HomeMy WebLinkAboutCBPR-6-11-11304 STRUCTURAL ENGINEER COMMENTS & SKETCH.tif k t 6 i f � { Mintich � Structural Design Engineering PLLC Struc I nspections Home Inspections June 22, 2011 Catawba County Permit Center Attn: Donna Ketchersid Hickory, NC 28061 Ref: CBPR -6 -11 -11304 Mechanical Changes BB &T Newton, NC Dear Ms. Ketchersid, Mintich Engineering was requested by Beam Electric Company to evaluate the existing roof structure of the BB &T building at 12 N. Main Avenue in Newton, NC. The purpose of this review was to determine if the roof structure was capable of adequately supporting the installation of mechanical equipment to be used for climate control in the building. Existing building drawings were not available for review so a field inspection of the structure was performed. It was noted that the roof is in generally good condition and an existing water tower cooling unit is being removed as part of this project. The roof structure in the area to the north of the access hatch was accessed from the inside of the building and found to be constructed with bar joists capable of supporting the outdoor units identified as ACC -1, ACC -2, and ACC -3 in the Mechanical Notes & Schedules drawing (M0.0) by Elm Engineering. The location of these units is indicated in the sketch below. The installation of the other 2 units (ACC -4 & ACC -5) will utilize the existing water cooling tower support in conjunction with the load bearing wall adjacent to this area. This location is also shown in the sketch below. The units are to be supported by steel or wood stringers as shown below. The placement of any necessary blocking between the roof and the stringers shall be located at the bar joist (units ACC -1, ACC -2, ACC -3) or at the existing supports (ACC -4, ACC -5). The stringers for units ACC - 4 and ACC - 5 shall also bear across the full width of the load bearing wall. Appropriate measures shall be taken to protect or repair the membrane roofing material. 3213 Mountainbrook Road a Charlotte, NC 28210 a 704553 -9100 ■ mmintich@yahoo.com x Mi ntich Structural Design Engineering PLC Structural Inspections Home Inspections I I - - -- I EXISTING SUPPORT FOR O WATER COOLING TOWER ACC ACCESS HATCH { I O BEAR ON FULL WALL /I WIDTH WITH ROOFING MEMBRANE PROTECTION LOAD BEARING WALL C - AS REQUIRED. -; �' ✓ i�- ✓7 PP RT S TRIN GER -I io I SU 0 S NGER Acc Acc -z ACC-3 I I I I 4 0 ., 4._0.. 12'k)" I I EXISTING BAR JOISTS I I ..._ T , ............. r ,- , -_ —T.T .... _ i i DRIVE THROUGH ROOF BELOW Partial Roof Plan Thank you for allowing Mintich Engineering to assist in the roof evaluation for the installation of these units. Please feel free to call with any questions. Sincerely, �H CAg4 .ee* SEAS. 027 p►t A Mark Mintich, PE NC #027836 3213 Mountainbrook Road ■ Charlotte, NC 28210 ■ 704 - 553 -9100 ■ mmintich@yahoo.com