January 18, 2011
Catawba County Plan Review
Attn: Steve Deitz
76 North Center Street
Hickory, NC 28601
Re: Zion Lutheran Church
1911 Zion Church Road
Hickory, NC 28602 g
Ref# BLDC -12 -10 -14096
Dear Steve,
Thank you for time working with us on this project. We have tried to address each
of your questions or concerns and have revised drawings when appropriate to do
so.
s.
BUILDING REVIEW
l
1. A written response has been provided along with revised clouded drawings
when appropriate.
2. I can provide a date on each sheet that we are not revising. Any revised sheet
will have a date on them. I can come by and date the others if you need me to.
3. Steve, we may have to discuss this next one, however, there is absolutely
nothing in this church project that would ever have us get to an Institutional
Occupancy. First of all, Zion Lutheran Church is a church. As such, it is an
A -3 occupancy. The educational, or Sunday school rooms are clearly covered
under 305.1. Religious educational rooms, which are accessory to places of z
worship in accordance with Section 508.3.1 and have occupant loads of less
than 100, shall be classified as A -3 occupancies. Those spaces are accessory
to the place of worship and are not, according to 508.3.1 exception 3, a
separate occupancy. Here is the bottom line. They are not going to sprinkle
the building, nor are they required to. They are not an Institutional
occupancy. Where did you get Mothers Morning Out anyway? It could only
have come from the cabinet elevations which were old and never got revised.
Those elevations have now been revised to reflect whats on the plans.
They may not make any changes to their existing programs that are currently
operating at the church. If, and only if, they did decide to use the rooms in the z
future to expand that program, and if it is suggested that by having a part time
mothers morning out program, which is part of the ministry at Zion Lutheran
Church, is what makes the project Institutional, then they would not do it.
With that being said, the number of children in any of the rooms being
3
{
i
Member of the American Institute of Architects • National Council of Architectural Registration Boards Certified
C.P>(r- -I $��s
WINSTEAD 0 ARCHITECTURE, PLLC
22 North Main Avenue P.O. Box 321 &mail: winarch@bellsouth.net
Newton, North Carolina 28658 Telephone: (828) 464 -2827
Fax: (828) 4643229
January 18, 2011
Catawba County Plan Review
Attn: Steve Deitz
76 North Center Street
Hickory, NC 28601
Re: Zion Lutheran Church
1911 Zion Church Road
Hickory, NC 28602
Ref# BLDC -12 -10 -14096
Dear Steve,
Thank you for time working with us on this project. We have tried to address each
of your questions or concerns and have revised drawings when appropriate to do
so.
BUILDING REVIEW
k 1. A written response has been provided along with revised clouded drawings
when appropriate.
2. I can provide a date on each sheet that we are not revising. Any revised sheet
will have a date on them. I can come by and date the others if you need me to.
3. Steve, we may have to discuss this next one, however, there is absolutely
nothing in this church project that would ever have us get to an Institutional
Occupancy. First of all, Zion Lutheran Church is a church. As such, it is an
A -3 occupancy. The educational, or Sunday school rooms are clearly covered
under 305.1. Religious educational rooms, which are accessory to places of
worship in accordance with Section 508.3.1 and have occupant loads of less
than 100, shall be classified as A -3 occupancies. Those spaces are accessory
to the place of worship and are not, according to 508.3.1 exception 3, a
separate occupancy. Here is the bottom line. They are not going to sprinkle
the building, nor are they required to. They are not an Institutional
occupancy. Where did you get Mothers Morning Out anyway? It could only
have come from the cabinet elevations which were old and never got revised.
Those elevations have now been revised to reflect whats on the plans.
They may not make any changes to their existing programs that are currently
operating at the church. If, and only if, they did decide to use the rooms in the
future to expand that program, and if it is suggested that by having a part time
mothers morning out program, which is part of the ministry at Zion Lutheran
Church, is what makes the project Institutional, then they would not do it.
With that being said, the number of children in any of the rooms being
Member of the American Institute of Architects • National Council of Architectural Registration Boards Certified
O__ J
1 1
f
discussed will not exceed 49, which is the number shown in Table 1015.1. If
we had to use an E occupancy and therefore have to look at note a. in the same
table, the number of occupants in any of those rooms in question is not more y
than the 10 allowed.
4. An emergency roof drain will be provided as required. See revised sheet A5.
5. See revised sheet A6 showing revised counter heights.
6. There is no range; therefore, there is no hood.
PLUMBING and MECHANICAL REVIEW
f
7. Sewage lift pump will be vented per 2009 NCPC 916.5 and Table 916.5.1 if a
sewage lift pump is opted for.
8. A water hammer arrestor will be used at the icemaker if the refrigerator has
S
one, and/ or if they use metallic piping.
9. See revised Sheet M1 showing exhaust fan in Toilet Room #112.
10. See revised Sheet M2 showing exhaust fan in Toilet Room #112.
11. There will be no hood required. See revised sheet M2.
FIRE REVIEW
1. N/A f
2. A written response is being provided in the order they appear as well as
clouded revisions when appropriate.
3. Duly noted.
4. Duly noted.
5. A KNOX Box key box will be provided if one is required per NCFC 506.1.'
6. The building is existing and has the required premises identification.
7. The creation of nursery /classroom space does not require direct access to the
outside. Table 1015.1 allows a single exit from the space up to 49 persons. If
we are less than 100 occupants we are still an A -3 per 303.1 and 305.1 If we
are looked at as an E occupancy, we can have up to 10 occupants without a
second exit. We will never be an institutional occupancy and would not be
required to sprinkle this building. k
8. We may already have a fire alarm but it is not required based on being
Institution because that is not our occupancy.
9. The mechanical room is existing and if it does not already have a sign one will
be provided as required. t
10. There is to be no stove in the kitchen.
11. An additional emergency light will be provided in the corridor created in 4
Storage 119 if required.
Thank you,
4
ti
J. Stan Winstead, AIA
J
discussed will not exceed 49, which is the number shown in Table 1015.1. If
we had to use an E occupancy and therefore have to look at note a. in the same
table, the number of occupants in any of those rooms in question is not more
than the 10 allowed.
4. An emergency roof drain will be provided as required. See revised sheet A5.
5. See revised sheet A6 showing revised counter heights.
6. There is no range; therefore, there is no hood.
PLUMBING and MECHANICAL REVIEW
7. Sewage lift pump will be vented per 2009 NCPC 916.5 and Table 916.5.1 if a
sewage lift pump is opted for.
8. A water hammer arrestor will be used at the icemaker if the refrigerator has
one, and/ or if they use metallic piping.
9. See revised Sheet M 1 showing exhaust fan in Toilet Room # 112.
10. See revised Sheet M2 showing exhaust fan in Toilet Room # 112.
11. There will be no hood required. See revised sheet M2.
FIRE REVIEW
1. N/A
2. A written response is being provided in the order they appear as well as
clouded revisions when appropriate.
3. Duly noted.
4. Duly noted.
5. A KNOX Box key box will be provided if one is required per NCFC 506.1.
6. The building is existing and has the required premises identification.
7. The creation of nursery /classroom space does not require direct access to the
outside. Table 1015.1 allows a single exit from the space up to 49 persons. If
we are less than 100 occupants we are still an A -3 per 303.1 and 305.1 If we
are looked at as an E occupancy, we can have up to 10 occupants without a
second exit. We will never be an institutional occupancy and would not be
required to sprinkle this building.
8. We may already have a fire alarm but it is not required based on being
Institution because that is not our occupancy.
9. The mechanical room is existing and if it does not already have a sign one will
be provided as required.
10. There is to be no stove in the kitchen.
11. An additional emergency light will be provided in the corridor created in
Storage 119 if required.
Thank you,
J. Stan Winstead, AIA
4
3
5
GEORGE O. BROWN & ASSOCIATES, PLLC P.O. BOX 3423
CONSULTING ENGINEERS HICKORY, NC 28603
OFFICE (828) 324 -4002 f:
FAX (828) 324 -4012
}
January 18, 2011
Winstead Architecture, PLLC
P.O. Box 321
Newton, N.C. 28658 1
Attn: Stan Winstead, Architect
Subject: PERMIT #BLDC12 -10 -14096
ZION LUTHERAN CHURCH
1911 Zion Church Road f
3
Hickory, N.C. 28602
Dear Stan:
The following is in response to a plan review dated January 12, 2011, concerning plumbing and mechanical items only:
E
7. SHEET P2: Sewage lift pump has been shown to be vented in accordance with 2009 NCPC 916.5.1 and Table
916.5.1.
8. SHEET P3: General note has been added calling for water hammer arrestor at icemaker if metallic pipe is used
Per 2009 NCPC 604.9.7.
9. SHEET MI: Exhaust fan has been specified to serve Toilet Room #112 to provide minimum 150 cfm exhaust per
'4 2009 NCMC Table 403.3.
10. SHEET M2: Exhaust fan has been shown in Toilet Room #112 to provide minimum 150 cfin exhaust per 2009
NCMC Table 403.3.
11. SHEET M2: Kitchen exhaust hood/fan has been eliminated.
If you have any questions, or need further clarification, please let us know.
Sincerely,
t
i
GEORGE O. BROWN, P.E.
GOB /jb
i
e
F
Y
g
Y
E
4
S
GEORGE O. BROWN & ASSOCIATES, PLLC P.O. BOX 3423
CONSULTING ENGINEERS HICKORY, NC 28603
OFFICE (828) 324 -4002
FAX (828) 324 -4012
January 18, 2011
Winstead Architecture, PLLC
P.O. Box 321
Newton, N.C. 28658
Attn: Stan Winstead, Architect
Subject: PERMIT #BLDC12 -10 -14096
ZION LUTHERAN CHURCH
1911 Zion Church Road
Hickory, N.C. 28602
Dear Stan:
The following is in response to a plan review dated January 12, 2011, concerning plumbing and mechanical items only:
7. SHEET P2: Sewage lift pump has been shown to be vented in accordance with 2009 NCPC 916.5.1 and Table
916.5.1.
8. SHEET P3: General note has been added calling for water hammer arrestor at icemaker if metallic pipe is used
Per 2009 NCPC 604.9.7.
9. SHEET M1: Exhaust fan has been specified to serve Toilet Room #112 to provide minimum 150 cfin exhaust per
2009 NCMC Table 403.3.
10. SHEET M2: Exhaust fan has been shown in Toilet Room #112 to provide minimum 150 cfin exhaust per 2009
NCMC Table 403.3.
11. SHEET M2: Kitchen exhaust hood/fan has been eliminated.
If you have any questions, or need further clarification, please let us know.
Sincerely,
GEORGE O. BROWN, P.E.
GOB /jb