HomeMy WebLinkAbout053 M200.pdfEm
E:1
D-@
PHOTOCELL
SUN SHIELD TS pal OUTSIDE AIR
PORTABLE OPERATOR TERMINAL TEMPERATURE
LAPTOP COMPUTER W/ALL SETUP
SOFTWARE/CABLES FOR MAIN SUN SHIELD HS Ai OUTSIDE AIR
BUILDING PANEL & ALL CONTROLLERS HUMIDITY
120 VAC BY ELEC.. COORO W/ 120 VAC BY ELEC: BORES
CDORD W/ ELECLLZ
ELEC CONTRACTOR TYP, UND CONTRACTOR TYP, UNO
LAN INTERNET CONNECTION VIA LOW VOLTAGE
WORLD WIDE WEB, TRANSFORMER(S)
BY OTHERS PROVIDED BY BAS
CONTRACTOR
COMMUNICATION TRUNK COMMUNICATION TRUNK
UPS ..
MPC MPC FEC FEC
00 HPR TO
FDI BORES
PSH55—UPS
GSHP GSHP ERV MISC 1/0 PANELS FOR
(TYP) (TYP) (TYP) PUMPS, LIGHTING, ETC.
SYSTEM EXECUTIVE
MODULE
(MECH RM)
SYSTEM ARCHITECTURE
r Iv1200 SCALE: NONE
NOTES:
1. PROVIDE ADDITIONAL CONTROL MODULES AS REQUIRED TO PROVIDE SEQUENCES/DATA POINTS AS
INDICATED ON CONSTRUCTION DOCUMENTS.
2. INSTALL SYSTEM MODULE IN MECHANICAL ROOM. COORDINATE EXACT LOCATION WITH OTHER TRADES
AS REQUIRED.
ELEC
HEATING COIL
ELECTRIC DINT HEATER (UH
-- 50) SCALE: NONE
momw
ANIMAL FREEZER
TEMPERATURE MONITORING
91
SCALE: NONE
TYP 2
FAULT BI AD SPEED
ENABLE BO BI CSR
Al Al
VFD
TS PS
AIR HLP-1A
SEPARATOR
GROUND SOURCE HEAT PUMP
U LOOP
. 50)
SCALE: NONE
LINE
VOLTAGE
R �
4 GAS UNIT HEATER (GUH)
IM IrSCALE: NONE
: - - 3 BUILDING OVERRIDE
(Al EXTERIOR PHOTOCELL
No
RELAY,TO LIGHTING ELECTRICAL ; LOCATION AND
QUANTITY TO R CONTROLLED
LIGHTING CONTROL
SCALE: NONE
NOTES:
1. PHOTOCELL AND RELAYS FURNISHED BY BAS CONTRACTOR, INSTALLED BY ELEC CONTRACTOR.
. COORDINATE LOCATION OF BUILDING OVERRIDE WITH ELECTRICAL DRAWINGS. OVERRIDE
DURATION SHALL BE 30 MINUTES MAXIMUM.
A
O! 2 HOUROVERRIDE
INPUTA! ANALOG
AD ANALOG OUTPUT
BAS
BUILDING
y AUTOMA11ON SYSTEM
ASC APPLICATIONrr
81 BINARY
, ■ INPUT
BO BINARY OUTPUT
CSR CURRENT SENSING RELAY
r DAMPER Or
DPS, DIFFERENTIAL PRESSURE SENSOR
S DAMPER
VING SWITCH
EA EXHAUST AIR
■ ELECTRIC • HEATER
ENERGYEUH
ERV RECOVERY VENTILATOR
FIELDFEC EQUIPMENT CONTROLLER
GSHP GROUND SOURCE HEAT PUMP
HEATERGUH GAS UNIT
HILP HEAT PUMP Or. PUMP
IDH INLINE DUCT HEATER
rd
r r d•
:x a -. +r• � *•� r A rr r
,,,
F� ,r
r r � - ., .r r
y■
r -®
�rf-r r •� � • i,r
®•«. r •! ! r • d.i
'rr � •+� � •1 x r_ry
R
r fE 11 L4i
- i � r r.A r• ��ir r ,r
SEQUENCE PE TION
CONVENTIONS
1, UNLESS OTHERWISE NOTED THE FOLLOWING CONVENTIONS SHALL APPLY FOR ALL HVAC SYSTEM SEQUENCES OF OPERATION CONTAINED HEREIN.
. IF A SENSED CHANGE RESULTS IN A PRESCRIBED ACTION', THE OPPOSITE OF THE SENSED CHANGE SHALL RESULT IN THE OPPOSITE ACTION,
. OCCUPIED UNOCCUPIED SCHEDULING SET POINTS AND SET POINT ADJUSTMENT SHALL BE COORDINATED WITH THE OWNER SHORTLY AFTER CONSTRUCTION IS COMPLETE....
4. SPECIFIC DIAGNOSTIC MESSAGES, AT A MINIMUM, SHALL INCLUDE:
a. SENSOR FAILURE. (IDENTIFY SENSOR)
b. PUMP IN HAND OPERATION. (IDENTIFY PUMP)
c. PUMP FAILURE. (IDENTIFY PUMP')
d. OUT OF LIMIT FOR NORMAL SYSTEM OPERATION. (ALL SENSORS)
e; LOSS OF COMMUNICATION. (IDENTIFY COMPONENT)
5. ALL POINTS COMPLETE WITH GRAPHICS,
P ICS, SHALL BE ACCESSIBLE REMOTELY VIA. THE WEB WITHOUT ADDITIONAL SOFTWARE. ALL SET POINTS SHALL BE ADJUSTABLE THROUGH THE
BAS. PROVIDE HYSTERESIS FOR SET POINTS. TYPICAL SET POINTS SHALL BE AS FOLLOWS:
a. TYPICAL OCCUPIED SET POINT RANGE FOR ROOD TEMPERATURES IS 707 DB HEATING, 787 DB COOLING, AND 50' RH.
b. UNOCCUPIED SET POINT SHALL BE 66T OB HEATING, 82-F DB COOLING AND 50% RH.
c. TYPICAL ALARM RANGE: 6'F DB ABOVE OR BELOW SET POINT.
d'!. MINIMUM ON/OFF TIME: 5/10 MINUTES.
6. UPON DETECTION OF ELECTRICAL LOSS OF PHASE, PHASE REVERSAL, LOSS OF POWER, HIGH OR LOW VOLTAGE THE BAS SHALL STOP ALL MOTOR DRIVEN EQUIPMENT UNDER ITS
CONTROL. UPON RESTORATION OF ELECTRICAL LOSS, THE BAS SHALL ENABLE COMPONENTS TO RESUME (OPERATION IN STAGES, TO AVOID UNNECESSARY ELECTRICAL DEMAND
SPIKES.
7. PROVIDE BUILDING COLOR CODED FLOOR PLAN THERMOGRAPH ZONED BY HVAC EQUIPMENT. EQUIPMENT TAGS SHALL BE COORDINATED WITH THE OWNER SHORTLY AFTER
CONSTRUCTION IS COMPLETE.
. REFER TO SPECIFICATIONS FOR ADDITIONAL BAS PERFORMANCE REQUIREMENTS.
GROUND -SOURCE HEAT PUMP LOOP2/M200
1. EITHER PUMP SHALL BE SELECTABLE TO BE THE LEAD PUMP. BOTH PUMPS SHALL BE OFF UNTIL THERE IS A NEED FOR WATER FLOW FROM ONE OR MORE HEAT PUMPS_ THE
NUMBER OF HEAT PUMPS NEEDED TO INITIATE THE LOOP FLOW SHALL BE EASILY CHANGED BY THE OPERATOR. THE LEAD PUMP SHALL ALTERNATE WEEKLY. SHOULD THE LEAD
PUMP FAIL, THE STANDBY PUMP SHALL AUTOMATICALLY BE STARTED AND AN ALARM SHALL BE GENERATED TO INDICATE THAT THE LEAD PUMP HAS FAILED,
2. NONE OF THE HEAT PUMPS' COMPRESSORS SHALL BE ALLOWED TO ENERGIZE UNTIL WATER FLOW IN THE LOOP IS PROVEN VIA THE DIFFERENTIAL PRESSURE SENSOR, SHOULD
FOR SOME REASON THE LOOP SUPPLY TEMPERATURE DROP BELOW 507 OR RISE ABOVE 1057 DEGREES, ALL HEAT PUMP SHALL BE LOCKED OUT AND AN ALARM SHALL BE
GENERATED.
3. THE SYSTEM DIFFERENTIAL PRESSURE SHALL BE CONTROLLED BY MODULATING THE LEAD PUMP'S VARIABLE FREQUENCY DRIVE (VFD). THE END OF THE LOOP BYPASS 'VALVE.
SHALL BE MODULATED OPEN TO MAINTAIN THE SYSTEM SET POINT ONLY AFTER THE PUMP VFD HAS MODULATED DOWN TO ITS MINIMUM SPEED.
4. SYSTEM GRAPHIC DISPLAY:
a. OUTSIDE AIR TEMPERATURE AND HUMIDITY..
b. NUMBER OF HEAT PUMPS REQUIRED TO INITIATE LOOP FLOW.
c. HPR/S ENTERING/DISCHARGE WATER TEMPERATURES AND PRESSURES.
dr PUMP DISCHARGE WATER TEMPERATURE AND PRESSURE.
e, PUMP ON/OFF OVERRIDE SWITCH,
. PUMP VFD ENABLE/DISABLE„ SPEED, STATUS, AND FAULT. VFD SPEED..
g: PUMP ALTERNATE LEAD/LAG SWITCH.
h. VFD/BYPASS VALVE LOOP PRESSURE DIFFERENTIAL CONTROL SET POINT.
. SUPPLY WATER PRESSURE AT BYPASS VALVE.
j. BYPASS VALVE PRESSURE DIFFERENTIAL.
k. BYPASS VALVE POSITION.
ELECTRIC UNIT HEATER (EUH) - 3/M 0
1. UNLESS NOTED OTHERWISE, UNITS SHALE. BE CONTROLLED BY FACTORY INSTALLED INTEGRAL THERMOSTATS AND SHALL NOT BE CONTROLLED OR MONITORED BY THE BAS.
IA- UNIT HEATER ((HUH) y-4/M200
1. UNLESS NOTED OTHERWISE, THE UNIT SHALL BE CONTROLLED BY A WALL MOUNTED THERMOSTAT AND SHALL NOT BE CONTROLLED OR MONITORED BY THE BAS.
TEMPERATURE MONITORING - /
1. ANIMAL FREEZER TEMPERATURE: THE BAS SHALL MONITOR THE TEMPERATURE IN THIS COMPARTMENT. THE BAS SHALL GENERATE AN ALARM IF THE TEMPERATURE RISES
ABOVE THE USER —DEFINED SET POINTS. PROVIDE SYSTEM GRAPHIC DISPLAY SHOWING TEMPERATURE SENSOR AND ALARM SET POINT.
2. SYSTEM GRAPHIC DISPLAY
a, FREEZER TEMPERATURE..
LIGHTING CONTROL -6/M-900
1. THE BASS HALL CONTROL INDIVIDUAL LIGHTING CIRCUITS (EXTERIOR/INTERIOR, AS INDICATED ON THE PLANS) VIA LIGHTING RELAYS. EACH RELAY SHALL HAVE ITS OWN
OPERATING SCHEDULE ACCORDING TO BAS PROGRAMMING AND PHOTOCELL. LIGHTING RELAYS ARE TO BE PROVIDED BY THE BAS CONTRACTOR.
is
0
0
CV
iwwr LU 0
�—
C�)
IU
z LLI
2
[ �[I
■ x.. r .ter...0
CID
00
C"
_ 0 Pam-
E— _j C3? N
-
r
oo L