HomeMy WebLinkAboutm_1MECHANICAL SPECIFICATIONS
GENERAL CONDITIONS: THE GENERAL CONDITIONS OF THE CONSTRUCTION CONTRACT AND SUPPLEMENTAL
GENERAL CONDITIONS BOUND WITH THE ADVERTISEMENT FOR BIDS, INSTRUCTIONS TO BIDDERS AND BID FORMS
APPLY TO ALL CONTRACTS AND ARE HEREBY MADE A PART OF THE MECHANICAL CONTRACT SPECIFICATIONS.
DESCRIPTION OF WORK: FURNISH ALL LABOR, SUPERVISION, MATERIALS, EQUIPMENT AND TOOLS NECESSARY
TO INSTALL COMPLETE AIR CONDITIONING SYSTEMS IN THE BUILDING.
DRAWINGS: THE CONTRACTOR SHALL FURNISH AND INSTALL ALL EQUIPMENT AND MATERIALS SHOWN IN THESE
DRAWINGS AND DESCRIBED IN THESE SP€CiFICATIONS. ALL MISC ELLANEOUS MATERIAL AND HARDWARE NECESSARY
FOR COMPLETE OPERATING SYSTEMS IN ACCORDANCE WITH GOOD TRADE PRACTICE AS IS OBVIOUSLY INTENDED
SHALL BE FURNISHED AND INSTALLED AS THOUGH IT WERE SPECIFICALLY LISTED.
ELECTRICAL WORK: THE ELECTRICAL CONTRACTOR SHALL TAKE POWER FROM THE SOURCE AS CALLED FOR ON THE
ACCOMPANYING DRAWINGS AND EXTEND THROUGH ELECTRICAL AND NECESSARY CONTROLS TO THE EQUIPMENT
FURNISHED AND INSTALLED UNDER THIS CONTRACT. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL WIRING
FROM THE LOAD SIDE OF THE DISCONNECT THROUGH THE STARTER TO THE EQUIPMENT.
SEE ELECTRICAL PLANS FOR DEFINITION OF WIRING AND ELECTRICAL FACILITIES TO BE INSTALLED UNDER THE ELECTRICAL
CONTRACT.
ALL ELECTRICAL WORK SHALL BE DONE BY OR UNDER THE DIRECT SUPERVISION OF A LICENSED ELECTRICIAN,
LICENSED IN THE STATE WHERE THE WORK WiLL BE PERFOMRED. ALL ELECTRICAL WORK SHALL BE IN ACCORDANCE
WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND ALL ADDENDA THERETO.
ALL CONTROL VOLTAGE SHALL BE SINGLE PHASE, 120 VOLTS OR LESS AND SHALL FEED FROM ONE (1) THERMAL
OVERLOAD TYPE TOGGLE BREAKER
ALL CONTROL WIRING SHALL BE RJN IN CONDUIT.
ALL STARTERS SHALL BE FURNISHED BY THE MECHANICAL CONTRACTOR AND INSTALLED BY THE ELECTRICAL
CONTRACTOR-
THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CONTROL AND INTERLOCK
WIRING 120 VOLTS AND LESS.
SEISMIC RESTRAINT - THIS BUILDING IS IN SEISMIC DESIGN CATEGORY (DESIGNER TO DETERMINE A, B, C OR D). ALL
EQUIPMENT, DUCTWORK AND PIPING FURNISHED AND INSTALLED UNDER THIS CONTRACT SHALL BE SEISMICALLY
Thermal Zone a
DRIVE SLIPS
RESTRAINED AS REQUIRED BY CHAPTER 16, STRUCTURAL DESIGN, IN THE NORTH CAROLINA BUILDING CODE, 2002
Exterior design condition
'I' -10" CENTERS
EDITION. SPECIFIC ATTENTION SHALL BE GIVEN TO SECTION 1621, ARCHITECTURAL, MECHANICAL AND ELECTRICAL
winter dry bulb 18' F
DRIVE SLIPS
COMPONENT SEISMIC DESIGN REQUIREMENTS, AND TO TABLE 16213, MECHANICAL AND ELECTRICAL COMPONENTS
93' F DBl14'
F WB
COEFFICIENTS. THE MECHANICAL CONTRACTOR SHALL INCLUDE IN HIS /HER BID PRICE THE COST TO ACCOMPLISH ALL
summer dry bulb
REQUIREMENTS OF THE AFOREMENTIONED CODE_
Interior deafen condition
I' -10" CENTERS
winter dry bulb �5' F
20
SHEET METAL WORK: THIS CONTRACTOR SHALL FURNISH ALL DUCTWORK AND ASSOCIATED SHEET METAL
summer dry bulb 18' F
WORK AS CALLED FOR ON THE DRAWINGS AND REQUIRED FOR A COMPLETE DUCTED AIR DISTRIBUTION SYSTEM.
4' -0" CENTERS
relative humid(ty 509.
20
DUCTWORK SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE WITH BEST PRACTICES OF SHEET METAL
Building heating loa 8.9 MBH
WORK AND SMACNA STANDARDS.
Building cooling loa 12.1 MBH
S -CLEAT
ALL DUCTWORK SHALL BE GALVANIZED SHEET IRON THROUGHOUT EXCEPT WHERE OTHERWISE SHOWN AND
Mechanical Spacing Conditioning System
DRIVE SLIPS
FABRICATED IN ACCORDANCE WITH THE FOLLOWING TABLE (ALL DUCT SIZES ON CONTRACT DRAWINGS ARE SHEET
Unitary
PACKAGED TERMINAL HEAT PUMP
METAL FABRICATION SIZES EXCEPT WHERE LINER IS REQUIRED):
description of unit
heating efficiency
SEE SCHEDULES
cooling efficiency
SEE SCHEDULES
nit
heat output of unR
SEE SCHEDULES
THE FOLLOWING CHART IS BASED ON P W.G. (MAXIMUM) STATIC, POSITIVE OR NEGATIVE PRESSURE. SEE SMACNA
cooling output unit
SEE SCHEDULES
MANUAL FOR DUCT CONSTRUCTION FOR HIGHER STATIC PRESSURES.
boiler
total boiler output. If oversized, state reason.
TRANSVERSE
N/A
MAXIMUM DIMENSION GAUGE
OF DUCT U.S. STD.
JOINT
UP TO 12"
26
DRIVE SLIPS
I I
I I I
'I' -10" CENTERS
13" TO 30"
24
DRIVE SLIPS
_ -J
L- L_r I
I
1' -10" CENTERS
31 TO 40 "
22
DRIVE SLIPS
i I I
I' -10" CENTERS
41" TO 60"
20
STANDING SEAM
ANGLES
s
4' -0" CENTERS
61" TO 84"
20
1 -1/2" STANDING
ANGLES
S -CLEAT
DRIVE SLIPS
4' -0" CENTERS
BRACING
NONE
I "XI "XI 18" ANGLES
4 FEET FROM JOINT
1 "X1 "X118" ANGLES
4 FEET FROM JOINT
1 -In "XI -1/2 "x1/8"
4' -0" CENTER/CENTER
1- 1/2 "Xi -1//2 "XI /8"
2 FEET FROM JOINT
DUCTMATE INDUSTRIES, INC. SYSTEMS MAY BE USED FOR TRANSVERSE JOINTS WITH THE
FOLLOWING LIMITATIONS:
SYSTEM "25" - SHEETMETAL GAUGES 22 THROUGH 26
SYSTEM "35" - SHEETMETAL GAUGES 18 THROUGH 24
SYSTEM "45" - SHEETMETAL GAUGES 14 THROUGH 20
MANUFACTURER'S RECOMMENDATIONS SHALL BE FOLLOWED WITHOUT EXCEPTION,
ALL DUCTS SHALL HAVE FLAT LOCK TYPE LONGITUDINAL SEAMS CONFORMING TO SMACNA STANDARDS.
ALL DUCTS SHALL HAVE SECTIONS "GROSS- BROKEN" AND SHALL BE INSTALLED WITH NECESSARY STIFFENERS TO
INSURE DUCTS AGAINST VIBRATING OR BREATHING.
DUCT SUPPORTS
ROUND DUCTS - DUCTS UP TO 26" IN DIAMETER - ONE (1) STRAP AND BAND 1" WIDE BY IS GAUGE, MAXIMUM
SPACING 8' -0 ". DUCTS OVER 26" IN DIAMETER- A 1 WIDE BY 16 GAUGE BAND AND TWO 3/8" HANGER RODS,
MAXIMUM SPACING V -0
RECTANGULAR DUCTS - DUCTS UP TO 24" WIDE - TWO (2) STRAPS, P WIDE BY 18 GAUGE, MAXIMUM SPACING 8' -0 ".
DUCTS OVER 24" WIDE - TRAPEZE TYPE HANGER WITH ANGLE IRON AND TWO (2) RODS PER SMACNA MANUAL. DO
NOT USE ANGLE LESS THAN 1 "x 111/2 "x 1/8" OR RODS LESS THAN 3/8 ", EVEN THOUGH SMALLER SIZES MAY BE
ALLOWED IN THE SMACNA TABLES. SIZES GIVEN ABOVE DO NOT ALLOW FOR EXTERNAL LOADS OTHER THAN
INSULATION, NORMAL REINFORCEMENT < TRAPEZE WEIGHT. SMACNA TABLES SHALL BE USED WHEREVER SMACNA
REQUIREMENTS ARE MORE STRINGENT THAN LISTED ABOVE. ALL STRAP AND ROD FASTENERS SHALL BE LOAD
RATED. ALL HANGERS SHALL BE PROPERLY SECURED TO THE BUILDING STRUCTURE AS DETAILED IN THE
SMACNA MANUAL.
UNLESS OTHERWISE SPECIFIED, FURNISH AND INSTALL ALL NECESSARY LINTELS, PROPERLY SIZED, SHEET METAL
SLEEVES AND ESCUTCHEON COLLARS WHERE DUCTWORK RISES THROUGH FLOORS OR PASSES THROUGH WALLS
OR CEILINGS.
MANUAL VOLUME CONTROL DAMPERS IN ROUND BRANCH DUCTS TO DIFFUSERS OR GRILLES SHALL BE FACTORY
FABRICATED AND EQUAL TO YOUNG REGULATOR CO. SERIES 5020 WITH MODEL 403 LOCKING LEVER
REGULATOR FOR UN- INSULATED DUCT, AND MODEL 44315 FOR INSULATED DUCT.
MANUALVOLUME CONTROL DAMPERS IN RECTANGULAR BRANCH DUCTS SHALL BE FACTORY FABRICATED AND
EQUAL TO YOUNG REGULATOR CO. SERIES 620 WITH MODEL 403 LOCKING LEVER REGULATOR FOR UN- INSULATED
DUCT, AND MODEL 4435 FOR INSULATED DUCT.
VOLUME EXTRACTORS EQUAL TO TUTTLE t BAILEY, MODEL AVLR, SHALL BE USED AT BRANCH DUCTS WHERE
RADIUS TAKEOFFS AND SPLITTER DAMPERS ARE NOT USED.
FURNISH AND INSTALL FLEXIBLE COLLARS IN THE DUCTWORK CONNECTIONS TO AIR HANDLING FANS TO PREVENT
NOISE TRANSMISSION BETWEEN SECTIONS. FABRIC SHALL BE VENTGLAS AS MANUFACTURED BY VENTFASRICS.
CHANGES IN DUCT DIRECTION SHALL BE ACCOMPLISHED BY LONG RADIUS ELBOWS. MITERED ELBOWS SHALL
HAVE AIRFOIL TURNING VANES EQUAL TO TUTTLE t BAILEY "DUCTURNS ".
chi I ler
total chiller capacity. If oversized, state reason.
N/A
List equipment efflciencfee N/A
Equipment schedules with motors (mechanical systems)
motor horsepower SEE SCHEDULES
number of phases SEE SCHEDULES
minimum erffcfency PER NEMA STD MG I -1958. TABLES 12 -10 E it
motor type ODP
• of poles 4
DESIGNER STATEMENR:
To the best of In knowledge and belief, the design of this building complies
with the mechanical systems, service systems and equipments of the
North Carolina State Buf ding Gode, volume X- Energy.
SIGNED-
NAME- DONALD R ERITTAIN
TITLE: PROFESSIONAL ENGINEER
PIPING:
CONDENSATE DRAIN PIPING: CONDENSATE DRAIN PIPING SHALL BE TYPE "L" HARD DRAWN COPPER PIPING WITH
CAST AND /OR WROUGHT COPPER FITTINGS PER ASTM 8 -88, 95/5 SOLDER
NAME PLATES AND IDENTIFICATION: THIS CONTRACTOR SHALL FURNISH AND INSTALL NAME PLATES WITH
ENGRAVED LETTERING TO IDENTIFY EACH ITEM OF EQUIPMENT, SWITCHES AND CONTROLS INSTALLED UNDER THIS
CONTRACT.
NAME PLATE IDENTIFICATION SHALL CORRESPOND WITH IDENTIFICATION OF EACH PIECE OF EQUIPMENT ON THE
CONTRACT DRAWINGS UNLESS OTHERWISE DIRECTED. NAME PLATES AND /OR IDENTIFICATION SHALL BE MADE AS
MANUFACTURED BY SETON NAME PLATE COMPANY OR APPROVED EQUAL. NAME PLATES SHALL BE ENGRAVED
RIGID PHENOLIC PLASTIC OR NONFERROUS METAL WITH 1/4 INCH HIGH LETTERING - "TAPEWRITER" LABELS WILL NOT
BE ACCEPTED.
EACH AIR HANDLING UNIT SHALL BE IDENTIFIED WITH ITS CONTRACT DRAWING DESIGNATION AND THE AREA SERVED.
OPERATING INSTRUCTIONS CERTIFICATES AND WARRANTIES: THE ORIGINAL OF ALL INSPECTION
CERTIFICATES SHALL BE DELIVERED TO THE OWNER AND ONE (1) COPY EACH TO THE ENGINEER PRIOR TO
REQUEST FOR FINAL PAYMENT.
THREE (3) COPIES OF OPERATING AND MAINTENANCE INSTRUCTIONS AND MANUFACTURER'S WARRANTIES FOR ALL
EQUIPMENT PROVIDED UNDER THIS CONTRACT SHALL BE PROVIDED TO THE OWNER PRIOR TO SUBMITTING
REQUEST FOR FINAL PAYMENT.
PRIOR TO FINAL PAYMENT TO THE CONTRACT, THE CONTRACTOR SHALL BE RESPONSIBLE TO TRAIN THE AUTHORIZED
PERSONNEL ON HOW TO SERVICE, START -UP AND SHUT -DOWN THE VARIOUS SECTIONS OF THE SYSTEM. UPON
COMPLETION OF THIS PHASE OF THE CONTRACT, THE CONTRACTOR SHALL SECURE A LETTER OF ACCEPTANCE FROM
THE OWNER THAT HE IS SATISFIED WITH THE CONDITIONS STIPULATED HEREIN. UPON ACCEPTANCE OF THIS
LETTER AND AT THE DISCRETION OF THE ENGINEER, THE FINAL PAYMENT WILL BE MADE.
THE CONTRACTOR SHALL PROVIDE A WRITTEN GUARANTEE OF ALL MATERIALS AND WORKMANSHIP FOR A PERIOD OF
ONE (U YEAR FROM DATE OF SYSTEM ACCEPTANCE.
MECHANICAL SYSTEMS, SERVICE SYSTEMS AND EQUIPMENT
METHOD OF COMPLIANCE
Prescriptive! EnergU Cost Budget
0
I I
I i
I I
I I
O
I I
I J
t- 2 —r --
° 48/24
THE WORK UNDER THIS CONTRACT WILL BE ACCEPTED ONLY AS AN ENTIRE SYSTEM UPON SATISFACTORY
COMPLETION OF THE REQUIRED TESTS. NO PARTIAL ACCEPTANCE OF ANY PART OR PORTION OF APPARATUS WILL
BE MADE.
INSTALL AND CONNECT ALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS AND DO
ALL WORK IN A NEAT AND WORKMANLIKE MANNER AND IN ACCORDANCE WITH ACCEPTED GOOD PRACTICE AS
JUDGED BY THE ENGINEER
ALL EQUIPMENT ANA PIPING SHALL BE SO INSTALLED THAT NO OBJECTIONABLE NOISES FROM EQUIPMENT,
PIPING OR AIR DISTRIBUTION ARE AUDIBLE IN THE FINISHED AREAS.
GUARANTEE: THIS CONTRACTOR SHALL GUARANTEE ALL MATERIALS, EQUIPMENT AND WORKMANSHIP FOR
ONE (1) YEAR FOLLOWING FINAL INSPECTION AND ACCEPTANCE OF THE BUILDING BY THE ENGINEER AND
OWNER THIS APPLIES TO ALL MATERIALS AND EQUIPMENT INSTALLED UNDER THIS CONTRACT, REGARDLESS OF
SOURCE.
THE ONE (1) YEAR GUARANTEE PERIOD WILL START ON THE DAY OF FINAL INSPECTION AND ACCEPTANCE BY THE
OWNER. THE CONTRACTOR SHALL PROVIDE THE ENGINEER A LETTER WITH TWO (2) COPIES STATING THE:
BEGINNING AND ENDING DATES OF THE GUARANTEE BASED ON THE AFOREMENTIONED STARTING DATES.
EXTENDED GUARANTEE: PROVIDE AN ADDITIONAL FOUR (4) YEAR GUARANTEE ON ALL COMPRESSORS
BEYOND THE ABOVE MENTIONED ONE (1) YEAR GUARANTEE PERIOD.
STOR. W.
�3
EXISTING EXHAUST FANS IK TCHEN
TO REMAIN — 46/24 DUCT UP IN DROP CEILING
— /
AREA TO ABOVE CORRIDOR
u
0
I
I
r =i__-
I I
I I I
I I I
I I I
I I I
L 0
_ -J
L- L_r I
I
I
i I I
I I I
lXY
s
NEW
I COOLER
ALL JOINTS SHALL BE SEALED PER 603.9 (NORTH CAROLINA 2006 MECHANICAL CODE) AND 80328 (NORTH CAROLINA
ENERGY CODE). HOWEVER PRESSURE SENSITIVE TAPE SHALL NOT BE THE ONLY METHOD OF SEALANT.
I
I L
MARS AIR CURTAIN MODEL 42CH,
42 ", 12OW10, MCA =6.4A, lie HP MOTOR
50 DOOR MICROSWITCH.
DUCTS UP TO
24" WIDTH
GALV. ALL - THREADED
ROD (TYPICAL)
DUCT
PICAL) '�—GALvANIZED ANGLE
DUCTS ABOVE ROUND
25" WIDTH
LOW PRESSURE DUCTWORK
DUCTWORK
A O R SM HANGERS NTS
TABLES 4 -1 AND 1-2, HVAC DUCT
CONSTRUCTION STANDARDS
7
OCR P
N 1/Z VO4
EXISTING CONDENSING UNITS TO BE
RELOCATED. M.G. SHALL DISCONNEC
AND REMOVE UNITS TO ALLOW FOR
PAD TO BE REMOVED AND REINSTA,
ON NEW PAD APPROX 4' -0" TO THE
RIGHT. M.C. SHALL EXTEND PIPING t
WIRING AS REQUIR €CHARG
BOTH UNITS.
BE
NEW FREEZER AND COOLER
CONDENSING UNITS.
NOTES.
IQ M.C. SHALL REMOVE EXISTING 4S" :K 24" LOUVER IN
EXTERIOR CANWASH WALL COMPLETE. M.G. SHALL
THEN RELOCATE EXISTING LOUVER/GRAVITY DAMPER
FROM EXHAUST FANS LOCATED ABOVE THE EXISTING
EXTERIOR DOOR TO OPENING IN EXTERIOR CANWASH
WALL. M.C. SHALL CAREFULLY REMOVE LOUVER/
GRAVITY DAMPER AND TRIM AS REQUIRED TO FIT
OPENING AND INSTALL TO INSURE DAMPER OPERATION.
u _ i _m
BRITTAIN ENGINEERING, INC.
CONSULTING MECHANICAL AND ELECTRICAL ENGINEERS
PO BOX 938 HICKORY, NC 28603
11/ z-
SHEET M 1 Of
BOTTOM OF LOUVER AT
APPROX. S' -l" AFF,
PTHP: TRANE MODEL PTHEI501UA, 208V/14
13000 BTUH COOLING, 12 ,200,5TUH HEATING,
365 CFM, 2-0 KW ELECTRIC HEATER MCA =11.4,
MOP =15.0, 6 -15 CORD AND PLUG, WALL SLEEVE,
OPTIONAL SUBBASE, ANODIZED ALUMINUM LOUVER
CONDENSATE DRAIN KIT.
CBSA
Architects
Ar@tttecture • Planning• Interior Design
www.cbsa- architects.coen
post office box 1239
226 second street nw
hickory, north carolina 286o1
phone (828) 3 - 3403
fax (828) 322 -1802
email cbsa @cbsa- architects.com
J
L7
t --t
W
W
V J
4
0
N
Lij
Lj
Icy-
LI_
3
W
Z
MARK
SCH
DD
CD
z
O
U
Q
m
i>
a
U
(n
J
0
0
U
U)
2007.017
Z
H
a
U
Z
Q
3
Q
U
COPYRIGHT:
CBSA ARCHITECTS, INC. 20
SHEET TITLE
Floor Plan - HVAC