HomeMy WebLinkAboute_1DETAILED ELECTRICAL SPECIFICATIONS SG FURNISH ALL MATERIALS, LABOR TOOLS, EQUIPMENT AND SUPERVISION NECESSARY TO INSTALL COMPLETE ELECTRICAL POWER AND LIGHTING SYSTEM IN THE BUILDING AS FURTHER DESCRIBED ON THE ELECTRICAL CONTRACT DRAWINGS. $UPPLY ALL MATERIALS, FITTINGS AND HARDWARE NECESSARY OR COMPLETE OPERATING SYSTEMS WITHIN THE OBVIOUS INTENT OF THE DRAWINGS. NO ATTEMPT HAS BEEN MADE TO DETAIL OR LIST EACH AND EVERY ITEM OF MATERIAL. THE ELECTRICAL CONTRACTOR 15 CAUTIONED TO READ THE ENTIRE PROJECT DRAWINGS AND SPECIFICATIONS TO ASSURE HIMSELF OF A THOROUGH KNOWLEDGE OF BUILDING CONSTRUCTION, STRUCTURAL RESTRICTIONS TO ELECTRICAL CONTRACT WORK AND TO ASSURE THAT NO REFERENCE ANYWHERE IN THE PROJECT DRAWINGS AND SPECIFICATIONS TO WORK BY THE ELECTRICAL CONTRACTOR IS OVERLOOKED. "ODES PERMITS AND INSPECTIONS: THE LATEST EDITION OF THE STATE OF NORTH CAROLINA BUILDING CODE WHICH INCLUDES THE LATEST EDITION OF TE NATIONAL ELECTRICAL CODE IS HEREBY MADE A PART OF THIS SPECIFICATION. CODE REQUIREMENTS SHALL TAKE PRECEDENCE OVER THESE SPECIFICATIONS WHERE THE CODE REQUIREMENTS EXCEED THAT OF THE SPECIFICATIONS. HOWEVER THE SPECIFICATIONS SHALL BE FOLLOWED WHERE THEY EXCEED CODE REQUIREMENTS. THE ELECTRICAL CONTRACTOR SHALL, AT NO ADDITIONAL COST TO TE OWNER, OBTAIN THE SERVICES OF THE LOCAL ELECTRICAL INSPECTOR TO MAKE ALL REQUIRED DURING CONSTRUCTION AND COMPLETED ELECTRICAL SYSTEM INSPECTIONS. MATERIALS AND WORiGMANSHIP: ALL MATERIAL BUILT INTO THIS PROJECT SHALL BE NEW OF EQUIVALENT OR BETTER QUALITY THAN THAT SPECIFIED. SPECIFIC NAMES AND CATALOG NUMBERS USED HEREIN ARE TO ESTABLISH THE ITEM FUNCTION, ARRANGEMENT AND QUALITY REQUIRED AND IS IN NOWISE TO RESTRICT COMPETITION. ALL MATERIALS SHALL BE UL APPROVED AND LABELED FOR THE PARTICULAR APPLICATION AS USED ON THIS PROJECT. CONDUCTORS• ALL CONDUCTORS SHALL B COPPER (+M0 44JG AND SMALLER SHALL BE SOLID, AND 0 5 Ara AND LARGER STRANDED) WITH THHN/THWN INSULATION, INSTALLED IN CONDUIT. CONDUCTORS SHALL BE 0 12 AWG MINIMUM EXCEPT WITHIN LIGHT FIXTURES, LOW VOLTAGE CONTROLS OR COMMUNICATION/FIR: ALARM EQUIPMENT. CONDUCTOR COLOR CODE SHALL CONFORM TO THE NEC. CONDUCTORS SHALL BE CONTINUOUS FROM TERMINAL TO TERMINAL OR FULL BOX TO PULL BOX. JOINTS SHALL BE MADE WITH IDEAL "WIRENUTS." RACEWAYS: RACEWAYS SHALL BE UL APPROVED RIGID GALVANIZED STEEL WITH THREADED JOINTS OR METALLIC TUBING (EMT) WITH THREADED STEEL HEXAGONAL COMPRESSION FITTINGS - NEITHER INDENTOR TYPE OR DIE METAL FITTING WILL BE ACCEPTED. CONDUIT UNDER THE FLOOR SLAB AND UNDER GROUND OUTSIDE THE BUILDING MAY BE PVC. FITTINGS IN EMT SHALL BE WEATHER TIGHT (THOMAS AND BETTS SERIES 0 5123 WITH NYLON INSULATED THROATS), BENDS SHALL BE FACTORY FABRICATED OR MADE COLD WITH BENDING TOOL, FREE OF KINKS OR RESTRICTIONS. NO SINGLE BEND SHALL BE IN EXCESS OF SO DEGREES. THERE SHALL BE NO MORE THAN THE EQUIVALENT OF THREE (3) SO DEGREE BENDS IN A GIVEN RACEWAY FROM PULL BOX TO PULL BOX. RIGID RACEWAY THREADS SHALL BE CUT STRAIGHT AND TRINE - PIPE ENDS SHALL B REAMED AND SMOOTHED INSIDE AND OUT. SUPPORT 1 -1/2 INCH AND LARGER CONDUIT 10 FEET O/C OR LESS, AND I INCH AND SMALLER 6 FEET O/C MAXIMUM. RACEWAYS SHALL BE SUPPORTED DIRECTLY FROM BUILDING STRJCTURE WITH BOLTS, SCREWS, STRAPS, HANGER RODS AND BRACKETS. ALL METALLIC HARDWARE SHALL BE GALVANIZED OR CADMIUM PLATED. NAILS, WIRE AND /OR PERFORATED STRAPS WILL NOT BE ACCEPTED. USE THREADED LOCKNUTS OUTSIDE AND THREADED LOCKNUT AND BUSHING INSIDE ALL RACEWAY CONNECTIONS TO BOXES, DEVICES, PANELS AND GUTTERS. USE NON - METALLIC BUSHINGS ON ALL 1 -1/4 INCH AND LARGER CONDUIT. UIT SHALL BE RUN STRAIGHT AND TRUE PARALLEL AND PERPENDICULAR TO PRIMARY BUILDING LINES. ELECTR I C4L 1.0GEND SYMBOL DESCRIPTION —� —^ 15 CONDUIT - - - -- CONDUIT UNDEi*FLOOR OR UNDERGROUND f` \l ARROW INDICATES HOMERUN, TICKMARKS: NEUTRAL,PHASE)sNO. ROMARICS POWER PANEL ® EXISTING PANEL T TELEPHONE BOARD —T— TELEPHONE CONDUIT b1W TELEPHONE OUTLET O JUNCTION BOX 5 DISCONNECT SWITCHs FUSEDt NONFUSED FPN FUSE PER NAMEPLATE S MOTOR TOGGLE SWITCH INCLUDED MOTOR 120V EXISTING OR BY OTHERS Q Q LIGHT FIXTURE S 8 SINGLE POLE SWITCH , 3 WAY, 4 WAY S , S PILOT LIGHT, DIMMER AFF ABOVE FINISHED FLOOR 6 DUPLEX RECEPT , ABOVE COUNTER ��{{,, WP VVGFI WEATHERPROOF , GROUND FAULT (] PULL STATION EMER3ENCY WALL PACK AN SIGNAL g SMOKE DETECTOR 2) 26W PLC LED EXPOSED GONAD BOXES AND DEVICES: ALL BOXES, PANELS AND EQUIPMENT SHALL BE SUPPORTED DIRECTLY FROM THE BUILDING STRUCTURE AND SHALL NOT DEPEND ON THE FEEDER RACEWAYS FOR SUPPORT. ALL ITEMS SHALL BE CAREFULLY ALIGNED SO THAT COVERS WILL FINISH FLUSH AND STRAIGHT. ALL UNUSED KNOCKOUTS SHALL BE CLOSED WITH BLANKING DEVICES. BOXES IN CONCRETE OR MASONRY SHALL BE 3 -1/2 INCH DEEP (MINIMUM) SQUARE 16 GAUGE GALVANIZED STEEL - STEEL CITY SERIES GW. BOXES INSTALLED IN WOOD PARTITIONS SHALL BE STEEL CITY 3 -1/2 INCH DEEP GANGABLE SQUARE CORNER TYPE. SURFACE MOUNTED BOXES SHALL BE SELL CITY 0 52151 AND /OR 52171 OR EQUAL. RECEPTACLES SHALL BE HUBBELL 5362 OR EQUAL. SWITCHES SHALL BE HUBBELL 1221 SERIES OR EQUAL. COVER PLATES SHALL BE STAINLESS STEEL. PULL BOXES SHALL BE 14 GAUGE GALVANIZED STEEL WITH BLANK COVER SIZED AS REQUIRED BY NATIONAL ELECTRICAL CODE. LOCATE DEVICES AND EQUIPMENT ABOVE FINISHED FLOOR AS FOLLOWS UNLESS OTHERWISE SPECIFICALLY NOTED ON PLANS: WALL SWITCHES - 4' -0" OR TO NEAREST MASONRY COURSE JOINT. RECEPTACLES - I' -6" OR TO NEAREST MASONRY COURSE JOINT. LIGHT FIXTURES - AS NOTED ON FIXTURE SCHEDULE. GROUNDING: THE ELECTRICAL SYSTEM AND ALL ELECTRICAL EQUIPMENT SHALL BE GROUNDED IN ACCORDANCE WITH ARTICLE 250 OF THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE. GREEN EQUIPMENT GROUND WIRE SHALL BE INSTALLED WITH ALL FEEDERS AND BRANCH CIRCUITS AND SHALL BE SIZED PER NEC 250.122. I IG+ -+TING FIXTURES: LIGHTING FIXTURES AND LAMPS SHALL BE PROVIDED AND INSTALLED AS PER SCHEDULE. ALL FIXTURES SHALL BE CLEANED ON COMPLETION OF INSTALLATION. BALLASTS AND /OR THE FIXTURE UNIT IN WHiCH THEY ARE INSTALLED SHALL HAVE UL APPROVAL FOR DIRECT CONTACT MOUNTING TO COMBUSTIBLE CEILING MATERIAL. ALL FLUORESCENT FIXTURES SHALL BE SUPPLIED WITH ELECTRONIC BALLASTS. THE FIXTURES SHALL BE COMPLETE IN ALL RESPECTS INCLUDING PLASTER RINGS WHERE REQUIRED, END PLATES AND OTHER APPURTENANCES NECESSARY FOR TE COMPLETE INSTALLATION. ALL WIRESNSHALL BE INSTALLED FOR ACD AY{ IN FLUORESCENT TU R ADDITIONAL ORESCENT FIXTURE.E THERE SHALL BE SUP S TWO S EELWIRES WIRES THE SAME TYPE AS USED TO SUPPORT THE LAY -IN CEILING TRACK ONE WIRE AT EACH OPPOSITE CORNER OF THE FIXTURE. TE WIRES SHALL BE FASTENED TO THE BUILDING STRUCTURE. FOR FIRE RATED CEILING, FIXTURE SHALL B SUPPORTED ON ALL OUR CORNERS AND AS PER THE CEILING DESIGN CRITERIA, TO THE BUILDING STRUCTURE. TESTS THE CONTRACTOR SHALL MEGGER ALL BUSWAYS, CABLES AND CONTROL CONNECTIONS TO PROVE INSULATION RESISTANCE IS OF ACCEPTABLE VALUE. PANELBOARDS: AND SQUARE D COMPANY MODEL NQOD OR UP TO VOLT5t MODEL NF OR SER ICES UP TO 480 LLAL TO VOLTSt AND "I- LINE" FOR POWER DISTRIBUTION PANELS. ALL PANELBOARDS SHALL BE SUPPLIED WITH AN EQUIPMENT GROUNDING BUS. CONSTRUCTION FEATURES SHALL INCLUDE MINIMUM 5" WIDE GUTTERS, DEAD FRONT CONSTRUCTION, ELECTRCOPLATED CURRENT CARRYING PARTSt UL TERMINALS SUITABLE OR CONDUCTORS SPECIFIED* FLUSH FRONT HINGED DOOR WITH CYLINDER TUMBLER TYPE LOCKS (ALL KEYS ALIKE)* CIRCUIT DIRECTORY AND FRAME, CODE GAUGE STEEL, GALVANIZED AND BAKED ENAMEL FINISHED. CIRCUIT BREAKERS SHALL BE BOLT -ON TYPE QOB (NQOD PANELBOARDS), TYPE EDB (NF PANELBOARDS), AND TYPE FA AND PH 6 -LINE PANELBOARDS). BREAKERS SHALL BE TOGGLE ACTION WITH QUICK -MAKE, QUICK -BREAK MECHANISM. TRIP INDICATION SHALL BE BY BREAKER HANDLE TAKING A POSITION BETWEEN ON AND OFF. ALL MULTI -POLE BREAKERS SHALL BE COMMON TRIP WITH A SINGLE HANDLE. ACCEPTABLE MANUFACTURERS: SQUARE D, GENERAL ELECTRIC, SIEMENS, CUTLER- HAMMER SAFETY SWITCHES: SWITCHES SHALL BE EQUAL TO SQUARE D TYPE HD WITH RATINGS AND FUSING PROVISIONS AS INDICATED. IDENTIFICATION AND NAMEPLATES- PROVIDE ENGRAVED, LAMINATED 54KELIE (WHITE LETTERS ON BLACK SURFACE) NAMEPLATES SCREWED TO EACH PIECE OF ELECTRICAL DISTRIBUTION EQUIPMENT AS FOLLOWS: A. PANELBOARDS, SWITCHBOARDS - DESIGNATION LI, Pl, ETC.,VOLTAGE, PHASE NUMBER OF WIRES, ETC.* WORDING EXAMPLE: PANEL LI- 208v -3 PHASE, 4 WIRE. B. MOTOR STARTERS, DISCONNECT SWITCHES - UNLESS MOUNTED DIRECTLY ON OR ADJACENT TO IDENTIFY EQUIPMENT* WORDING EXAMPLE: EXHAUST FAN I, MAKE -UP AIR UNIT. A T O T H E T YPED EXACT R NUMBSEFRS OR AREA S ERVE D AND T CI YPE OF CIRCUIT, Jr. E CIRCUIT BREAKER 104 LIGHTS" OR "CAFETERIA EXHAUST FAN ". EQUIPMENT CONNECTIONS: THIS CONTRACTOR SHALL BRING ALL REQUIRED ELECTRICAL SERVICE TO ALL EQUIPMENT ITEMS FURNISHED UNDER OTHER SECTIONS OF THESE SPECIFICATIONS OR BY TE OWNER MAKE FINAL CONNECTIONS, AND LEAVE EQUIPMENT READY FOR OPERATION. THIS CONTRACTOR SHALL COORDINATE WITH ANY AFFECTED TRADE TO ASSURE CORRECT OPERATION OF THE EQUIPMENT ITEM. CONTROL AND INTERLOCK WIRING: EXCEPT AS OTHERWISE INDICATED ON THE DRAWINGS, ALL CONTROL AND INTERLOCK WIRING SHALL BE PERFORATED BY THE RESPECTIVE CONTRACTORS. THE ELECTRICAL SUBCONTRACTOR SHALL INSTALL ALL STARTERS, PILOT SWITCHES, CONTROL DEVICES AND MISCELLANEOUS ITEMS OF ELECTRICAL EQUIPMENT FURNISHED UNDER OTHER SECTIONS OF THESE SPECIFICATIONS THAT ARE NOT INTEGRALLY MOUNTED WITH THEIR ASSOCIATED EQUIPMENT. SERVICE: THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING SERVICE WITH THE UTILITY COMPANY. ALL CHARGES ASSOCIATED WITH SERVICE SHALL BE PAID BY THE E.G. PROVIDE UTILITY REQUIRED METERING PROVISIONS. PROVIDE CT CAN OR CONCRETE PAD FOR TRANSFORMER AS REQUIRED, PROVIDE CONDUIT FOR UTILITY PRIMARY IF DIRECTLY REQUIRED. EC SHALL WORK I OR SERVICE APPLICATION. WHERE A NEW SERVICE IS NOT P U L REQUIRED, BUT LOADS S AREADDEDTo AN EXISTING ING SERVICE, E.r—. SHALL NOTIFY UTILITY OF ADDITIONAL LOADS E.C. SHALL PROVIDE THIS INFORMATION AT BEGINNING OF PROJECT TO ALLOW TIME FOR A TRANSFORMER CHANGE OUT IF NECESSARY. VIBRATION ISOLATION AND SEISMIC RESTRAINT: ALL EQUIPMENT AND CONDUIT FURNISHED AND INSTALLED UNDER THIS CONTRACT SHALL BE SEISMICALLY RESTRAINED BY CHAPTER 16 OF THE NORTH CAROLINA STATE BUILDING CODE, VOL. I - GENERAL CONSTRUCTION AND SPECIFICALLY SECTION 1601b.4 AND TABLE 1601.6.4A WHICH RELATES TO MECHANICAL AND ELECTRICAL COMPONENTS. SUBMITTALS: SHOP DRAWING SUBMITTALS WILL BE R FOR THIS PROJECT. SUBMIT EIGHT (8) COPIES SH LIGHT REVIEW ALFIXTURES BMIT SUBMITTALS AND MAKE CORRECTIONS EQUIPMEN APPROVAL. AS REQUIRED PRIOR TOSUBMI TIING OO ENG NEER OR THE CONTRACTOR SHALL ALSO AFFIX HIS STAMP TO THE SUBMITTALS INDICATING THAT HIS REVIEW HAS BEEN COMPLETED. IT IS IT IS NOTE HE RESPONSIBIPRLITTY�OF Or EQUALITY 15 THE THE ENGINEER TO ROVE T INEQUALITY O EOF HCONTRACTOR OPOSED SUBSTITUTIONS AND THAT UTIO S FURTHERMORE THE DECISION OF THE ENGINEER IS FINAL, SHOULD ANY SUBSTITUTE ITEMS BE SUBMITTED AND DISAPPROVED, THEN THOSE ITEMS MUST BE FURNISHED EXACTLY AS DESCRIBED HEREIN. THE ENGINEER'S REVIEW OF SHOP DRAWINGS AND /OR SUBMITTAL DATA SHALL NOT RELIEVE THE CONTRACTOR OF RESPONSIBILITY FOR DEVIATIONS FROM THE CONTRACT DRAWINGS OR SPECIFICATIONS. I LiGHTING FIXTURE SCHEDULE 036 1 1 —� —^ 15 MANUFACTURER CATALOG NO. BALLAST QT) TYPE LAMPS QT) TYPE TOTAL WATTS VOLTAGE ROMARICS MARK TYPE MOUNTINGS LAY -IN COLUMBIA ST824-232G-1=642.125- EBSLA NV U ELECTRONIC 2) F32T8/41 b1W 120v AIR CURTAIN 0.11 5 A 2' x 4' TROFFER FREEZER EVAPORATING UNIT CORNER STONE _ INCLUDED 10 120V w MIN. BATTERY BACKUP 125A MLO 1.18 9 0 E EMERSSETNCY WALL Nv2 WE EMER3ENCY WALL PACK EXTERIOR WALL M "T a 8' -0" AFF MAXIMUM UNIVERSAL LUMINAIRE YWP1212- 2PLC26 -120- OP- BLK- EMB /CAB/PC CORN ER STONE GCIREW U ELECTRONIC 2) 26W PLC LED 58W MAX FACE MA 120V 120V BACKUP CONNECT AS EMG EGRESS FIXTUi E, FLUSH MTD BACK X W/ HOT 90 MIN BATTERY No. OF FACES AND ARROWS AS SHOUN X EXIT (DIE CAST) ELECTRICAL SYSTEM AND EQUIPMENT METHOD OF COMPLIANCE: Prescriptive-AL-J°erformance e nergy Cost Budget Provide a standard riser dlagram which indicates designated points for check metering. Provide a standard panel schedule description which Identifies different enduse loads. Lighting schedule See Fixture Sched e Tamp type required In fixture number of lamps in fixture See Fixture Schedule ballast type used in the fixture See Fixture Schedule number of ballasts in fixture See Fixture Schedule total wattage per fixture See Fixture Schedule total interior wattage specified ve allowed 330/485 total exterior wattage specified vs allowed N/A Equipment schedules with motors (not used for mechanical systems) motor horsepower N/A number of phases N/A minimum efffcienc4 N/A motor type N/A •of poles N/A DESIGNER STATE1­104T: To the best of my knowledge and belief, the design of this building complies with the electrical system and aq utpment requirements of the North Carolina State Building Cod e Vo�, lume X -Ener� SIGNED: NAME Donald R B rittaIn TITLE: North Carolina Professional Englneer +rf883 FF�ALAR1'1 LAYOUT 15 FOR INFORMATION ONLY. TE FIRE ALARM CONTRACTOR SHALL PROVIDE A DESIGN AND SYSTEM TO MEET THE NC BLDG CODE, NFPA - 12 AND INSTALL ALL DEVICES AS REQUIRED BY THE LOCAL AND /OR STATE FIRE MARSHALL. I y WC 10,000 AMPS RMS. SYM, I.C. FLUSH MOUNTED P�4NE1. P3 INTEGRATED EQUIPMENT RATING 120/208 VOLTS, 3 PHASE, 4 UJIRE, 125 AMP MAiN Ll1G6 ONLY A B C SERVE6 RECEPTACLES 036 1 1 —� —^ 15 13 — I4 2AO 60 30 2 480 4 480 FREEZER CONDENSING UNIT LIGHTING 033 3 6 480 —� �— 24 AIR CURTAIN 0.11 5 8 2.10 FREEZER EVAPORATING UNIT PTHP 1 116 1 10 2.10 125A MLO 1.18 9 0 SERVES 12 1.44 FREEZER LIGHTI TAFE , ARE 11 13 — I4 2AO 30 COOLER CONDENSING UNIT D 15 —� 16 2.40 11 —� — 18 2.40 NEW 19 —� 20 1.44 j23 COOLER EVAPORATING UNIT SPACE PANEL 21 —� �— 22 0.15 COOLER LIGHTING —� �— 24 SPACE ALL BREAKERS ARE IF-20A UNLESS OTHERWISE NOTED TOTAL CONNECTED LOAD: 333 KYA J 'EC SHALL STUB (3) 3/4" t (1) P CONDUITS FROM PANEL TO ABOVE CEILING FOR FUTURE ACCESS.' NEL NOTES: 0 (DEC SHALL VERIFY EXACT LOAD REQUIREMENTS W/ REFRIG. EQUIPMENT SUPPLIER EXISTING MSBD 4WI211 V [ 37, 4 -WIRE [ 2000A I I THE BOTTOM OF WALL MOUNTED INDICATING APPLIANCES SHALL BE 80 INCE5 MINIMUM TO 96 INCHES MAXIMUM ABOVE FINISHE FLOOR NOTES- 1. SYSTEM SHALL COMPLY W/ NFPA 72 t / ALL REQUIREMENTS OF THE LOCAL AUTHORITY HAVING JURISDICTION. EXISTING WIRING GUTTER I I r- - - - --� I I LV LEI I I [ z28K I [ r — 480V- 1201208V 4 4�- BSAhitects Arahitaatura a plannta - Inteelor D®algn www.cbaa- arch9[eate.com post Office box 1239 226 second street nw hickory, north carolina 286o1 phone (828) 322-3403 fax (828) 322 -1802 email cbsa @cbsa- architects.com 0 LO H LLI LLI I- F 0 I I I XF" iR I I I I S NEW 250/20 EXISTING DISCONNECT T F DISCONNECT FUSED TO REMAIN, AT 125A. MAKE CONNECTIONS IN GUTTER AS REQUIRED. 2. WIRING SHALL BE IN CONDUIT. — — — — — — 3. STROBES SHALL BE SYNCHRONIZED. 4. SEE PLANS FOR DEVICE QUANTITIES. I 5. INSTALL PULL STATIONS AT 48" AFF- II I I II EXISTING CABLING TO TEL BD EXISTING UL I I I TYPICAL LISTED DUAL EXISTING r — — — � ACTIVATING LINE DIGITAL I I ADT FIRE ALARM ANN I DEVICE COMMUNICATOR[ I CONTROL PANEL I L — — — i--- - - -- [ [ EXISTING L--- - - - - -J ANNUNCIATOR AT MAIN ENTRANCE TO BUILDING EXi ST i1�C� WIRE AL.Ale "i RI NTS POWER R i SER NTS NOTE: SMOKE DETECTORS SHOULD NOT BE LOCATED IN A DIRECT AIRFLOW NOR CLOSER THAN 3 FEET FROM AN AIR SUPPLY DIFFUSER OR RETURN AIR OPENING PER NFPA 12. DEPENDING ON AIR VELOCITY OR THROW OF THE DIFFUSER THREE FEET CLEARANCE MAY NOT BE ADEQUATE. NOTE: THE EXISTING FIRE ALARM CONTROL PANEL IS AN ADT UNIT. ALL NEW DEVICES SHALL MATCH EXISTING DEVICES. W LA Lij W L1_ LLI Z Q H Z < U D O�z Z 0 QO U U) U Q 3 U U MARK DATE DESCRIPTION SCH SCHEMATIC PHASE DD DESIGN DEVELOPMENT CD 5/11/07 BID SET IRMA PROJECT NO: 2007.017 rpm RLM �, SG ' PY IP I J' C .. t� 2006 Amok. NMI I 051106JM Specs, Riser, Panels, Details, Appendix B BRITTAIN ENGINEERING, INC. CONSULTING MECHANICAL AND ELECTRICAL ENGINEERS PO BOX 639 HICKORY• NC 28603 + -+ SHEET E1 OF 0 NEW PANEL W "KP3" J 120/206V 0 3m, 4 -WIRE 125A MLO 0 I I I XF" iR I I I I S NEW 250/20 EXISTING DISCONNECT T F DISCONNECT FUSED TO REMAIN, AT 125A. MAKE CONNECTIONS IN GUTTER AS REQUIRED. 2. WIRING SHALL BE IN CONDUIT. — — — — — — 3. STROBES SHALL BE SYNCHRONIZED. 4. SEE PLANS FOR DEVICE QUANTITIES. I 5. INSTALL PULL STATIONS AT 48" AFF- II I I II EXISTING CABLING TO TEL BD EXISTING UL I I I TYPICAL LISTED DUAL EXISTING r — — — � ACTIVATING LINE DIGITAL I I ADT FIRE ALARM ANN I DEVICE COMMUNICATOR[ I CONTROL PANEL I L — — — i--- - - -- [ [ EXISTING L--- - - - - -J ANNUNCIATOR AT MAIN ENTRANCE TO BUILDING EXi ST i1�C� WIRE AL.Ale "i RI NTS POWER R i SER NTS NOTE: SMOKE DETECTORS SHOULD NOT BE LOCATED IN A DIRECT AIRFLOW NOR CLOSER THAN 3 FEET FROM AN AIR SUPPLY DIFFUSER OR RETURN AIR OPENING PER NFPA 12. DEPENDING ON AIR VELOCITY OR THROW OF THE DIFFUSER THREE FEET CLEARANCE MAY NOT BE ADEQUATE. NOTE: THE EXISTING FIRE ALARM CONTROL PANEL IS AN ADT UNIT. ALL NEW DEVICES SHALL MATCH EXISTING DEVICES. W LA Lij W L1_ LLI Z Q H Z < U D O�z Z 0 QO U U) U Q 3 U U MARK DATE DESCRIPTION SCH SCHEMATIC PHASE DD DESIGN DEVELOPMENT CD 5/11/07 BID SET IRMA PROJECT NO: 2007.017 rpm RLM �, SG ' PY IP I J' C .. t� 2006 Amok. NMI I 051106JM Specs, Riser, Panels, Details, Appendix B BRITTAIN ENGINEERING, INC. CONSULTING MECHANICAL AND ELECTRICAL ENGINEERS PO BOX 639 HICKORY• NC 28603 + -+ SHEET E1 OF