HomeMy WebLinkAboutELE2005-03219.tif P.O. Box 389 ELECTRICAL
Newton, NC 28658
PERMIT
Phone: (828)465 -8399
v 1�►� / Fax: (828)465 -8962 PERMIT NO.: ELE2005 - 03219
11/ APPLIED: 12114 /2005
Web Site: www.catawbacountyne.gov ISSUED: 12/14/2005
\8 a 2 Popular Pages /Online Permit Center EXPIRES: 06/14/2006
SITE ADDRESS: 420 N CENTER ST HICKORY NC
ASSESSOR'S PARCEL NO.: 370319614570
TYPE OF WORK: ALTERATIONS
TYPE OF USE: INSTITUTIONAL
BUILDING SO. FOOTAGE: sf
PHYSICAL DIRECTIONS: FRYE REGIONAL MEDICAL CENTER N CENTER ST
PROJECT DESCRIPTION: INTERIOR WIRING - CHANGING 3 ELEVATOR BREAKERS TO SHUNT
TRIP STYLE TIE INTO FIRE ALARM SYSTEM
OWNER /APPLICANT CONTRACTOR 1 CONTRACTOR 2
FRMC ELECTRIC SERVICE GROUP, INC.
420 N CENTER ST 212 2ND ST. N.W.
HICKORY NC 28601 HICKORY
SWT #6416
Electrical Fixtures Fees
Fixture Type Amps Quantity
Electrical wiring per tenant spac 1 Type By Date Amount
I
PRMT LHS 12/14/2005 $50.00
Total: $50.00
I
This permit is issued on the express condition that the above work shall conform in all respects to the statements certified to in the application for
such permit, and that all work shall be done in accordance with all applicable zoning, building, electrical, plumbing and mechanical ordinances of
the County of Catawba and the State of North Carolina.
A permit issued for work under this Code shall expire by limitations six months after the date of issuance if the work authorized (FOOTINGS ARE
CONSIDERED 1st INSPECTION ON NEW CONSTRUCTION) has not been commenced. If after commencement the work is discontunued for a
period of 12 months, the permit therefore shall expire.
* * *AN ADDITIONAL CHARGE PER TIE CURRENT FEE SCHEDULE MAY BE ASSESSED FOR EACH UNWARRANTED INSPECTION
SCHEDULED. * **
If there are any questions, please contact the office between 8:00a m. and 5:00p.m.
titrr'
�� � T /- 1i
fit/
(828) 465 -8399 Office Number Catawba County FAX CALL ❑ WITH ISSUED PERMIT #
(828) 465 -8962 Newton Fax Number Application for Permit TOT NUMBER (810 31,7 -7fM
(828) 322 -6814 Hickory Fax Number
www.catawbacountync.gov
(Please print or type) P.0 Box 389 Newton, NC 28658
�c0.Cc�,�'C �' 2.°��$ tit - 7•U5'
Type of Permi 1l 4ectrical ❑ Plumbing ❑ Mechanical ire Date VL-
Active Building / Mobile Home Permit # Property ID # (if known)
* If no active Building or Mobile Home permit please list driving directions from a major intersection:
Use of structure: ❑ Mobile Home ❑ Single family ❑ Multi family I& ommercial ❑ Industrial /Factory ❑ Church Owned ❑ Gov't Owned ❑ Accessory
Physical 911 Address of Project - Zt7 to , teu-rte 'SN
Owner or Business rr F`r�� C, Telephone IaLib • $ • SO-L
Address
Subcontractor '� ,�c �a� Q�� L > �o►o�,p Telephone t'Lib • 3'. Z • 2> k Lo
Address 'x..1'1. 'o," 4 SN N.\4 License # \-X
General Contractor N►tA Telephone
I
Design Professional Telephone
Address NC Reg #
ELECTRICAL (List each panel separately) Panel # 1 Amps Panel # 2 Amps Panel # 3 Amps Panel # 4 Amps
❑ New Building Wiring ❑ Pole Service ❑ Wire Mechanical unit only (No Svc Chg) Total#
❑ Additional Service (existing bldg) ❑ Service Change Amps ❑ Interior Wiring (No Service Change)
Imo' ❑ Addition of Sub Panel ❑ Load Control ❑ RV Servic
❑ Saw Service ❑ Mobile Home Other (Li
❑ Sign Service ❑ Modular Home S►�1v„Kt Q0.`@ S'��4�
❑ Service Repair Total Electrical Cost $ ad - t1t t wN%% I C,
PLUMBING S�tscfr(1
❑ Full or Partial Bath/Toilet Rooms. (Includes future.)
Total number being installed ❑ Gas Line /Pressure Test only
❑ Mobile home (new set -up only) ❑ Modular Home
❑ Water Heater (Electric, Gas) ❑ Other (List)
MECHANICAL (Check One ❑ New Installation ❑ Change out exiting system
❑ Heat Pump or Furnace with A/C Total #_ ❑ Gas Line/ Pressure Test ❑ Other (List)
❑ Furnace (Oil, Gas, or Electric) Total # _ ❑ Gas Logs Total # ❑ Mobile Home
❑ Air Conditioner Total # _ ❑ Unit Heater Total #
❑ Water Heater (Electric /Gas) Total # _ ❑ Modular Home
FIRE (Check permit type applicable)
❑ Fire Extinguishing System ❑ Compressed Gases ❑ Spraying & Dipping
❑ Fire Alarm /Detection System ❑ Hazardous Materials ❑ Standpipe Systems
❑ Fire Pumps & Related Equipment ❑ Industrial Ovens ❑ Temp. Membrane Structures
❑ Flammable & Combustible Liquids ❑ PVT Fire Hydrants ❑ Other
*"All fees entered by Permit Center, DOUBLE FEE charged for work started prior to obtaining permit. "The undersigned makes application for
permits and inspection of work described and agrees to comply with all applicable State, County codes and laws regulating the work.
PRINT NAM SIGNATURE \A
(Subcontractor) License Holder /Owner
I
12/09/2005 11:39 FAX 704 376 7072 MCCRACKEN & LOPEZ IM 001/004
McCracken
& Lopez, PA
Facsimile Transmittal
Consulting Engineers
1300 Baxter Street, Sulte 350
PA_ Box 32515 (28232)
Charlotte, North Carolina 28 2D4
Phone 704.376 -7072 Fax 704. 3764465
generaldeliveryQrnwmck enlopez_ccm
Date: 1 /JS To: p o r J D f(.J 1 e
Projaer. 1� (t-M G E t- ev kTL- e_ S ►ku -3 ; T+u N company: E t- e e.T R-c S S 01- v
Project No.: ?i0 3 . ° 3 ? . 1 Fax: V1 — 1 S'
p of Pages; From:
Urgent ✓ For Review Please Reply
Distribution:
i
i
c�Re t Pr C-
UL
1< 5
N o I rte- LC rL
Q- j L
a
art. u s r t3C- (,j I riv a 2 ` 1JF SP& tiuc
C r c �T `
P �f m I M F2J wt. i3(j rvi� TAI u $ sP'L
�alu�Pr«'4T Pldo tl W r Z `cjF ACL_ At
iM /i- cTVil,, �
If you have any difficulties receiving this fax or have received this fax is error, please notify us immediately.
RECEIVED TIME DEC. 9_ 11 :AAnm DDTAIT 'rTMn __..
12/09/2005 11:39 FAX 704 376 7072 MCCRACKEN & LOPEZ 16002 /004
ELEVATORS AND CONVEYING SYSTEMS 3005.3.2 — 3006.6
(o - l S 4
comply with ASME 'B20.1. hoistway e .
30053.1 Enclosure. Conveyors and related equipment
(3i3 7 600 0 06. 1 .Shunt trip.• Where elevator hole ys or elevator
connecting successive floors or levels shall be enclosed- machine rooms containing elevator contr 1 equipment are
with fire barrier walls and approved opening protectives protected with automatic sprinklers, a m installed th
complying with the requirements of Section 3002 and accordance with NFPA 72; Section,' Elevetor
Chapter 7. Shutdown, :shall be provided to disconnect autotnatitlly the
main line.'power supply to the affecied elevator ad
3005.3.2 Conveyor safeties. Power - operated conveyor , prior' to die, application of water. This means shall not be self -
belts and other material- moving devices shall be resetting. The activation of sprinklers outside the hoistway
with automatic limit switches which will shut off th or machine room shall not disconnect the main line power
power in an emergency and automatically stop all opera-
tion of the device.
3006.6 Plumbing system& Plumbing systems shall not be
3005A Personnel and material hoists. Personnel and mate- located in elevator equipment rooms.
rial hoists shall be designed utilizing an approved method
that accounts for the conditions imposed during the intended
operation of the hoist device. The design shall include, but is
not limited to, anticipated loads, structural stability, impact,
vibration, stresses and seismic restraint. The design shall
! account for the construction, installation, operation and
inspection of the hoist tower, car, machinery and control
equipment, guide members and hoisting mechanism.
Additionally, the design of personnel hoists shall include,pro-
visions for field testing and maintenance which will demon -
strate that the hoist device functions in accordance with the
j design. Field tests shall be conducted upon the completion of
an installation or following a major alteration of a personnel
hoist.
SECTION 3006
MACHINE ROOMS
3006.1 Access. An approved means of access shall be pro-
vided to elevator machine rooms and overhead machinery
spaces.
j 3006.2 Venting. Elevator machine rooms that contain solid-
i state equipment for elevator operation shall be provided with
an independent ventilation or air- conditioning system to pro -
sect against the overheating of the electrical equipment. The
{ system shall be capable of maintaining temperatures within
the range established for the elevator equipment.
3006.3 Pressurization. The elevator machine room serving w,
a pressurized elevator hoistway shall be pressurized upon
activation of a heat or smoke detector located in the elevator i
machine room_
3006.4 Machine rooms and machinery spaces. Elevator
machine rooms and machinery spaces shall be enclosed with
"i.r✓ construction having a fire- resistance rating not less than the
required rating of the hoistway enclosure served by the
machinery. Openings shall be protected with assemblies hav-
ing a fire- resistance rating not less than that required for the
2 . - PRINT TIME DEC. 9. 11: 46RM 647
0
12/09/2005 11:39 FAX 704 376 7072 MCCRACKEN & LOPEZ 1a003/004
PROTECTED PREMISES FIRE ALARM SYSTEMS 72 -55
(1) The smoke detector or other automatic fire detection as 6.15.5.4 If the fire alarm control unit actuates the HVAC sys-
permitted by 6.15.3.7 located in the designated elevator tem for the purpose of smoke control, the automatic alarm -
recall lobby shall actuate the first elevator control circuit. initiating zones shall be coordinated with the smoke-control
In addition, if the elevator is equipped with front and rear zones they actuate.
doors, or if the elevator machine room is located at the 6.Ib.5.5 Where interconnected as a combination system, a
designated level, the required smoke detectors shall actu-
ate the first elevator control circuit. The smoke detectors Firefighter's Smoke Control Station (FSCS) shall be provided
or other automatic fire detection as permitted by 6.15.3.7 to perform manual control over the automatic operation of
1 in both lobbies at the designated level shall acruate the the system's smoke control strategy.
first elevator control circuit. 6.15.5.6 Where interconnected as a combination system, the
(2) The smoke detectors or other automatic fire detection as smoke control system programming shall be designed such
permitted by 6.15.3.7 in the remaining elevator lobbies that normal HVAC operation or changes do not prevent the
shall actuate the second elevator control circuit intended performance of the smoke control strategy.
(3) The smoke detectors or other automatic fire detection as
permitted by 6.15.3.7 in elevator hoistways and the eleva- 6.15,6 Door Release SeMce.
for machine room (s) shall actuate a third elevator control 6.15.6.1 The provisions of 6.15.6 shall apply to the methods of
circuit connection of door hold-open release devices and to integral
( Elevator Shutdown. door hold-open release, closer, and smoke detection devices.
5.4.1* Where heat deuccors aze used m shut down elevator 6.15.6.2 All detection devices used for door hold -open re-
wer prior eo sprinkler operation, the detector shall have ease service shall be monitored for integrity in accordance
th 4.4.7.
h a lower temperature rating and a higher sensitivity as
pared to the sprinkler. Exception: Smoke deuctors used only for door release and not Jor open
5.4.2 If heat detectors are used to shut down elevator area protection.
er prior co sprinkler operation, they shall be placed within 6.15.6.3 All door hold-open release and integral door release
mm (2 ft) of each sprinkler head and be installed in actor. and closure devices used for release service shall be monitored
ce with the requirements of Chapter 5. Alternatively, engi- for integrity in accordance with 6.15.2.
ering methods, such as specified in Annex B, shall be per- 6.15.6.4 Magnetic door holders that allow doors to close
tted to be used to select and place heat detectors to ensure upon loss of operating power shall not be required to have a
ponse prior co any sprinkler head operation under a•ariery secondary power source.
fire growth rate scenarios.
6,15,4.3 If pressure or waterflow switches arc used to shut 6.15.7 Door Unlocking Devices.
down elevator power immediately upon or prior to the dis- 6.15.7.1 Any device or system intended to actuate the locking
charge of water from sprinklers, the use of devices with time- or unlocking of exits shall be connected to the fire alarm sys-
delay switches or time -delay capability shall not be permitted_ tern serving the protected premises.
6.15.4.4* Control circuits to shut down elevator power shall be 6.15.7.2 All exits connected in accordance with 6.15.7.1 shall
monitored for presence of operating voltage. Loss of voltage unlock upon receipt of any fire alum signal by means of the
to the control circuit for the disconnecting means shall cause fire alarm system serving the protected premises.
a supervisory signal to be indicated at the control unit and Exception: Wherr adwrwire rrquiird or permitted by the authority
required remote annunciators. having jtsrisdiciion or other codes.
.15.4.5 The initiating devices described in 6.15.4.2 and 6.15.7.3 All exits connected in accordance with 6.15.7.1 shall
6.15.4.3 shall be monitored for integrity by the control u unlock upon loss of the primary power to the fire alarm system
quired in 6.15.3.1 and 6.15.5.2. serving the protected premises_ The secondary power supply
shall not be utilized to maintain these doors in the locked
6.15. yste condition.
6.15.5.1 The provisions of 6.15.5 shall apply to the basic 6.15.7.4 If exit doors are unlocked by the fire alarm system,
method by which a fire alarm system interfaces with the HVAC the unlocking function shall occur prior to or concurrent with
systems. activation of any public-mode notification appliances in the
6.15.5.2 If connected to the fire alarm system serving the area (s) served by the normally locked exits.
protected premises, all detection devices used to cause the 6.16" Special Requirements for low Power Radio (Wireless)
operation of HVAC systems smoke dampers, fire dampers, fan Systems.
control, smoke doors, and fire doors shall be monitored for 6,16.1" gM
Requirements. p
. Com Hance with Section 6.16
integrity in accordance with 4.4.7. shall require ttue use of low -power radio equipment 5pecifi-
6.15.5.3 Connections between fire alarm systems and the tally listed for the purpose.
HVAC system for the purpose of monitoring and control shall 6.16.2 Power Supplies. Aprimary battery (dry cell) shall be per-
operate and be monitored in accordance with applicable mitted to be used as the sole power source of a lot -power radio
NFPA standards. Smoke detectors mounted in the air ducts of rr,,,Q„,; where all of the following conditions are met
HVAC systems shall initiate either an alarm signal at the pro.
tcctcd premises or a supervisory signal at a constantly attended (1) Each transmitter shall serve only one device and shall be
location or supervising station. individually identified at the receiver /control unit.
2002 Edition
RECEIVED TIME DEC. 9. 11 :44AM PRINT TIME DEC. 9. 11 :46AM
12/09/2005 11:40 FAX 704 376 7072 MCCRACKEN & LOPEZ 1a004/004
a�
Rule 101,"ule 102.2 ASME A17.1a -1997
(a) Ropes and sheaves leading to the remote ma- ing conductors installed in the hoistway shall not
chine room that penetrate separate fire - resistive areas interfere with the operation of the elevator.
of the structure shall be fully enclosed and conform
to Rule 100.1a.
(b) Rope and sheave enclosures leading to the
remote machine room shell be protected against
unauthorized access. Rule 102.2 Installation of Pipes or Ducts
(c) Permanent means of access shall be provided Conveying Gases, Vapors, or Liquids In
to the enclosures for inspection, repair, and mainte- Hoistways, Machine Rooms, or
nance of hoist ropes passing over sheaves and any Machinery Spaces
deflecting, overhead, and secondary sheaves that are
not located in the hoistway or remote machine room. ( Steam and hot water pipes are permitted to
Access doors to these enclosures shall be provided be installed in hoistways, machine rooms, and ma-
at each sheave location conforming to Rule 101.3d. chinery spaces for the purpose of heating these areas
Access openings shall be provided for inspection only, subject to the following.
and maintenance of hoist ropes passing over sheaves (1) Heating pipes shall convey only low pressure
and conform to Rule 101.3d. A stop switch meeting steam 15 psi (34 kPa) or lessl or hot water 1212 °F
the requirements of Rule 210.2(e), a permanent elec- (100 °C) or less).
tric outlet, light switch, and light shall be provided (2) All risers and return pipes shall be located
in the enclosures immediately inside the access doors outside the hoistway.
� (3) Traps and shutoff valves shall be provide
and openings.
(d) A permanent means of communication be-
in accessible locations outside the hoistway.
tween the elevator car and remote machine room (b) only ducts for heating, cooling, ventilating, and
and or control room shall be provided. venting these spaces are permitted to be installed
in the hoistway, machine room, and machinery space.
G t`� (c) Standard sprinkler protection conforming to the 19"] requirements of ANSUNFPA 13 shall be permitted to
Ai>lc �/1�c be installed in these spaces, subject to the fallowing.
(1) All risers and returns shall be located outside
r SECTION 102 these spaces.
(2) Branch lines in the hoistway alaiii9mo l
ELECTRICAL EQUIPMENT, WIRING, PIPES, t h evel.
AND DUCTS IN HOISTWAYS AND (3) eans s all be provided to automatically 19s
MACHINE ROOMS disconnect the main line power supply to the affected 197a
elevator upon or prior to the application of water
te5bi Rule 102.1 Installation of Electrical Equipment and from sprinklers located ' e machine room or in
Wiring in Ho'tstways and Machine th tha ft (610 mm) above the it
Rooms 0 1 e evator
All electrical equipment and wiring shall confor control and shall not be self - resetting. The activation
to the requirements of ANSUNFPA 70. of sprinklers outside of the hoistway or machine room
Only such electrical wiring, raceways, and cable shall not disconnect the main line power supply.
used directly in connection with the elevator, inclu - (4) Smoke detectors shall not be used to activate
ing wiring for signals, for communication with t spri klers in these spaces or to disconnect the main
car, for lighting, heating, air conditioning, and vent
lating the car, for fire - detecting systems, for pit sump (5) When sprinklers are installed in the hoistway, t9 l
pumps, and for heating and lighting the hoistway all electrical equipment, except earthquake protective
and /or the machine room, may be installed inside devices conforming to the requirements of Rule j
the hoistway and /or the machine room. 2409.1b(4), located less than 4 ft (1219 mm) above
Bonding conductors from the lightning protection the pit floor shall be:
system grounding down conductor to long vertical (a) weatherproof (NEMA4); and
metal bodies in the hoistway such as elevator rails IN wiring shall be identified for use in wet
and vertical wireways, shall be permitted to be in- locations in accordance with the requirements in
stalled in the hoistway as required by NFPA -780. The ANSUNFPA 70.
lightning protection system grounding down conduc- es or ducts conveying gases, vapor ,
for shall not be permitted in the hoistway, and the or liquid and not used in connection with the opera-
elevator rails shall not be used as the lightning tion of the elevator shall not be installed in any
protection system grounding down conductor. Bond- hoistway, machine room, or machinery space.
28