HomeMy WebLinkAboutBLDR-1-11-14704 ENG LTR RETAINING WALL.tif • TAYLOR AND VIOLA
STRUCTURAL ENGINEERS
J. KIRK VIOLA, P.E. JAMES S. T
ATE, P.E. JASON M. BEEP, P.E.
,g January 26, 2011
Mr. Jon Beaver
Pleasure Pool & Spas
1952 Briarwood Drive
Hickory, NC 28602
3
RE: Segmental Retaining Wall
Tim Holt Residence
6362 Hayden Drive
Hickory, NC
Dear Mr. Beaver:
i
Per your request I have analyzed the subject segmental retaining wall. The wall is
approximately 5' -0" in height at its maximum with a level backfill, and will be
constructed with HIGHLAND STONE segmental - locking units at a 10.6 setback. The
wall shall be backfilled with compacted porous gravel and reinforced with 5' -0" lengths
of geogrid located vertically at approximately 1/3- points of the wall height (elevations 2'-
0" and 4' -0" below upper grade elevation). The gravity of the compacted backfill along
the length of the 5' -0" geogrid is utilized to resist the active soil pressure of the retained
backfill.
The wall as described is adequate to resist the anticipated soil pressures.
If you have any questions or comments, please feel free to contact me.
Sincerely,
TAYLOR & VIOLA STRUCTURAL, ENGINEERS, P.C.
O //yy�` y ea e , •i' "
d : O
Jason M. Reep PE -
1
02; 8,
° .� ! n R
P.O. BOX 2616 • 231 13TH AVENUE PLACE N.W.. NORTHWEST PROFESSIONAL PARK
HICKORY, NORTH CAROLINA 28603 • TELEPHONE (828) 328 -6331 • FAX: (828) 322 -1801
F
• TAYLOR AND VIOLA
STRUCTURAL ENGINEERS
J. KIRK VIOLA, P.E. JAMES S. TATE, P.E. JASON M. REEP, P.E.
January 26, 2011
Mr. Jon Beaver
Pleasure Pool & Spas
1952 Briarwood Drive
Hickory, NC 28602
RE: Segmental Retaining Wall
Tim Holt Residence
6362 Hayden Drive
Hickory, NC
Dear Mr. Beaver:
Per your request I have analyzed the subject segmental retaining wall. The wall is
approximately 5' -0" in height at its maximum with a level backfill, and will be
constructed with HIGHLAND STONE segmental- locking units at a 10.6 setback. The
wall shall be backfilled with compacted porous gravel and reinforced with 5' -0" lengths
of geogrid located vertically at approximately 1/3- points of the wall height (elevations 2%
0" and 4' -0" below upper grade elevation). The gravity of the compacted backfill along
the length of the 5' -0" geogrid is utilized to resist the active soil pressure of the retained
backfill.
The wall as described is adequate to resist the anticipated soil pressures.
If you have any questions or comments, please feel free to contact me.
Sincerely,
TAYLOR & VIOLA STRUCTURAL ENGINEERS, P.C � +ecle