Loading...
HomeMy WebLinkAboutCBPR-5-11-10710 WILLIAM SONOMA LIGHTING ARCHITECT COMMENTS.tif David E. Canup, P.E. 7953 Stage Hills Blvd., Suite 107 Bartlett, TN 38133 t P:901- 379 -9762 F: 901- 379 -9763 May 11, 2011 Catawba County Plan Review 76 N. Center Street Hickory, NC 28601 Att: Mr. James Lamb Re: 2973 Kelly Blvd. Claremont, NC Dear Mr. Lamb, We received your code comments for the above referenced project and offer the following responses: 1. Revised drawing E4.1 with the revisions clouded has been submitted with these responses. 2. It is our opinion that this facility meets the requirements of the following paragraphs of the 2008 National Electrical Code: 230.2.132 and C1. The facility is large and warrants a second service to the facility. Also, the load for the facility exceeds 2000 amps. A plaque will be provided as required in 230.2.C. 3. Plans have been modified to indicate that the conductor and conduit sizes were based on TI II IN / TIIWN and EMT conduit except at the service where PVC conduit is being utilized. 4. Panel LVFRS has a 225/3 main circuit breaker and is within 10' of the transformer that feeds it. 5. We clarified that panel HV WP is a double section panelboard. 6. New panel installations will comply with NEC article 110.26 for proper working clearances. If you have any questions or comments regarding these responses, please feel free to give me a call. Thank you j D C0�I� David E. Canup, P.E. MAY 201111.