HomeMy WebLinkAbout09-003570001.PDFCity Structums D&P. Inc. Eogineet*g fbir Amhftctary September 21, 2009 Teresa Hamby, Plans Facilitator 76 North Center Street Hickory, North Carolina 28601 Re. Inspection Comment Responses Reference * PLN2009-00357 Project No. 09-45 September 18, 2009 This letter coinnrms that the existing roof joists in the location shown on , drawing A4.1 have an adequate load capacity to support the suspended exhaust hood, The suspended exhaust hood weighs up to 1100#. At points of suspension, mom than 4" from a joist panel point, provide L 1 % x L 1 �� web stiffbners as indicated on detaH 4122. Sincereiy, 1,111'. � 0 A R EA Eddie Cobb, PE a -S Located in The Lewisvilie Mill -6275- Shalloo Orcd Road - Suite 200 - Lowisvilie, NC 27023-0760 Phow (336) 945-1105 - Fax (336) 445-1107 I U'he's ite'dure, L).C. Donatos Pizza at Second Street Sguare Hickory, North Carolina Inspection Comment Responses Reference # PLN2009-0035�7 PrQject No. 09-45 September 18, 2009 Teresa'Flamby Plans Facilitator Development Assistance Centei- 76 North Center Street Hickory, North Carolina 28601 Dear Ms, Hamby: The following items represent responses and clarifications to the construction documents per the comments from the inspections department, ZoDing 1, 10. 1 1.6(b) All of the mechanical equipment including hood exhaust will be screened from view from all off -site approaches. Existing parapet heights will be high enough to screen all new equipment. 2, 1, 0,7,1 All solid waste will be placed in the existing on -site durnpsters. 1 Signage will be covered under a separate application. Catawba Coun_h, Plans Review I . Sheet C2: sheet removed from the set per conversation w/ Steve Deitz. 1 Sheet A1 1: hood emergency activation switch is located along wall in direction of egress travel. It is located on the wall on the left side of the can wash. It is located per 2009 NCBC 904.11.1. 1 Sheet A2.1 . restrooms do meet requirement of 60 Inch clear floor space per NCAC 11,3.2.2. Allowance for 12 inch overhang of door swing. Drawings show 10 1/8" overhang. 4. Sheet A4.1 : see Detail 4110 for platform detail that supports 100 gallon hot water heater 155 SWInYT1011 COUrt, SUiIC 100 WiTlston-Salem, NC 27106 336-722-4447 Fax 336-722-4402 0 Donatos Pizza at Second Street Square September 18, 2009 Page 2 above mop sink. 5. Sheet A6,2: restrooms do meet requirement of 60 inch clear floor space per NCAC 11.3.2.2. Allowance for 12 inch overhang of door swing. Drawings show 10 1/8'" 6. Sheet A62: See revised elevation note 1. Si rage to be submitted as separate package. 7. Sheet A6.3: removed from set per conversation w/ Steve Reitz. 8. Captiveair Drawings: sheets removed from set per conversation w/ Steve Reitz.. 9. Eastern Food Equipment Drawings, sheets removed frorn set per conversation w/ Steve Deitz. 10, Sheet S2. sheet removed from set per conversation w/ Steve Deitz, IL Sheet P I: floor sink at prep sink has been routed through, grease interceptor, per 2009 NCPC 1003.3.1, 12. Sheet P 1: See detail 4110 for platform supporting the 100 gallon water heater above the mop sink. 13, Sheet MI: See attached letter from structural engineer stating that the existing bar joists were designed to carry the load of the exhaust hood. 14. Sheet M2- See note on sheet M2 stating that the kitchen hood exhaust will not affect gas water heater function. 15. Sheet M2: A note has been added to the hood detail to install the hood as per the manufacturer's recommendations and to maintain the inanufacturer's required clearances. After checking with the hood manufacturer (Captiveaire), the hood typically needs to be 18" from combustibles (tlic ceiling tiles are not combustibles per USG). Captiveaire also st ated. that they make a 0" to combustibles hood but that it is a very custom hood and is only installed in appli cati ons where you are surrounded with wood construction within 18 which is not our scenario. 16. Sheet El: See revised sheet showing the total load of each panel, in KVA. 17. Sheet E2: The service entrance and feeder conductors have been resized per 2008 NEC 338.10(13)(4)(b) and 340.80. Fire Marshal 1. The occupant load has been verified and per conversations with fire marshal modified to meet egress requirements. The Appendix B has been revised to show the proper occupant load for each area. Sheet A2.2 has been revised to show tables and chairs in lieu of booths in the dining, area. 2, The Appendix B has been revised showing that a Fire Alarrn System is not going to'be installed. Donatos Pizza at Second Street Square September 18., 2009 Page 3 Environinental Health 1, The hand sinks in the kitchen area will come with splashguards on both sides standard. I The rack- next to the three compartment sink and aqjacont wall have been reconfigured so the wall will be next to the three compartment sink and the rack, will be next to the prep sink. The rack is used for storage of food prep items. 3. The hand sink has been relocated closer to the order taking area along the wall that it is on now 4, The six gallon hot water heater will be used to service the restroom sinks and hand sinks. The six gallon hot water heater temperature will be set to I 10 degrees Fahrenheit versus the main hot water heater tetilperature of 140 degrees Fahren-lieit. The following items are included with this package: 0 Letter from structural engineer stating that the bar joists were designed to handle the lend of the exhaust hood, Sincerely,, Vaughn P. Shaffer Prepared by: Vaughn P. Shaffer Thomas H. Hughes / Architecture, PC CC. Jamey Horton City of Hickory — Development Assistance Center File