HomeMy WebLinkAboutCBPR-12-10-8646 WPCOG ARCHITECT COMMENTS.tif t o _ 9 C�P12 CODE REVIEW WRITTEN RESPONSE TO COMMENTS WPCOG — New Construction DATE — 0104 2011 ------------------------------------------- i I PROJECT - 279319611443 CODE JURISDICTION — Catawba County, NC DEPARTMENT — BLDG FIRE REVIEWER — Bldg - Steve Deitz Fire - William Bump ----------------------------------------------------------------------------------------------- We have attempted to fully comply with all code comments and requests. Regards, Ray Campbell ;A g . 9 Campbell Design, PA Architecture and Interior Design Ray Campbell, AIA Project Manager Campbell Design Architecture + Interiors 4511 North Highway 16 Denver, NC 28037 (704) 489 -1438 Fax: (704) 489 -1439 www.campbelldesign.com f C o— 96 CODE REVIEW WRITTEN RESPONSE TO COMMENTS WPCOG — New Construction DATE — 01 04 2011 ----------------------------------------------------------------- PROJECT - 279319611443 CODE JURISDICTION — Catawba County, NC DEPARTMENT — BLDG FIRE REVIEWER — Bldg - Steve Deitz Fire - William Bump ---------------------------------------------------------------------- We have attempted to fully comply with all code comments and requests. Regards, / Ray Campbell IA Campbell Design, PA Architecture and Interior Design Ray Campbell, AIA Project Manager Campbell Design Architecture + Interiors 4511 North Highway 16 Denver, NC 28037 (704) 489 -1438 Fax: (704) 489 -1439 www.campbelldesign.com BLDG - Steve Deitz — (email) Review Comments: 1. A written response to the comments in the order they appear in thi correspondence as well as appropriate clouded revisions to the plans shall b P rovid ed ' RESPONSE — WILL COMPLY 2. GENERAL NOTE: ALL MATERIALS ABOVE THE CEILING LINE SHALL BE PLEMUM RATED. RESPONSE — WILL COMPLY reflected clg sheet 3. Sheet CS.3: Head of wall detail roof construction does not agree with the roof construction of this building. Provide complete head of wall detail that does agree. RESPONSE — WILL COMPLY added detail 4. Sheet CS.3: UL designs furnished do not agree � 411 o r revise Appendix Appendi geas A ppendix B. Provide complete UL Design for UL 465 required. RESPONSE — WILL COMPLY revised to agree -9 must be sealed, signed, and dated by a design 5. GENERAL NOTE: Sheets C -1 thru C professional licensed in North Carolina. RESPONSE — WILL COMPLY 6. Sheet A.O: General note — All signs must be submitted and permitted separately. RESPONSE — WILL COMPLY zoning will get a copy and approve 7. Sheet Al .1: Verify that toilet stall doors on handicap accessible stalls area self - closing per ICC / ANSI Al 17.1 -2003 604.8.3 RESPONSE — WILL COMPLY will double check in shop drawing phase as well 8. Sheet A1.1: Men's toilet ambulatory stall door swing does not meet ICC / ANSI Al 17.1 -2003 section 604.9.3 and the large scale toilet room layout. Revise. RESPONSE — WILL COMPLY revised so that both match } 9. Sheet P -3: Provide water hammer arrestors at dishwashers, icemaker, etc. per 2009 NCPC 604.9 or verify that water distribution piping is not metallic. (Materials above ceiling shall be plenum rated.) RESPONSE — WILL COMPLY 10. E.2: Provide exit signs from conference room #184 (left side) to exterior of building. RESPONSE — WILL COMPLY 11. Sheet E.5: Verify that all exit signs have 2 bulbs per 2008 NEC 700.16. RESPONSE — WILL COMPLY s g i BLDG - Steve Deitz — (email) Review Comments: 1. A written response to the comments in the order they appear in this correspondence as well as appropriate clouded revisions to the plans shall be provided. RESPONSE — WILL COMPLY 2. GENERAL NOTE: ALL MATERIALS ABOVE THE CEILING LINE SHALL BE PLEMUM RATED. RESPONSE — WILL COMPLY reflected clg sheet 3. Sheet CS.3: Head of wall detail roof construction does not agree with the roof construction of this building. Provide complete head of wall detail that does agree. RESPONSE — WILL COMPLY added detail 4. Sheet CS.3: UL designs fiunished r the as Appendix B. Provide complete UL Design for UL 465 and UL 411 o required. RESPONSE — WILL COMPLY revised to agree 5. GENERAL NOTE: Sheets C -1 thru C -9 must be sealed, signed, and dated by a design professional licensed in North Carolina. RESPONSE — WILL COMPLY 6. Sheet A.O: General note — All signs must be submitted and permitted separately. RESPONSE — WILL COMPLY zoning will get a copy and approve 7. Sheet Al. 1: Verify that toilet stall doors on handicap accessible stalls area self - closing per ICC / ANSI A117.1 -2003 604.8.3 RESPONSE — WILL COMPLY will double check in shop drawing phase as well 8. Sheet Al. 1: Men's toilet ambulatory stall door swing does not meet ICC / ANSI Al 17.1 -2003 section 604.9.3 and the large scale toilet room layout. Revise. RESPONSE — WILL COMPLY revised so that both match 9. Sheet P -3: Provide water hammer arrestors at dishwashers, icemaker, etc. per 2009 NCPC 604.9 or verify that water distribution piping is not metallic. (Materials above ceiling shall be plenum rated.) RESPONSE — WILL COMPLY 10. E.2: Provide exit signs from conference room #184 (left side) to exterior of building. RESPONSE — WILL COMPLY 11. Sheet E.5: Verify that all exit signs have 2 bulbs per 2008 NEC 700.16. RESPONSE — WILL COMPLY i FIRE — William Bump — (email) Review Comments: 1. Pg C -1— Per NCFC 508.5.1 — Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more the 400 feet (122m) from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the building, on -site fire hydrants and mains shall be provided where required by the fire code official. The hydrant indicated on the plans exceeds this distance when measured along the apparatus routes to the front of the facility. RESPONSE — WILL COMPLY a new hydrant is shown on the site plan, however owner wants to explore the option of using another existing hydrant. Instead of adding one. 2. Per NCFC 505.1— New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102mm) high with G l minimumm stroke idth of .5 inches (12.7mm). Coordination with the Catawba County Department will be required to ensure proper numbering. RESPONSE — WILL COMPLY added to elevation sheet 3. Add one 4A:60BC fire extinguisher at Offices 136/137 to provide adequate distribution per NFPA 10. RESPONSE — WILL COMPLY added 4. Emergency Lighting shall include the areas of exit discharge. This is not indicated of Page E.2. RESPONSE —WILL COMPLY some of the emergency lighting is in the can fixtures 5. A complete set of fire alarm plans shall be submitted for approval prior the installation of any component of the fire alarm system. RESPONSE — WILL COMPLY 6. Duct detectors shall be connected to the buildings fire alarm control panel. RESPONSE — WILL COMPLY 7. Page EA indicates a KNOX Box provided at the front of the building. Coordinate with the Long View Fire Department at 828- 322 -1311 to obtain the application and determine the approved mounting location. 't RESPONSE — WILL COMPLY will meet or coordinate 8. Page E.3A shows an exit indication near the rear wall of the left side of the Conference Room. Please provide clarification. RESPONSE — WILL COMPLY this was removed because it reefed to an earlier door that was shifted down END OF REPORT A • c t�P� - �Z - to -� b�tL FIRE — William Bump — (email) Review Comments: 1. Pg C -1 — Per NCFC 508.5.1 — Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more the 400 feet (122m) from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the building, on -site fire hydrants and mains shall be provided where required by the fire code official. The hydrant indicated on the plans exceeds this distance when measured along the apparatus routes to the front of the facility. RESPONSE — WILL COMPLY a new hydrant is shown on the site plan, however owner wants to explore the option of using another existing hydrant. Instead of adding one. 2. Per NCFC 505.1 — New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102mm) high with a minimum stroke width of .5 inches (12.7mm). Coordination with the Catawba County GIS Department will be required to ensure proper numbering. RESPONSE — WILL COMPLY added to elevation sheet 3. Add one 4A:60BC fire extinguisher at Offices 136/137 to provide adequate distribution per NFPA 10. RESPONSE — WILL COMPLY added 4. Emergency Lighting shall include the areas of exit discharge. This is not indicated of Page E.2. RESPONSE — WILL COMPLY some of the emergency lighting is in the can fixtures 5. A complete set of fire alarm plans shall be submitted for approval prior the installation of any component of the fire alarm system. RESPONSE — WILL COMPLY 6. Duct detectors shall be connected to the buildings fire alarm control panel. RESPONSE — WILL COMPLY 7. Page E.4 indicates a KNOX Box 828-322-1311 1 t obtain the application the Long View Fire Department at on and determine the approved mounting location. RESPONSE — WILL COMPLY will meet or coordinate 8. Page E.3A shows an exit indication near the rear wall of the left side of the Conference Room. Please provide clarification. RESPONSE — WILL COMPLY this was removed because it reefed to an earlier door that was shifted down END OF REPORT