JUNE 14, 2011
PROJECT CONSTRUCTION MEMO (PLAN REVIEW COMMENTS)
NUMBER (RESPONSE TO CODE COMMENTS DATED 05- 25 -11)
DELIVERY: HAND DELIVERY - ONLY
PROJECT: AN NEW PROJECT FOR:
321 SHELL
HICKORY, NORTH CAROLINA
CONTRACTOR: DAVID E. LOOPER, INC
FROM: BARRY (CARD, AIA - MACKIE JOHNSON, ARCHITECT
TO: CATAWBA COUNTY
HICKORY DEVELOPMENT ASSISTANT CENTER
COPY TO: MATT WINTERS- DAVID E. LOOPER, INC
REFERENCE: REPLY TO REVIEW COMMENTS DATED 05 -25 -11
BUILDING STATUS: (COMPLETE - DISAPPROVED)
COMMENT #1: A written response to the comments in the order they appear in this
correspondence as well as appropriate clouded revisions to the plans shall
be provided.
(WE SHALL COMPLY)
COMMENT #2: Provide retaining wall design drawings prepared by the design
professional licensed in North Carolina.
(SEE ATTACHED)
ENVIRONMENTAL HEALTH STATUS: (N /A)
EROSION CONTROL STATUS: (UNDER REVIEW)
PAGE 1 OF 4
FIRE STATUS: (PLAN RECEIVED - APPROVED WITH NOTES)
BUILDING SHELL REVIEW ONLY
SPRINKLER/UTILITIES:
b
1. Consult with Hickory Public Utilities regarding if a Double Detector Check Valve
s assembly is approved for this Building to be used as Medical, revise plans if a
Reduced Pressure Zone Detector is required. If a RPZD is to be in a vault excess
water discharge drainage would need to be addressed to eliminat-- flooding of
monitoring equipment.
2. Location of FDC as shown noted, an approved sign shall be posted indicating the
location of the Fire Department Connection. Sign shall comply with Section 510
of the NC Fire Code.
3. All underground water mains, fire hydrants, and their appurtenances shall be
installed to meet the specifications of the Public Utilities Department and NFPA
Standard #24.
4. The Public Utilities Department shall inspect all underground water mains, fire
hydrants, and their appurtenances. Contact Paul Solomon or Raphael McRae at
323 -7427 for inspection requirements and procedures:
5. A flushing of all sprinkler run -ins shall be witnessed by a fire official and Public
Utilities. For fire inspection flushing requirements and procedures contact the Fire
Prevention Bureau at (828) 323 -7522.
ATTENTION: The sprinkler contractor shall verify that the flushing has been signed off
and approved by a Fire Code Official PRIOR to connection of the sprinkler riser to the
underground sprinkler run -in.
6. Sprinkler contractor shall obtain a permit from the Fire Prevention Bureau prior to
beginning any installation /renovation of the sprinkler /standpipe system. A copy of
submittal requirements and applications are available upon request, 828 -323-
7522 or available on line At
http: / /www.hickorygov.com/ department / /division.php ?fDD =8 -13
7. NFPA 13 2002 year is the applicable standard for sprinkler installation.
FIRE ALARM:
1. Location of remote annunicator noted just inside main entrance approved.
2. Location of master control panel for Area of Rescue Assistance noted.
3. Location of Knox Box approved, Knox Box ordering may be done by phone (1 -800-
552 -5669) or web site (knoxbox.com).
4. Fire alarm contractor shall obtain a permit from the Fire Prevention Bureau prior to
any installation of the fire alarm system. A copy of submittal requirements and
applications are available upon request, 828 - 323 -7522 or available on line at
hftp://www.hickorygov.com/department//division.php?fDD=8-13
5. Elevator Recall required by section 607 of the 2009 North Carolina Fire Prevention
Code. Heat and smoke detectors shall be provided for elevator shutdown and
recall according to NFPA 72.
6. A means shall be provided to supervise the electric heat (in the event of heater
failure) in the sprinkler riser room to maintain a minimum of 40 degrees to prevent
freezing of the sprinkler system.
7. NFPA 72 2002 is the applicable standard for fire alarm installation.
PAGE 2OF4
i
t
GENERAL COMMENTS:
Comment #1: Up -fit plans are to be submitted. The building or structure shall not be
occupied prior to the code official issuing a permit that indicates that applicable
provisions of the NC Fire Code has been met.(WE SHALL COMPLY)
Comment#2: Street numbers to be verified. Street numbers shall be posted on the
building and visible from the roadway. Numbers shall contrast with their
background. Numbers shall be a minimum of 4 inches high with a minimum
stroke width of 0.5 inches. (WE SHALL COMPLY)
1 Comment#3: Per NC Fire Code, Section 510, fire protection equipment rooms
containing controls for HVAC's, sprinkler risers, other fire detection control
I elements shall be identified for the use of the fire department with signs installed,
and readily visible. (WE SHALL COMPLY)
Comment#4: Portable fire extinguishers shall be selected, installed and maintained in
accordance with Section 906 of the 2009 North Carolina Fire Prevention Code
and NFPA 10. (WE SHALL COMPLY)
Comment#5: Construction and use of the building shall comply with the North
Carolina Building Code and North Carolina Fire Code. (WE SHALL COMPLY)
Comment#6: See 06 North Carolina Building Code Chapter 33 Safeguards During
Construction and sections of 09 North Carolina Fire Prevention Code Chapter 14
Fire Safety During Construction and Demolition that would be applicable to this
project. (WE SHALL COMPLY)
Please contact if assistance or questions regarding plan review comments:
Kelly Davis
Senior Fire Inspector
Hickory Fire Prevention Bureau
76 N. Center Street NE
Hickory, NC 28601
(828) 323 -7522 - phone (828) 323 -7476 - fax
kdavis @ci. hickory. nc. us
ZONING STATUS: (APPROVED WITH NOTES)
1. Double Detector Check Valve on FDC shall be changed to approved RPZ per State
standards.
2. North Carolina State permits required for all line extensions prior to utility construction
start.
3. Utility work shall be done by North Carolina licensed contractor approved by Hickory
Public Utilities Department.
4. 6 "x6" FDC @ $3,413.00
5. 2" domestic water @ $1,705.00 cap.only.
6. 4" sewer @ $3,032.00 capacity only.
7. Meter shall be Tru -Flow radio read meter to be purchased by developer and or
contractor.
8. Clean -out plug in driveway needs to be in traffic grade box.
9. Preconstruction meeting shall be held prior to utility construction start.
Hickory Zoning Review 05/10/2011 Approved with Notes Clara Coulbourne
a PAGE 3 OF 4
r
f
w
FIRST REVIEW
05/10/2011
(1) Setbacks shown on plan are from previous LDC. Shown setbacks meet current
setback standards.
(2) IND maximum height is 80ft. This property is also within the Airport Overlay District
where the
maximum height is 50ft. The building shown is less than 50 ft in height.
(3) Sheet C1 shows location of dumpster pad and indicates screening will be provided,
and references a
` plan detail, but detail is not included. Dumpster screening must conform to the
' standards of LDC Section
9.7.
(4) The eastern, western and southern boundaries of the parking area(s) are not
properly screened. Trees
must be planted 30ft on center (LDC Section 9.14.7 (B).
(5) This project is in a WS -IV (CA) Watershed. This project is being developed as Low -
Density.
Impervious calculations are shown in sheet C1.
(6) Phone, cable, electricity and like utility lines must be placed underground.
(7) All aspects of this project shall conform to the standards contained within Hickory's
Land
Development Code.
(8) All signs are permitted separately.
PLEASE REVIEW AND CALL IF YOU HAVE ANY QUESTIONS.
THANKS,
BARRY (CARD, AIA
MACKIE JOHNSON, ARCHITECT
ATTACHMENTS: FIVE SETS OF REVISED DRAWINGS ONLY
SITE RETAINING WALLS
STATEMENT OF SPECIAL INSPECTIONS
PAGE 4 OF 4
END OF PROJECT CONSTRUCTION MEMO NUMBER ONE
R Ax
ivtcGili
ASSOCIATES
i
Memo
To: Barry Icard, Mackie Johnson Architecture
From: Shad Walters, PE
CC: David E. Looper & Co.
File
Date: 6/6/2011
Re: Responses to City of Hickory comments
The following are responses for the items McGill Associates addressed. The comments were
from the Catawba County Permit Plan Review Notes.
Hickory Fire Prevention Bureau: Notes dated 5/12/2011:
Sprinkler/Utilities:
1. A Reduced Pressure Zone Detector has been added. See sheet #C4 for revised
vault/RPZ details.
2. Will comply to comments pertaining to FDC, see sheet C4.
3. Will comply, utilities will meet the specifications of the Public Utilities Department
and NFPA Standard #24., see sheet C4.
4. Will comply to Public Utility Department inspection requirements and procedures.
5. Will comply to flushing requirements and procedures, see sheet C4.
6. Will comply, sprinkler requirements.
7. Sprinkler design will comply with applicable standard.
Fire Alarm and General Comments to be addressed by others.