MACKIE JOHNSON, ARCHITECT
i
OFFICE: 828-464-1028 FAx:828 -465 -4562
MAILING ADDRESS SHIPPING ADDRESS
P. O. Box 428 11 4 TH AVENUE S W
CONOVER, N. C. 28613 ONOVER, N.C. 28613
MJA p@MACKIEJOHNSON.COM
APRIL 8, 2011
PROJECT CONSTRUCTION MEMO (PLAN REVIEW COMMENTS)
NUMBER (RESPONSE TO CODE COMMENTS DATED 02- 21 -11)
DELIVERY: HAND DELIVERY - ONLY
PROJECT: A NEW TENANT UPFIT FOR:
MOUNTAIN VIEW URGENT CARE
CONTRACTOR: DAVID E. LOOPER, INC.
FROM: BARRY (CARD, AIA - MACKIE JOHNSON, ARCHITECT
TO: CATAWBA COUNTY — JAMES LAMB
HICKORY DEVELOPMENT ASSISTANT CENTER
COPY TO: BRIAN WALKER -DAVID E. LOOPER, INC
REFERENCE: REPLY TO REVIEW COMMENTS DATED 02 -21 -11
BUILDING STATUS: (COMPLETE - DISAPPROVED)
Comment # 1:
A written response to the comments in the order they appear in this correspondence as
well as appropriate clouded revisions to the plans shall be provided.
(We shall comply)
Comment # 2:
Provide 60 inch circular turning diameter in Exam room 1, 2, 3 and 4.
(See attached revised drawing -A+15 t
,8,, A . )
FIRE STATUS: (PLAN RECEIVED - APPROVED WITH NOTES)
Comment # 1:
Appendix B identifies a fire alarm system for this space, Electrical sheets does not detail
a fire alarm system. Verify if a Fire Alarm System (audible /visual notification devices) is
being installed or if there is only a Fire Alarm Panel only in this building to monitor the
required Sprinkler system.
(A Fire Alarm System will be installed)
PAGE 1 OF 2
Comment # 2:
If a fire alarm system with notification devices is to be installed, Engineered signed and
sealed Fire Alarm System plans would be required. Fire alarm contractor shall obtain a
permit from the Fire Prevention Bureau prior to any installation of the fire alarm system.
A copy of submittal requirements and applications are available upon request, 828 -323-
7522 or available on line at http: / /www.hickorygov.com /department/ /division.php ?fDD =8-
13
(We shall comply)
Comment # 3:
Sprinkler contractor shall obtain a permit from the Fire Prevention Bureau prior to
beginning any installation /renovation of the sprinkler /standpipe system. A copy of
submittal requirements and applications are available upon request, 828 - 323 -7522 or
available on line at http: / /www.hickorygov.com /department/ /division.php ?fDD =8 -13
(We shall comply)
Comment # 4:
See Hickory Fire Prevention Bureau plan review comments for Unifour Family Practice
dated 10/06/2010, some of the items noted may also be applicable for this upfit.
(We shall comply)
GENERAL NOTES:
1. Street numbers shall be posted on the building and visible from the roadway.
Numbers shall contrast with their background. Numbers shall be a minimum of 4 inches
high with a minimum stroke width of 0.5 inches.
2. Portable fire extinguishers shall be selected, installed and maintained in accordance
with Section 906 of the 2009 North Carolina Fire Prevention Code and NFPA 10.
3. See 09 North Carolina Building Code Chapter 33 Safeguards During Construction and
sections of 09 North Carolina Fire Prevention Code Chapter 14 Fire Safety During
Construction and Demolition that would be applicable to this project.
4. The building space shall not be occupied prior to the code official issuing a permit that
indicates that applicable provisions of the NC Fire Code has been met.
5. Occupant shall obtain a Fire Department Use Permit.
Please contact if assistance or questions regarding plan review comments:
Kelly Davis
Plans Examiner
Hickory Fire Prevention Bureau
76 N. Center Street NE
Hickory, NC 28601
(828) 323 -7522 - phone (828) 323 -7476 - fax
kdavis @ci. hickory. nc. us
ZONING STATUS: (APPROVED)
ATTACHMENTS:SIX SETS OF REVISED DRAWINGS ONLY
PAGE 2OF2
END OF PROJECT CONSTRUCTION MEMO NUMBER ONE