IS BELOW 50 DEGREES.
c. UNITS WITHOUT DUCTED VENTILATION AIR: THE UNIT SUPPLY FAN SHALL CYCLE AS REQUIRED TO MAINTAIN OCCUPIED SET POINTS.
5. UNOCCUPIED MODE: THE SUPPLY FAN SHALL CYCLE WITH THE COMPRESSOR IN HEATING OR COOLING AS REQUIRED TO MAINTAIN UNOCCUPIED HEATING AND COOLING SET POINTS.
6. ISOLATION VALVE: THE LEAVING WATER ISOLATION VALVE SHALL OPEN QUICKLY WHENEVER THE COMPRESSOR IS COMMANDED TO ENERGIZE, AND CLOSE SLOWLY WHEN THE
COMPRESSOR IS DE -ENERGIZED.
7. IF CONDENSATE BEGINS TO BUILD UP IN THE CONDENSATE PAN, THE WATER DETECTION DEVICE SHALL DISABLE THE UNIT AND SEND AN ALARM TO THE BAS.
8. SYSTEM GRAPHIC DISPLAY:
a. OUTDOOR TEMPERATURE AND RELATIVE HUMIDITY.
b. OCCUPIED/ UNOCCUPIED STATUS.
c. OCCUPANCY OVERRIDE STATUS.
d. SPACE TEMPERATURE AND SET POINT.
e. SPACE RELATIVE HUMIDITY AND SET POINT, REHEAT UNITS ONLY.
f. SUPPLY AIR TEMPERATURE.
g. LOOP SUPPLY TEMPERATURE.
h. FAN STATUS.
i. HEAT/COOL MODE.
j. DEHUMIDIFICATION MODE STATUS.
k. CONDENSATE WATER LEVEL DETEC11ON DEVICE STATUS.
I. AIR CLEANING SYSTEM STATUS,
m. ELECTRIC DUCT HEATER OUTSIDE AIR TEMPERATURE SET POINT, STATUS, DISCHARGE AIR TEMPERATURE AND SET POINT.
n. UNIT ALARM: OVER/UNDER VOLTAGE FAULT, HIGH/LOW PRESSURE FAULT, LOW WATER TEMPERATURE FAULT, CONDENSATE OVERFLOW FAULT.
SALLYPORT EXHAUST FAN (EF-1) - 5/M201
1. EF-1: THE EXHAUST FAN SHALL BE CONTROLLED BY LINE VOLTAGE THERMOSTAT AND IS NOT MONITORED OR CONTROLLED BY THE BAS. FAN SHALL INTERLOCK WITH MOTORIZED
OUTSIDE AIR DAMPER TO PROVIDE MAKEUP AIR.
BUILDING POWER MONITORING - 6/M201
1. THE BAS SHALL MONITOR AND LOG KW DEMAND, PHASE, VOLTAGE, & KWH. PROVIDE SYSTEM GRAPHIC DISPLAY SHOWING ALL POINTS.
2. BAS SHALL PROVIDE REQUIRED GATEWAY TO COMMUNICATE WITH ELECTRICAL UTILITY PULSED METERING EQUIPMENT.
0)
4-a
0
0 0
) 0
C\j
uj o
or)
5 N E
C/) 0
<
+ Ld >
z Ld
II-j Lu
A% ui > CID -t 4will
%a O� C/) Nt cf)
IIIIIIIIN"Ift " LIJ 00 CY)
00
o 0)
_j 0) N
0 M 4 .4
< Co cy)
0 (.5 I-1 LL
xxxo\%%%jI I I I
* Vz�
ItIIIIIII 111
2rw Consultants, Inc.
100 1 Oth Street NE, Ste, 202
Chadoltesvifle, VA 22902
434.296.2116
www.2rw.com
,MINOR
ccr
AP AM
cc
E
Affilk
%no?
cc
Co U)
3 _j
= 0
E 1--p
cc
Cc
0
NNNo
PROJECT PHASE:
Permit Set
PROJECT #: DATE:
09MO9122 7 DEC 2012
Od
S H ET e #tp C' r
6nce SLD
Ca