HomeMy WebLinkAboute_1_rJi DETAILED ELECTRICAL SPECIFICATIONS SCOPE: FURNISH ALL MATERIALS, LABOR, TOOLS, EQUIPMENT AND SUPERVISION NECESSARY TO INSTALL COMPLETE ELECTRICAL POWER AND LIGHTING SYSTEM IN THE BUILDING AS FURTHER DESCRIBED ON THE ELECTRICAL CONTRACT DRAWINGS. SUPPLY ALL MATERIALS, FITTINGS AND HARDWARE NECESSARY FOR COMPLETE OPERATING SYSTEMS WITHIN THE OBVIOUS INTENT OF THE DRAWINGS. NO ATTEMPT HAS BEEN MADE TO DETAIL OR LIST EACH AND EVERY ITEM OF MATERIAL. THE ELECTRICAL CONTRACTOR IS CAUTIONED TO READ THE ENTIRE PROJECT DRAWINGS AND SPECIFICATIONS TO ASSURE HIMSELF OF A THOROUGH KNOWLEDGE OF BUILDING CONSTRUCTION, STRUCTURAL RESTRICTIONS TO ELECTRICAL CONTRACT WORK AND TO ASSURE THAT NO REFERENCE ANYWHERE IN THE PROJECT DRAWINGS AND SPECIFICATIONS TO WORK BY THE ELECTRICAL CONTRACTOR IS OVERLOOKED. CODES PERMITS AND INSPECTIONS- THE LATEST EDITION OF THE STATE OF NORTH CAROLINA BUILDING CODE WHICH INCLUDES THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE IS HEREBY MADE A PART OF THIS SPECIFICATION, CODE REQUIREMENTS SHALL TAKE PRECEDENCE OVER THESE SPECIFICATIONS WHERE THE CODE REQUIREMENTS EXCEED THAT OF THE SPECIFICATIONS. HOWEVER, THE SPECIFICATIONS SHALL BE FOLLOWED WHERE THEY EXCEED CODE REQUIREMENTS. THE ELECTRICAL CONTRACTOR SHALL, AT NO ADDITIONAL COST TO THE OWNER, OBTAIN THE SERVICES OF THE LOCAL ELECTRICAL INSPECTOR To MAKE ALL REQUIRED DURING CONSTRUCTION AND COMPLETED ELECTRICAL SYSTEM INSPECTIONS. MATERIALS AND WORKMANSHIP. ALL MATERIAL BUILT INTO THIS PROJECT SHALL BE NEW OF EQUIVALENT OR BETTER QUALITY THAN THAT SPECIFIED. SPECIFIC NAMES AND CATALOG NUMBERS USED HEREIN ARE TO ESTABLISH THE ITEM FUNCTION, ARRANGEMENT AND QUALITY REQUIRED AND IS IN NOWISE TO RESTRICT COMPETITION L ALL MATERIALS SHALL BE UL APPROVED AND LABELED FOR THE PARTICULAR APPLICATION AS USED ON THIS PROJECT. CONDUCTORS: ALL CONDUCTORS SHALL BE COPPER ( AUG AND SMALLER SHALL BE SOLID, AND 0 8 AWG AND LARGER STRANDED) WITH THHN/THWN INSULATION, INSTALLED IN CONDUIT. CONDUCTORS SHALL BE 0 12 AWG MINIMUM EXCEPT WITHIN LIGHT FIXTURES, LOW VOLTAGE CONTROLS OR COMMUNICATION/FIRE ALARM EQUIPMENT. CONDUCTOR COLOR CODE SHALL CONFORM TO THE NEC. CONDUCTORS SHALL BE CONTINUOUS FROM TERMINAL TO TERMINAL OR PULL BOX TO PULL BOX. JOINTS SHALL BE MADE WITH IDEAL "WIRENUTS." RACEWAYS: RACEWAYS SHALL BE UL APPROVED RIGID GALVANIZED STEEL WITH THREADED JOINTS OR METALLIC TUBING (EMT) WITH THREADED STEEL HEXAGONAL COMPRESSION FITTINGS - NEITHER INDENTOR TYPE OR DIE METAL FITTING WILL BE ACCEPTED. CONDUIT UNDER THE FLOOR SLAB AND UNDER GROUND OUTSIDE THE BUILDING MAY BE PVC. FITTINGS IN EMT SHALL BE WEATHER TIGHT (THOMAS AND BETTS SERIES "5123 WITH NYLON INSULATED THROATS), BENDS SHALL BE FACTORY FABRICATED OR MADE "COLD" WITH BENDING TOOL, FREE OF KINKS OR RESTRICTIONS. NO SINGLE BEND SHALL BE IN EXCESS OF W DEGREES. THERE SHALL BE NO MORE THAN THE EQUIVALENT OF THREE (3) W DEGREE BENDS IN A GIVEN RACEWAY FROM PULL BOX TO PULL BOX. RIGID RACEWAY THREADS SHALL BE CUT STRAIGHT AND TRUE - PIPE ENDS SHALL BE REAMED AND SMOOTHED INSIDE AND OUT. SUPPORT 1 -1/2 INCH AND LARGER CONDUIT 10 FEET O/C OR LESS, AND I INCH AND SMALLER 6 FEET O/C MAXIMUM. RACEWAYS SHALL BE SUPPORTED DIRECTLY FROM BUILDING STRUCTURE WITH BOLTS, SCREWS, STRAPS, HANGER RODS AND BRACKETS. ALL METALLIC HARDWARE SHALL BE GALVANIZED OR CADMIUM PLATED. NAILS, WIRE AND /OR PERFORATED STRAPS WILL NOT BE ACCEPTED. USE THREADED LOCKNUTS OUTSIDE AND THREADED LOCKNUT AND BUSHING INSIDE ALL RACEWAY CONNECTIONS TO BOXES, DEVICES, PANELS AND GUTTERS. USE NON - METALLIC BUSHINGS ON ALL 1 -1/4 INCH AND LARGER CONDUIT. EXPOSED CONDUIT SHALL BE RUN STRAIGHT AND TRUE PARALLEL AND PERPENDICULAR TO PRIMARY BUILDING LINES. BOXES AND DEVICES - ALL BOXES, PANELS AND EQUIPMENT SHALL BE SUPPORTED DIRECTLY FROM THE BUILDING STRUCTURE AND SHALL NOT DEPEND ON THE FEEDER RACEWAYS FOR SUPPORT. ALL ITEMS SHALL BE CAREFULLY ALIGNED SO THAT COVERS WILL FINISH FLUSH AND STRAIGHT. ALL UNUSED KNOCKOUTS SHALL BE CLOSED WITH BLANKING DEVICES. BOXES IN CONCRETE OR MASONRY SHALL BE 3 -1/2 INCH DEEP (MINIMUM) SQUARE 16 GAUGE GALVANIZED STEEL -STEEL CITY SERIES GW. BOXES INSTALLED IN WOOD PARTITIONS SHALL BE STEEL CITY 3 -1/2 INCH DEEP GANGABLE SQUARE CORNER TYPE. SURFACE MOUNTED BOXES SHALL BE STEEL CITY 0 52151 AND /OR 0 52111 OR EQUAL. RECEPTACLES SHALL BE HUBBELL 5362 OR EQUAL. SWITCHES SHALL BE HUBBELL 1221 SERIES OR EQUAL. COVER PLATES SHALL BE STAINLESS STEEL. PULL BOXES SHALL BE 14 GAUGE GALVANIZED STEEL WITH BLANK COVER SIZED AS REQUIRED BY NATIONAL ELECTRICAL CODE. LOCATE DEVICES AND EQUIPMENT ABOVE FINISHED FLOOR AS FOLLOWS UNLESS OTHERWISE SPECIFICALLY NOTED ON PLANS: WALL SWITCHES - 4' -0" OR TO NEAREST MASONRY COURSE JOINT. RECEPTACLES - I' -6" OR TO NEAREST MASONRY COURSE JOINT. LIGHT FIXTURES - AS NOTED ON FIXTURE SCHEDULE. GROUNDING: THE ELECTRICAL SYSTEM AND ALL ELECTRICAL EQUIPMENT SHALL BE GROUNDED IN ACCORDANCE WITH ARTICLE 250 OF THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE. GREEN EQUIPMENT GROUND WIRE SHALL BE INSTALLED WITH ALL FEEDERS AND BRANCH CIRCUITS AND SHALL BE SIZED PER NEC 250.122. LIGHTING FIXTURES: LIGHTING FIXTURES AND LAMPS SHALL BE PROVIDED AND INSTALLED AS PER SCHEDULE. ALL FIXTURES SHALL BE CLEANED ON COMPLETION OF INSTALLATION. BALLASTS AND /OR THE FIXTURE UNIT IN WHICH THEY ARE INSTALLED SHALL HAVE UL APPROVAL FOR DIRECT CONTACT MOUNTING TO COMBUSTIBLE CEILING MATERIAL. ALL FLUORESCENT FIXTURES SHALL BE SUPPLIED WITH ELECTRONIC BALLASTS. THE FIXTURES SHALL BE COMPLETE IN ALL RESPECTS INCLUDING PLASTER RINGS WHERE REQUIRED, END PLATES AND OTHER APPURTENANCES NECESSARY FOR THE COMPLETE INSTALLATION. ALL LIGHTING FIXTURES SHALL BE SECURED TO THE CEILING STRUCTURE PER THE NEC. ADDITIONAL SUPPORT WIRES (TIE WIRES) SHALL BE INSTALLED FOR EACH LAY -IN FLUORESCENT FIXTURE. THERE SHALL BE TWO STEEL WIRES OF THE SAME TYPE AS USED TO SUPPORT THE LAY -IN CEILING TRACK ONE WIRE AT EACH OPPOSITE CORNER OF THE FIXTURE. THE WIRES SHALL BE FASTENED TO THE BUILDING STRUCTURE. FOR FIRE RATED CEILING, FIXTURE SHALL BE SUPPORTED ON ALL FOUR CORNERS AND AS PER THE CEILING DESIGN CRITERIA, TO THE BUILDING STRUCTURE. TESTS: THE CONTRACTOR SHALL MEGCsER ALL BUSWAYS, CABLES AND CONTROL CONNECTIONS TO PROVE INSULATION RESISTANCE IS OF ACCEPTABLE VALUE. PANELBOARDS: PROVIDE PANELBOARDS RATED AND SIZED AS INDICATED IN THE SCHEDULE AND SHOWN ON THE PLANS EQUAL TO SQUARE D COMPANY MODEL NQOD FOR SERVICES UP TO 240 VOLTSt MODEL NF FOR SERVICES UP TO 480 VOLTSt AND "I- LINE" FOR POUTER DISTRIBUTION PANELS. ALL PANELBOARDS SHALL BE SUPPLIED WITH AN EQUIPMENT GROUNDING BUS. CONSTRUCTION FEATURES SHALL INCLUDE MINIMUM 5" WIDE GUTTERS, DEAD FRONT CONSTRUCTION, ELECTRCOPLATED CURRENT CARRYING PARTSt UL LISTED TERMINALS SUITABLE FOR CONDUCTORS SPECIFIEDt FLUSH FRONT HINGED DOOR WITH CYLINDER TUMBLER TYPE LOCKS (ALL KEYS ALKE)t CIRCUIT DIRECTORY AND FRAME, CODE GAUGE STEEL, GALVANIZED AND BAKED ENAMEL FINISHED. CIRCUIT BREAKERS SHALL BE BOLT -ON TYPE QOB (NQOD PANELBOARDS), TYPE EDB (NF PANELBOARDS), AND TYPE FA AND FH (I -LINE PANELBOARDS). BREAKERS SHALL BE TOGGLE ACTION WITH QUICK -MAKE, QUICK -BREAK MECHANISM. TRIP INDICATION SHALL BE BY BREAKER HANDLE TAKING A POSITION BETWEEN ON AND OFF. ALL MULTI -POLE BREAKERS SHALL BE COMMON TRIP WITH A SINGLE HANDLE. ACCEPTABLE MANUFACTURERS. SQUARE D, GENERAL ELECTRIC, SIEMENS, CUTLER - HAMMER SAFETY SWITCHES: SWITCHES SHALL BE EQUAL TO SQUARE D TYPE HD WITH RATINGS AND FUSING PROVISIONS AS INDICATED. IDENTIFICATION AND NAMEPLATES PROVIDE ENGRAVED, LAMINATED BAKELITE (WHITE LETTERS ON BLACK SURFACE) NAMEPLATES SCREWED TO EACH PIECE OF ELECTRICAL DISTRIBUTION EQUIPMENT AS FOLLOWS: A. PANELBOARDS, SWITCHBOARDS - DESIGNATION LI, PI, ETC,VOLTAGE, PHASE NUMBER OF WIRES, ETC.t WORDING EXAMPLE: PANEL LI- 208V -3 PHASE, 4 WIRE. B. MOTOR STARTERS, DISCONNECT SWITCHES - UNLESS MOUNTED DIRECTLY ON OR ADJACENT TO IDENTIFY EQUIPMENTt WORDING EXAMPLE: EXHAUST FAN 1, MAKE -UP AIR UNIT. PROVIDE TYPED DIRECTORIES FOR PANELBOARD BRANCH CIRCUIT IDENTIFICATION. IDENTIFY EACH CIRCUIT BREAKER AS TO THE EXACT ROOM NUMBERS OR AREA SERVED AND THE TYPE OF CIRCUIT, I.E. "ROOMS 101 -104 LIGHTS" OR "CAFETERIA EXHAUST FAN ". EQUIPMENT CONNECTIONS; THIS CONTRACTOR SHALL BRING ALL REQUIRED ELECTRICAL SERVICE TO ALL EQUIPMENT ITEMS FURNISHED UNDER OTHER SECTIONS OF THESE SPECIFICATIONS OR BY THE OWNER, MAKE FINAL CONNECTIONS, AND LEAVE EQUIPMENT READY FOR OPERATION. THIS CONTRACTOR SHALL COORDINATE WITH ANY AFFECTED TRADE TO ASSURE CORRECT OPERATION OF THE EQUIPMENT ITEM. CONTROL AND INTERLOCK WIRING: EXCEPT AS OTHERWISE INDICATED ON THE DRAWINGS, ALL CONTROL AND INTERLOCK WIRING SHALL BE PERFORMED BY THE RESPECTIVE CONTRACTORS. THE ELECTRICAL SUBCONTRACTOR SHALL INSTALL ALL STARTERS, PILOT SWITCHES, CONTROL DEVICES AND MISCELLANEOUS ITEMS OF ELECTRICAL EQUIPMENT FURNISHED UNDER OTHER SECTIONS OF THESE SPECIFICATIONS THAT ARE NOT INTEGRALLY MOUNTED WITH THEIR ASSOCIATED EQUIPMENT. SERVICE: THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING SERVICE WITH THE UTILITY COMPANY. ALL CHARGES ASSOCIATED WITH SERVICE SHALL BE PAID BY THE E.G. PROVIDE UTILITY REQUIRED METERING PROVISIONS. PROVIDE CT CAN OR CONCRETE PAD FOR TRANSFORMER AS REQUIRED. PROVIDE CONDUIT FOR UTILITY PRIMARY IF REQUIRED. EC SHALL WORK DIRECTLY WITH THE UTILITY AND SHALL COMPLETE AND SUBMIT ALL LOAD DATA SHEETS REQUIRED FOR SERVICE APPLICATION. WHERE A NEW SERVICE IS NOT REQUIRED, BUT LOADS ARE ADDED TO AN EXISTING SERVICE, E.G. SHALL NOTIFY UTILITY OF ADDITIONAL LOADS E.C. SHALL PROVIDE THIS INFORMATION AT BEGINNING OF PROJECT TO ALLOW TiME FOR A TRANSFORMER CHANGE OUT IF NECESSARY. VIBRATION ISOLATION AND SEISMIC RESTRAINT ALL EQUIPMENT AND CONDUIT FURNISHED AND INSTALLED UNDER THiS CONTRACT SHALL BE SEISMICALLY RESTRAINED BY CHAPTER 16 OF THE NORTH CAROLINA STATE BUILDING CODE, VOL. I - GENERAL CONSTRUCTION AND SPECIFICALLY SECTION 1601.6.4 AND TABLE 1601.6_44 WHICH RELATES TO MECHANICAL AND ELECTRICAL COMPONENTS. SUBMITTALS: SHOP DRAWING SUBMITTALS WILL BE REQUIRED FOR THIS PROJECT. SUBMIT EIGHT (8) COPIES OF ALL LIGHT FIXTURES AND MAJOR SPECIFIED EQUIPMENT TO THE ENGINEER FOR APPROVAL. THE ELECTRICAL CONTRACTOR SHALL REVIEW ALL SUBMITTALS AND MAKE CORRECTIONS AS REQUIRED PRIOR TO SUBMITTING TO ENGINEER FOR APPROVAL. THE CONTRACTOR SHALL ALSO AFFIX 1416 STAMP TO THE SUBMITTALS INDICATING THAT HIS REVIEW HAS BEEN COMPLETED. IT IS UNDERSTOOD THAT PROOF OF EQUALITY IS THE RESPONSIBILITY OF THE CONTRACTOR AND /OR SUPPLIER AND THAT IT IS NOT THE RESPONSIBILITY OF THE ENGINEER TO PROVE THE INEQUALITY OF THE PROPOSED SUBSTITUTIONS. FURTHERMORE THE DECISION OF THE ENGINEER IS FINAL. SHOULD ANY SUBSTITUTE ITEMS BE SUBMITTED AND DISAPPROVED, THEN THOSE ITEMS MUST BE FURNISHED EXACTLY AS DESCRIBED HEREIN. THE ENGINEER'S REVIEW OF SHOP DRAWINGS AND /OR SUBMITTAL DATA SHALL NOT RELIEVE THE CONTRACTOR OF RESPONSIBILITY FOR DEVIATIONS FROM THE CONTRACT DRAWINGS OR SPECIFICATIONS. L IGHTING F i XTURE SCHEDULE MARK TYPE MOUNTING MANUFACTURER DALLAST LAMPS TOTAL VOLTAGE REMARKS ca POWER PANEL ® CATALOG NO. MT) TYPE (SIT) TYPE WATTS TELEPHONE CONDUIT V A WRAPAROUND SURFACE COLUMBIA U ELECTRONIC 2) F32T8/41 61W UNIVERSAL MOTOR TOGGLE SWITCH 120 MOTOR r i I AUN4- 232- E88LHUNV 0 LIGHT FIXTURE 6 120V/211v S S BE 2'x 4' LAY -IN COLUMBIA ST824- 332G- FSAl2.125- U ELECTRONIC 3) F32T8/41 10111i UNIVERSAL 90 MIN. ElATTERY BACKUP. F❑ TROFFER 1 EB8LHUNV -EL S SMOKE DETECTOR 12 120V/2llV FREEZER LIGHTINCs/HEAT TAPE ELEC I R (V ,4L LEGENC� SYMBOL DESCRIPTION Co CONDUIT 100 100 —� 40 100 - - - -- CONDUIT UNDERFFLOOR OR UNDERGROUND C 0 20 — �— �— �— I00 �— ARROW INDICATES HOMERUN, TICKMARKS: NEUTRAL,PWASE,GND. ca POWER PANEL ® EXISTING PANEL T T TELEPHONE BOARD —T— TELEPHONE CONDUIT V TELEPHONE OUTLET O I JUNCTION BOX O; 0' DISCONNECT SWITCHt FUSHDt NONFUSED FFN FUSE PER NAMEPLATE S MOTOR TOGGLE SWITCH 120 MOTOR r i I EXISTING OR BY OTHERS 0 LIGHT FIXTURE 6 SINGLE POLE SWITCH, 3 WAY, 4 WAY S S PILOT LIGHT, DIMMER AFF ABOVE FINISHED FLOOR 6 DUPLEX RECEPT , ABOVE COUNTER 230 WP NYGFI ��{{ WEATHERPROOF , GROUND FAULT F❑ PULL STATION 1 A/V SIGNAL S SMOKE DETECTOR ELECTRICAL SYSTEM AND EQUIPMENT METHOD OF COMPLIANCE: Prescrfpttvs__*__Performance e nergy Cost Budget Provide a standard riser diagram which indicates designated points for check metering. Provide a standard panel schedule descrfptlon which Identifies different enduse loads. Lightingg schedule damp type required in fixture See Fixture Schedule number of lamps in fixture See Fixture Schedule ballast type used In the fixture See Fixture Schedule number of ballasts in fixture See Fixture Schedule total wattage per fixture See Fixture Schedule total interior wattage specified ve allowed 110/115 total exterior wattage specified vs allowed N/A Equipment schedules with motors (not used for mechanical ayatems) motor horsepower N/A number of phases N/A minimum efffciency N/A motor type N/A *OF poles N/A DESIGNER STATEMENT: To the best of my knowledge and belief, the design of this buildin complies with the electrical system and equipment re ufrements of the North Carolina State Building Code, Volume X- E�re SIGNED: NAME: Donald R Brittain TITLE: North Carolina Professional Engineer 4 `1883 EXIS EXI ST ING AMPS RMS. SYM. I.C. FLUSH MOUNTED PoA,Nr1 !tP INTEGRATED EQUIPMENT RATING 120/208 VOLTS, 3 PHASE, 4 WIRE, 600 AMP MAIN BREAKER SERVES LO Co Ho 100 100 —� 40 100 A B C 0 20 — �— �— �— I00 �— NO ca SERVES 0.18 EXISTING LOADS r4,10 1 2 100% EXISTING LOADS 3 4 - FREEZER CONDENSING UNIT IQ 0.18 3 4 120 5 6 - - 120 - 230 1 8 2JO FREEZER EVAPORATING UNIT COOLER CONDENSING UNIT D 230 g 10 2.10 423 13.1 1 TOTAL 230 II 12 120 FREEZER LIGHTINCs/HEAT TAPE 12 9 10 1.44 13 14 SPARE COOLER LIGHTING II 12 16 SPACE 13 14 IS I9 15 16 SPACE 21 Il 18 23 24 19 10 ALL TOTAL CONNECTED LOAD: 291 KVA ARE IF-20A UNLESS OTHERWISE NOTED PANEL NOTES: (DEC SHALL VERIFY EXACT LOAD REQUIREMENTS W/ FREEZER AND COOLER EQUIPMENT SUPPLIER 21 22 23 24 25 26 21 28 29 30 31 31 103 33 34 NEW PANEL "KP3" QI 103 35 36 103 31 38 TOTAL CONNECTED LOAD: 110 KVA ESTIMATED ALL BREAKERS AIRE IF-20A UNLESS OTHERWISE NOTED PANEL NOTES: 1 REPLACE EXISTING 10 AMP, 3 -POLE BREAKER W/ NEW 100 AMP, 3 -POLE BREAKER PI14NE �GP3 INTEGRATED P EQU UI IPi'1ENT RATING SURFA MOUNTED 120/208 VOLTS, 3 PHASE, 4 WIRE, 100 AMP MAIN LUG;i ONLY SERVES LO NO. —� —� —� 30 A B C 60 30 BREAKERS NO NO. SINGLE PHASE SERVES RECEPTACLES 0.18 I 2 r4,10 1.61 - 100% LIGHTING Oil 3 4 - FREEZER CONDENSING UNIT IQ 0.18 - AIR CURTAIN 120 5 6 - - 120 - 230 1 8 2JO FREEZER EVAPORATING UNIT COOLER CONDENSING UNIT D 230 g 10 2.10 423 13.1 1 TOTAL 230 II 12 120 FREEZER LIGHTINCs/HEAT TAPE 12 151 COOLER EVAPORATING UNIT 1.44 13 14 SPARE COOLER LIGHTING 030 15 16 SPACE Il IS I9 20 SPACE 21 22 23 24 ALL TOTAL CONNECTED LOAD: 291 KVA ARE IF-20A UNLESS OTHERWISE NOTED PANEL NOTES: (DEC SHALL VERIFY EXACT LOAD REQUIREMENTS W/ FREEZER AND COOLER EQUIPMENT SUPPLIER EST IMATED !.0 140 T145UL14T i ON FOR POWER CO. LOADS IN KVA EXISTING DEMAN NEW CONNECTED DIVERSIT FACTOR NEW DEMAND TOTAL KVA EXISTING NEW DEMAND SINGLE PHASE THREE PHASE SINGLE PHASE THREE PHASE SINGLE PHASE THREE PHASE LIGHTING - - 1.61 - 100% 1.61 - 1.61 RECEPTACLES - - 0.18 - 10% 0.13 - 0.13 AIR CURTAIN - - 120 - 100% 120 - 120 REFRIGERATION - - 5.64 21.0 1590 423 13.1 1 TOTAL - - 8.10 21.0 12 151 23.0 CBSA Architects nrchitecture•I'lanning•Interior Design www.ebsa- architecrs. com post office box 1239 226 second street nw hickory, north Carolina 286oi phone (8 3 fax (828) 322 -1802 email cbsa @cbsa- architects.com CONSULTANTS J 0 0 U LD W CL W U) U) Of 0 W 0 06 N LLJ W LL W z 1 1111 J 2 U Q z 0 of Q 0 z 0 m Q 0 CD 4 s5, "8 GND, 1 r r } Z O U Q m Q H Q U EXISTING NEW PANEL PANEL PROJECT NO: a 1 120/208V 1 II I 1 3m, 4 -WIRE 1 1201208V 30, 4 -WIRE DRAWN BY: JMS1 16,00A MLO 1 100A MLO CHK'D BY: DMA p U REPLACE EXISTING 704,3-POLE BREAKER W/ NEW 100A.3-POLE BREAKER 1 R i SER NTS BRITTAIN ENGINEERING, INC. CONSULTING MECHANICAL AND ELECTRICAL ENGINEERS re PO BOX 939 HICKORY. NC 26603 CBSA AR INC. 2006 SHEET TITLE Specs, Riser, Panels, Details, Appendix B SHEET E1 OF