HomeMy WebLinkAboute_1DETAILED ELECTRICAL SPECIFICATION SCOPE: FURNISH ALL MATERIALS, LABOR, TOOLS, EQUIPMENT AND SUPERVISION NECESSARY TO INSTALL COMPLETE ELECTRICAL POWER AND LIGHTING SYSTEM IN THE BUILDING AS FURTHER DESCRIBED ON THE ELECTRICAL CONTRACT DRAWINGS. SUPPLY ALL MATERIALS, FITTINGS AND HARDWARE NECESSARY FOR COMPLETE OPERATING SYSTEMS WITHIN THE OBVIOUS INTENT OF THE DRAWINGS. NO ATTEMPT HAS BEEN MADE TO DETAIL OR LIST EACH AND EVERY ITEM OF MATERIAL. THE ELECTRICAL CONTRACTOR IS CAUTIONED TO READ THE ENTIRE PROJECT DRAWINGS AND SPECIFICATIONS TO ASSURE HIMSELF OF A THOROUGH KNOWLEDGE OF BUILDING CONSTRUCTION, STRUCTURAL RESTRICTIONS TO ELECTRICAL CONTRACT WORK AND TO ASSURE THAT NO REFERENCE ANYWHERE IN THE PROJECT DRAWINGS AND SPECIFICATIONS TO WORK BY THE ELECTRICAL CONTRACTOR IS OVERLOOKED. QQDES. PERMITS AND INSPECTIONS: THE LATEST EDITION OF THE STATE OF NORTH CAROLINA BUILDING CODE WHICH INCLUDES THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE IS HEREBY MADE A PART OF THIS SPECIFICATION. CODE REQUIREMENTS SHALL TAKE PRECEDENCE OVER THESE SPECIFICATIONS WHERE THE CODE REQUIREMENTS EXCEED THAT OF THE SPECIFICATIONS. HOWEVER, THE SPECIFICATIONS SHALL BE FOLLOWED WHERE THEY EXCEED CODE REQUIREMENTS. THE ELECTRICAL CONTRACTOR 'SHALL, AT NO ADDITIONAL COST TO THE OWNER, OBTAIN THE SERVICES OF THE LOCAL ELECTRICAL INSPECTOR TO MAI(E ALL REQUIRED DURING CONSTRUCTION AND COMPLETED ELECTRICAL SYSTEM INSPECTIONS. MATERIALS AND WORKMAN HIP• ALL MATERIAL BUILT INTO THIS PROJECT SHALL BE NEW OF EQUIVALENT OR BETTER QUALITY THAN THAT SPECIFIED. SPECIFIC NAMES AND CATALOG NUMBERS USED HEREIN ARE TO ESTABLISH THE ITEM FUNCTION, ARRANGEMENT AND QUALITY REQUIRED AND IS IN NOWISE TO RESTRICT COMPETITION. ALL MATERIALS SHALL BE UL APPROVED AND LABELED FOR THE PARTICULAR APPLICATION AS USED ON THIS PROJECT. CONDUCTORS: ALL CONDUCTORS SHALL BE COPPER ( #10 AWG AND SMALLER SHALL BE SOLID, AND #8 AWG AND LARGER STRANDED) WITH THHN/THWN INSULATION, INSTALLED IN CONDUIT. CONDUCTORS SHALL BE #12 AWG MINIMUM EXCEPT WITHIN LIGHT FIXTURES, LOW VOLTAGE CONTROLS OR COMMUNICATION /FIRE ALARM EQUIPMENT. CONDUCTOR COLOR CODE SHALL CONFORM TO THE NEC. CONDUCTORS SHALL BE CONTINUOUS FROM TERMINAL TO TERMINAL OR PULL BOX TO PULL BOX. JOINTS SHALL BE MADE WITH IDEAL "WIRENUTS." RACEWAYS: RACEWAYS SHALL BE UL APPROVED RIGID GALVANIZED STEEL WITH THREADED JOINTS OR METALLIC TUBING (EMT) WITH THREADED STEEL HEXAGONAL COMPRESSION FITTINGS — NEITHER INDENTOR TYPE OR DIE METAL FITTING WILL BE ACCEPTED. CONDUIT UNDER THE FLOOR SLAB AND UNDER GROUND OUTSIDE THE BUILDING MAY BE PVC. FITTINGS IN EMT SHALL BE WEATHER TIGHT (THOMAS AND BETTS SERIES #5123 WITH NYLON INSULATED THROATS), BENDS SHALL BE FACTORY FABRICATED OR MADE "COLD" WITH BENDING TOOL, FREE OF KINKS OR RESTRICTIONS, NO SINGLE BEND SHALL BE IN EXCESS OF 90 DEGREES. THERE SHALL BE NO MORE THAN THE EQUIVALENT OF THREE (3) 90 DEGREE BENDS IN A GIVEN RACEWAY FROM PULL BOX TO PULL BOX. RIGID RACEWAY THREADS SHALL BE CUT STRAIGHT AND TRUE — PIPE ENDS SHALL BE REAMED AND SMOOTHED INSIDE AND OUT. SUPPORT 1 -1/2 INCH AND LARGER CONDUIT 10 FEET O/C OR LESS, AND 1 INCH AND SMALLER 6 FEET O/C MAXIMUM. RACEWAYS SHALL BE SUPPORTED DIRECTLY FROM BUILDING STRUCTURE WITH BOLTS, SCREWS, STRAPS, HANGER RODS AND BRACKETS. ALL METALLIC HARDWARE SHALL BE GALVANIZED OR CADMIUM PLATED. NAILS, WIRE AND /OR PERFORATED STRAPS WILL NOT BE ACCEPTED. USE THREADED LOCKNUTS OUTSIDE AND THREADED LOCKNUT AND BUSHING INSIDE ALL RACEWAY CONNECTIONS TO BOXES, DEVICES, PANELS AND GUTTERS. USE NON— METALLIC BUSHINGS ON ALL 1 -1/4 INCH AND LARGER CONDUIT. EXPOSED CONDUIT SHALL BE RUN STRAIGHT AND TRUE PARALLEL AND PERPENDICULAR TO PRIMARY BUILDING LINES. BOXES AND DEVICES: ALL BOXES, PANELS AND EQUIPMENT SHALL BE SUPPORTED DIRECTLY FROM THE BUILDING STRUCTURE AND SHALL NOT DEPEND ON THE FEEDER RACEWAYS FOR SUPPORT. ALL ITEMS SHALL BE CAREFULLY ALIGNED SO THAT COVERS WILL FINISH FLUSH AND STRAIGHT. ALL UNUSED KNOCKOUTS SHALL BE CLOSED WITH BLANKING DEVICES. BOXES IN CONCRETE OR MASONRY SHALL BE 3 -1/2 INCH DEEP (MINIMUM) SQUARE 16 GAUGE GALVANIZED STEEL — STEEL CITY SERIES GW. BOXES INSTALLED IN WOOD PARTITIONS SHALL BE STEEL CITY 3 -1/2 INCH DEEP GANGABLE SQUARE CORNER TYPE. SURFACE MOUNTED BOXES SHALL BE STEEL CITY #52151 AND /OR #52171 OR EQUAL. RECEPTACLES SHALL BE HUBBELL 5362 OR EQUAL. SWITCHES SHALL BE HUBBELL 1221 SERIES OR EQUAL. COVER PLATES SHALL BE STAINLESS STEEL. PULL BOXES SHALL BE 14 GAUGE GALVANIZED STEEL WITH BLANK COVER SIZED AS REQUIRED BY NATIONAL ELECTRICAL CODE. LOCATE DEVICES AND EQUIPMENT ABOVE FINISHED FLOOR AS FOLLOWS UNLESS OTHERWISE SPECIFICALLY NOTED ON PLANS: WALL SWITCHES — 4' -0" OR TO NEAREST MASONRY COURSE JOINT. RECEPTACLES — 1' -6" OR TO NEAREST MASONRY COURSE JOINT. LIGHT FIXTURES — AS NOTED ON FIXTURE SCHEDULE. GROUNDING: THE ELECTRICAL SYSTEM AND ALL ELECTRICAL EQUIPMENT SHALL BE GROUNDED IN ACCORDANCE WITH ARTICLE 250 OF THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE. GREEN EQUIPMENT GROUND WIRE SHALL BE INSTALLED WITH ALL FEEDERS AND BRANCH CIRCUITS AND SHALL BE SIZED PER NEC 250.122. LIGHTING FIXTURES: LIGHTING FIXTURES AND LAMPS SHALL BE PROVIDED AND INSTALLED AS PER SCHEDULE. ALL FIXTURES SHALL BE CLEANED ON COMPLETION OF INSTALLATION. BALLASTS AND /OR THE FIXTURE UNIT IN WHICH THEY ARE INSTALLED SHALL HAVE UL APPROVAL FOR DIRECT CONTACT MOUNTING TO COMBUSTIBLE CEILING MATERIAL. ALL FLUORESCENT FIXTURES SHALL BE SUPPLIED WITH ELECTRONIC BALLASTS. THE FIXTURES SHALL BE COMPLETE IN ALL RESPECTS INCLUDING PLASTER RINGS WHERE REQUIRED, END PLATES AND OTHER APPURTENANCES NECESSARY FOR THE COMPLETE INSTALLATION. ALL LIGHTING FIXTURES SHALL BE SECURED TO THE CEILING STRUCTURE PER THE NEC. ADDITIONAL SUPPORT WIRES (TIE WIRES) SHALL BE INSTALLED FOR EACH LAY —IN FLUORESCENT FIXTURE. THERE SHALL BE TWO STEEL WIRES OF THE SAME TYPE AS USED TO SUPPORT THE LAY —IN CEILING TRACK. ONE WIRE AT EACH OPPOSITE CORNER OF THE FIXTURE. THE WIRES SHALL BE FASTENED TO THE BUILDING STRUCTURE. FOR FIRE RATED CEILING, FIXTURE SHALL BE SUPPORTED ON ALL FOUR CORNERS AND AS PER THE CEILING DESIGN CRITERIA, TO THE BUILDING STRUCTURE. TESTS: THE CONTRACTOR SHALL MEGGER ALL BUSWAYS, CABLES AND CONTROL CONNECTIONS TO PROVE INSULATION RESISTANCE IS OF ACCEPTABLE VALUE. PANELBOARDS: PROVIDE PANELBOARDS RATED AND SIZED AS INDICATED IN THE SCHEDULE AND SHOWN ON THE PLANS EQUAL TO SQUARE D COMPANY MODEL NQOD FOR SERVICES UP TO 240 VOLTS; MODEL NF FOR SERVICES UP TO 480 VOLTS; AND "I— LINE" FOR POWER DISTRIBUTION PANELS. ALL PANELBOARDS SHALL BE SUPPLIED WITH AN EQUIPMENT GROUNDING BUS. CONSTRUCTION FEATURES SHALL INCLUDE MINIMUM I 5" WIDE GUTTERS, DEAD FRONT CONSTRUCTION, ELECTRCOPLATED CURRENT CARRYING PARTS; UL LISTED TERMINALS SUITABLE FOR CONDUCTORS SPECIFIED; FLUSH FRONT HINGED DOOR WITH CYLINDER TUMBLER TYPE LOCKS (ALL KEYS ALIKE); CIRCUIT DIRECTORY AND FRAME, CODE GAUGE STEEL, GALVANIZED AND BAKED ENAMEL FINISHED. CIRCUIT BREAKERS SHALL BE BOLT —ON TYPE QOB (NQOD PANELBOARDS), TYPE EDB (NF PANELBOARDS), AND TYPE FA AND FH (I —LINE PANELBOARDS). BREAKERS SHALL BE TOGGLE ACTION WITH QUICK —MAKE, QUICK —BREAK MECHANISM. TRIP INDICATION SHALL BE BY BREAKER HANDLE TAKING A POSITION BETWEEN ON AND OFF. ALL MULTI —POLE BREAKERS SHALL BE COMMON TRIP WITH A SINGLE HANDLE. ACCEPTABLE MANUFACTURERS: SQUARE D, GENERAL ELECTRIC, SIEMENS, CUTLER — HAMMER SAFETY SWITCHES: SWITCHES SHALL BE EQUAL TO SQUARE D TYPE HD WITH RATINGS AND FUSING PROVISIONS AS INDICATED. IDENTIFICATION AND NAMEPLATES: PROVIDE ENGRAVED, LAMINATED BAKELITE (WHITE LETTERS ON BLACK SURFACE) NAMEPLATES SCREWED TO EACH PIECE OF ELECTRICAL DISTRIBUTION EQUIPMENT AS FOLLOWS: A. PANELBOARDS, SWITCHBOARDS — DESIGNATION L1, P1, ETC.,VOLTAGE, PHASE NUMBER OF WIRES, ETC.; WORDING EXAMPLE: PANEL L1- 208V -3 PHASE, 4 WIRE. B. MOTOR STARTERS, DISCONNECT SWITCHES — UNLESS MOUNTED DIRECTLY ON OR ADJACENT TO IDENTIFY EQUIPMENT; WORDING EXAMPLE: EXHAUST FAN 1, MAKE —UP AIR UNIT. PROVIDE TYPED DIRECTORIES FOR PANELBOARD BRANCH CIRCUIT IDENTIFICATION. IDENTIFY EACH CIRCUIT BREAKER AS TO THE EXACT ROOM NUMBERS OR AREA SERVED AND THE TYPE OF CIRCUIT, I.E. "ROOMS 101 -104 LIGHTS" OR "CAFETERIA EXHAUST FAN ". EQUIPMENT CONNECTIONS: THIS CONTRACTOR SHALL BRING ALL REQUIRED ELECTRICAL SERVICE TO ALL EQUIPMENT ITEMS FURNISHED UNDER OTHER SECTIONS OF THESE SPECIFICATIONS OR BY THE OWNER, MAKE FINAL CONNECTIONS, AND LEAVE EQUIPMENT READY FOR OPERATION. THIS CONTRACTOR SHALL COORDINATE WITH ANY AFFECTED TRADE TO ASSURE CORRECT OPERATION OF THE EQUIPMENT ITEM. CONTROL AND INTERLOCK WIRING: EXCEPT AS OTHERWISE INDICATED ON THE DRAWINGS, ALL CONTROL AND INTERLOCK WIRING SHALL BE PERFORMED BY THE RESPECTIVE CONTRACTORS. THE ELECTRICAL SUBCONTRACTOR SHALL INSTALL ALL STARTERS, PILOT SWITCHES, CONTROL DEVICES AND MISCELLANEOUS ITEMS OF ELECTRICAL EQUIPMENT FURNISHED UNDER OTHER SECTIONS OF THESE SPECIFICATIONS THAT ARE NOT INTEGRALLY MOUNTED WITH THEIR ASSOCIATED EQUIPMENT. DRY TYPE DISTRIBUTION TRANSFORM RS• TRANSFORMERS TO BE DRY —TYPE WITH NATURAL DRAFT VENTILATION. UNITS TO BE RATED FOR 480 VOLTS, 3 PHASE, 3 WIRE PRIMARY, AND 120/208 VOLTS, 3 PHASE, 4 WIRE SECONDARY, UNLESS OTHERWISE INDICATED. UNITS TO BE DESIGNED FOR 60 HERTZ OPERATION, WITH KVA CAPACITIES AS SHOWN ON DRAWINGS. TRANSFORMERS TO CONFORM WITH APPLICABLE NEMA AND ANSI STANDARDS, INCLUDING NEMA TP -1 ENERGY EFFICIENT STANDARDS AND BE UL LISTED. TRANSFORMERS TO HAVE CLASS H INSULATION, HIGH GRADE SILICONE STEEL CORES, AND BE RATED FOR A MAXIMUM TEMPERATURE RISE OF 115 DEGREES C. UNITS RATED 30 KVA AND LARGER TO HAVE FOUR 2 1/2% TAPS BELOW NORMAL AND TWO 2 1/2% TAPS ABOVE NORMAL. UNITS RATED LESS THAN 30 KVA TO HAVE TWO 5% TAPS BELOW NORMAL. SOUND LEVELS GENERATED BY TRANSFORMERS ARE NOT TO EXCEED THE FOLLOWING VALUES: 9 KVA AND LESS —40 DB, 10 TO 45 KVA —42 DB, 50 TO 150 KVA —45 DB. SERVICE : THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING SERVICE WITH THE UTILITY COMPANY. ALL CHARGES ASSOCIATED WITH SERVICE SHALL BE PAID BY THE E.C. PROVIDE UTILITY REQUIRED METERING PROVISIONS. PROVIDE CT CAN OR CONCRETE PAD FOR TRANSFORMER AS REQUIRED. PROVIDE CONDUIT FOR UTILITY PRIMARY IF REQUIRED. EC SHALL WORK DIRECTLY WITH THE UTILITY AND SHALL COMPLETE AND SUBMIT ALL LOAD DATA SHEETS REQUIRED FOR SERVICE APPLICATION, WHERE A NEW SERVICE IS NOT REQUIRED, BUT LOADS ARE ADDED TO AN EXISTING SERVICE, E.C. SHALL NOTIFY UTILITY OF ADDITIONAL LOADS E.C. SHALL PROVIDE THIS INFORMATION AT BEGINNING OF PROJECT TO ALLOW TIME FOR A TRANSFORMER CHANGE OUT IF NECESSARY. VIBRATION ISOLATION AND SEISMIC RESTRAINT ALL EQUIPMENT AND CONDUIT FURNISHED AND INSTALLED UNDER THIS CONTRACT SHALL BE SEISMICALLY RESTRAINED BY CHAPTER 16 OF THE NORTH CAROLINA STATE BUILDING CODE, VOL. 1 — GENERAL CONSTRUCTION AND SPECIFICALLY SECTION 1607.6.4 AND TABLE 1607.6.4A WHICH RELATES TO MECHANICAL AND ELECTRICAL COMPONENTS. SUBMITTALS: SHOP DRAWING SUBMITTALS WILL BE REQUIRED FOR THIS PROJECT. SUBMIT EIGHT (8) COPIES OF ALL LIGHT FIXTURES AND MAJOR SPECIFIED EQUIPMENT TO THE ENGINEER FOR APPROVAL. THE ELECTRICAL CONTRACTOR SHALL REVIEW ALL SUBMITTALS AND MAKE CORRECTIONS AS REQUIRED PRIOR TO SUBMITTING TO ENGINEER FOR APPROVAL. THE CONTRACTOR SHALL ALSO AFFIX HIS STAMP TO THE SUBMITTALS INDICATING THAT HIS REVIEW HAS BEEN COMPLETED. IT IS UNDERSTOOD THAT PROOF OF EQUALITY IS THE RESPONSIBILITY OF THE CONTRACTOR AND /OR SUPPLIER AND THAT IT IS NOT THE RESPONSIBILITY OF THE ENGINEER TO PROVE THE INEQUALITY OF THE PROPOSED SUBSTITUTIONS. FURTHERMORE THE DECISION OF THE ENGINEER IS FINAL. SHOULD ANY SUBSTITUTE ITEMS BE SUBMITTED AND DISAPPROVED, THEN THOSE ITEMS MUST BE FURNISHED EXACTLY AS DESCRIBED HEREIN. THE ENGINEER'S REVIEW OF SHOP DRAWINGS AND /OR SUBMITTAL DATA SHALL NOT RELIEVE THE CONTRACTOR OF RESPONSIBILITY FOR DEVIATIONS FROM THE CONTRACT DRAWINGS OR SPECIFICATIONS. ELECTRICAL SYSTEM AND EQUIPMENT METHOD OF COMPLIANCE: Prescriptive _!_ Performance Energy Cost Budget Provide a standard riser diagram which indicates designated points for check metering. Provide a standard panel schedule description which identifies different enduse loads. Lighting schedule lamp type required in fixture EXISTING number of lamps in fixture EXISTING ballast type used in the fixture EXISTING number of ballasts in fixture EXISTING total wattage per fixture EXISTING total interior wattage specified vs allowed EXISTING total exterior wattage specified vs allowed EXISTING Equipment schedules with motors (not used for mechanical systems) motor horsepower EXISTING number of phases EXISTING minimum efficiency EXISTING motor type __ EXISTING #of poles EXISTING DESIGNER STATEMENT:' To the best of my knowledge and belief, the design of this building complies with the electrical system and equipment re quirements of the North Carolina State Building rg Code: ney Cons rvation Code SIGNED: �A /� 2006. � NAME: onald R. Brittain TITLE: North Carolina Professional Engineer #7883 EXISTING UTILITY METER BASE TO BE REMOVED AND REPLACED W/ A NON —FUSED DISCONNECT. REFER TO "REVISED POWER RISER" BELOW. u EXISTING FEEDER TO REMAIN. EXISTIN EXISTING PANEL "A" 120/208V 10, 3 —WIRE 150A EXISTING PANEL A 120/208 VOLTS, 1 EXISTING AMPS RMS. SYM. I.C. INTEGRATED EQUIPMENT RATING PHASE, 3 WIRE, 150 AMP MAIN FLUSH MOUNTED BREAKER SERVES LOAD No A —^ —^ 90 90 —^ —^ —^ —^ B ^— ^— ^— ^— ^— ^— ^— ^— NO ® LOAD SERVES LIGHTING 1.23 1 2 0.80 RECEPTALCES UGHTING 1.23 3 4 0.80 RECEPTALCES HVAC UNIT 7.3E 5 6 EXISTING OR BY OTHERS SPACE LIGHT FIXTURE 7.36 7 8 PILOT LIGHT , DIMMER AFF SPARE 9 10 WP V GFI WEATHERPROOF GROUND FAULT SPACE QUAD —PLEX RECEPTACLE 11 12 13 14 15 16 TOTAL CONNECTED LOAD: 19.0 KVA ESTIMATED ALL BREAKERS ARE 1P -20A UNLESS OTHERWISE NOTED PANEL NOTES: ++ ALL LOADS ARE E(ISTING. PANEL SCHEDULE SHOWN FOR REFERENCE ONLY. ** EXISTING SERVICE ENTRANCE GROUNDING AND BONDING TO BE REMOVED. PANEL "A" WILL NO LONGER SERVE AS A SERVICE ENTRANCE PANEL. REMAIN EXISTING #6 COPPER GROUND CONDUCTOR TO REMAIN. TOWER RISER NTS F EXISTING "MDP" 120/208V, 30, 4 —WIRE, 2500A LOCATED IN ELECTRICAL ROOM 110 REVI EXISTING PANEL "A" Q 120/208V 4 10, 3 —WIRE 150A EXISTING Q1 INSTALL 200A FUSES IN EXISTING SPARE 600A SWITCH. FUSE REDUCERS SHALL BE REQUIRED. REFER TO LITTLE FUSE CO. PART #LRU2662R, OR EQUAL, FOR FUSE REDUCER. EC SHALL VERIFY W/ MANUFACTURE THAT FUSE REDUCER CHOSEN WILL OPERATE AS REQUIRED. Q2 3 #3/0, #6 GND, 2 "C. Q3 250/200/10, FUSE ® 150A. LOCATE IN ELECTRICAL ROOM BESIDE MDP. ® 3 #1/0, #6 GND, 1 1/2 "C. 05 250/200/10/3R/NF, TO REPLACE EXISTING METER. REFER TO "EXISTING POWER RISER" ABOVE. © EXISTING #6 COPPER GROUND CONDUCTOR. INSTALL (2) NEW 3/4 "X10' -0" GROUND RODS AND RECONNECT #6 GROUND. ELECTRICAL L SYMBOL DESCRIPTION oo CONDUIT — CONDUIT UNDERFFLOOR OR UNDERGROUND " \1 ARROW INDICATES HOMERUN, TICKMARKS: NEUTRAL,PHASE,GND. 0 0 POWER PANEL ® EXISTING PANEL T TELEPHONE BOARD —T— TELEPHONE CONDUIT V TELEPHONE OUTLET JQ JUNCTION BOX ❑' DISCONNECT SWITCH; FUSED; NONFUSED FPN FUSE PER NAMEPLATE S,,., MOTOR TOGGLE SWITCH _ MOTOR EXISTING OR BY OTHERS Q 0 LIGHT FIXTURE S S S4 SINGLE POLE SWITCH , 3 WAY, 4 WAY S S PILOT LIGHT , DIMMER AFF ABOVE FINISHED FLOOR DUPLEX RECEPT ABOVE COU WP V GFI WEATHERPROOF GROUND FAULT 41 QUAD —PLEX RECEPTACLE ED POWER R ISE N NTS 250/200/10/3R/NF 3 #1/0, #6 GND, 1 1/2 "C, TO NEW DISCONNECT LOCATED IN ELECTRICAL ROOM BESIDE MDP. REFER ALSO TO "REVISED POWER RISER" THIS SHEET. DISTANCE IS APPROX. 180' -0 ". MDP -1 INSTALL (1) 3/4" PVC CONDUIT, W/ PULL STRING, FROM MOBILE CLASS ROOM UNIT TO ELECTRICAL ROOM FOR DATA AND TELEPHONE CABLING BY OTHERS. VERIFY EXACT "STUB —UP" LOCATIONS W/ OWNER. DISTANCE IS APPROX. 180' -0 ". 0 FLOOR PLAN - ELECTRICAL SCALE 1/4" = 1' - 0 " I�r�rr��I -'Ns I -NPI. f 00[�Uli9flgl R6 O'INAL Oa�81,tG TH C0i132SE OF FIND C -11'I_ V OF TF±6S Picfl' ^C' AUG 2 2 470) .D RB , U U) Z W W Z C7 � Z W Za U I Off WW COM W IjmN oo _Z Jm� c0 Ud� 0 0 W= 2 Z" W CD J z Z M W O 1, mi O p o Cl) LL o� a O Z aJo a �OQ Z =� W Cal c O J z c >- W M �Yo v O � _v O O= J = 3 It nNe O JOB NO. 117700 OWN BY: DGR DATE: 8/21/07 SCALE: AS SHOWN 011:I2I:111Ir E =1 OF