HomeMy WebLinkAboutEHPR-3-11-9766 (2).TIF � •
� PLAN REVIEW RESPONSE COMMENTS
�
Case #: CBPR-3-11-9762 Status: Disapproved
REVIEW RECEIVED COMPLETED STATUS ASSIGNED TO
Building Review 03/10/2011 Requires Re-Submit Bill Rogers
FIRST REVIEW
04/15/2011
A written response to the comments in the order they appear in this correspondence as welt as appropriate
clouded revisions to the plans shall be provided.
1. Sheet 1- The side exit of this building is designed to discharge onto a concrete pad. Per NCBC section
1007.1, both exits from this occupancy are required to be accessible. Per NCBC section 1024.6 the exterior
path of travel to a public way and shall be a fixed, firm, nonslip surface a minimum of 42 inches in width.
Egress path shall be shown on drawings.
1. SHOWED SIDEWALK FROM SIDE DOOR TO FRONT SIDEWALK
2. Sheet 2- Appendix B shows the occupant load being based on 15 square foot per person. This would be
assuming the presence of tables and chairs. If the building is to be set up with tables and chairs then a
layout shall be provide . If no layout is provided the occupant load shafl be based on the two highest
occupant loads in accordance with NCBC Table 1004.1.1( concentrated, standing space).
2. SHOWED TABLE LAYOUT FOR OCCUPANCY LOAD ON SHHET 3.
3. Sheet 3- Provide door hardware schedule. Per NCBC section 1008.1.9, panic hardware shall be installed
on all egress doors in this occupancy.
3. SHOWED PANIC HARDWARE ON EGRESS DOORS IN SCHEDULE.
4. Sheet 3- Per NCBC Section2406.3 #6, Window on each side of main entry door are closer than 24 inches
to the door by scale. These windows shall contain safety glazing,
4. MOVED WINDOW LOCATION SO THEY ARE MORE THAN 24" FROM FRONT DOOR.
5. Sheet 3= Cabinet installation shall comply with the requirements of ICC/ANSI A117.1-2003 chapter.
5. SHOWED CABINET INSTALLATION DETAILS.
6. Sheet P- 2- Water closet Detail- A vertical grab bar shall be instalied in accordance with ICC/ANSI
A117.1-2003 section 604.5.1
6. SHOWED VERTICAL GRAB BAR AT WATER CLOSET.
7. Page M-I Per- An attic Access shall be provided in accordance with NCMC section 306.3. Provide
location of attic access.
7. ATTIC ACCESS SALL BE FROM REMOVAL OF 2X2 ACCOUSTICAL CEILING.
Comments: Created from Permit BLDC-3-11-15934.
RECEIVED
APR 21 2011
CA7AW8l1 C
ENVIAOMVfENTAL TH
:�
�
` �