HomeMy WebLinkAboutCBPR-11-10-8084 Architect comments to 1st review.pdf Architects Architecture ■ Planning ■ Interior Design P O Box 1239 I Hickory, North Carolina 28603 I (828) 322-3403 December 6, 2010 Jeffrey N. Hinkle Code Official, Field Supervisor Catawba County Building Services Hickory Permit Center 76 North Center Street Hickory, NC 28601 RE: Catawba County Schools Addition to the Webb Murray Elementary School 3 1010 Dear Jeff, Thank you for your review and your staffs' review of this project on November 18, 2010. Enclosed with this response letter are 7 sets of the revised drawings, 7 copies of the addendums and a copy of the response letter to William Moeller at the NC Department of Insurance. This project was successfully bid on the 23rd of this month and contract may be awarded at the next school board meeting on December In response to the comments I have the following: Building Review 1) The current Catawba County Special Inspection Forms, partially filled in are attached to this response letter. The NCBC Edition is listed as 2009. Architect and Engineers of record have been indicated with the license numbers. The Earth retention box has been checked. Once the Contract has been awarded on Dec. 6th, the form will be completed and sent to you. 2) The percentage of increase for open area has been corrected on sheet BC1.0, see attached. 3) The assumed property line on sheet BC1.1 at the existing physical education classroom has been revised to be more than 10'-0" away fro the existing door. The existing wall of CMU and brick masonry has an equivalent rating greater than 1 hour. 4) UL numbers have been added to Wall Legend notes on sheet BC1.1, see attached revised sheet BC1.1. 5) The ASTM number of F-1488 has been added to the new sewer pipe under corridor 127, see attached revised sheet C3.1. 6) Rated walls have been shown on the revised sheet A1.0, see attached. 7) Slope of ramp has been shown on the floor plan sheet Al.l, see attached. 8) See attached response from Mike Ward P.E. CBSA Architects PAGE 2 9) See attached response from Mike Ward P.E. 10) See attached response from Mike Ward P.E. 11) See attached response from Mike Ward P.E. 12) See attached response from Mike Ward P.E. 13) See attached response from Mike Ward P.E. 14) See attached response from Mike Ward P.E. 15) See attached response from Mike Ward P.E. 16) Response similar to that for 15. 17) See attached response from Connor Bullard P.E. 18) See attached response from Connor Bullard P.E. 19) See attached response from Connor Bullard P.E. 20) See attached response from Connor Bullard P.E. 21) See attached response from Connor Bullard P.E. Environmental Review: There will not be any high gloss paint on ceilings and no repairs will be made in the existing toilet rooms or kitchen. In response to the comments from the Catawba County Fire Approval I have the following: 1) Appendix B has been revised to indicate "No Sprinklers" 2) Adequacy of all emergency and exit lighting to be evaluated in the field. 3) Fire extinguishers will be added to the mechanical rooms by the owner and will be surface mounted. 4) Fire hydrants were relocated by addendum #1 item no.l (drawings) and on attached addendum sheet Cl. Also see revised sheet C3.1. 5) Entrance road has been widened to 26' by addendum # 1 item no. 2 (drawings) and on attached addendum sheets C2. Also see revised sheet C3.1. 6) A KNOX Key Box is shown on the revised sheet C3.1. 7) The existing KNOX Box will be relocated to the new entrance by owner. 8) The new building is separated into two areas by a 2 hour wall. See revise appendix B that has the corrected areas of increase for open area. Also see sheet BC1.1 that corrects the assumed property line between the buildings. 9) Fire lane signs have been added, see attached sheet C3.1 and sheet C7.2. 10) Premises identification signs are shown on sheet C3.1. 11) A set of fire alarm shop drawings will be submitted to the permitting center when they become available. Landscaping: Two islands have been added, see sheet C3.1. Traffic/Transportation: The Board of Education is working with the NCDOT for the driveway permits. Negotiations are underway with the adjoining property owners for rights of way. Hickory Utilities Review: G:\2010.025\correspondence\ltJeffHinklell2910.doc CBSA Architects PAGE 3 Utilities have been revised per meeting with City of Hickory Utilities on Monday 11/22/2010. See attached Statement of Special Inspections by James Tate, PE. Please let me know if you have any questions or comments. Thank you for your continued assistance with this project. Sincerely, , ^/uiw W*"*"*^ J. Steven Walker, AIA CBSA Architects cc: Steve Demiter, Assistant Superintendent CCS Rick Sain, Construction Manager CCS Ernie Sills, AIA, LEED AP G:\2010.025\correspondence\IUeffHinklell2910.doc Mcknight • smith • ward • griffin ENGINEERS, INCORPORATED PO Box 240826 • 4223 South Boulevard • Charlotte. NC 2B224 704.527.2112 • FAX: 7O4.523.1315 • E-Mail: mswgemswg.com December 1,2010 Catawba County Plan Review 76 North Center Street Hickory, NC 28601 Attention: Mr. Steve Deitz REFERENCE: CATAWBA COUNTY SCHOOLS WEBB A. MURRAY -ADDITION PIN NO: 373317200984 CASE NO: CBPR-11-10-8084 Dear Mr. Deitz: In response to your review comments dated November 16, 2010 we offer the following: Comment No. Response 8-Isometric has been revised to eliminate the Floor Drain. 9-The referenced plan and schematic have been coordinated and revised. 10-The referenced venting arrangement has been revised to become compliant. 11 ■ The faucets in question are the metering type. 12 The referenced venting arrangement has been revised to become compliant. 13. The referenced Fire Damper has been added as requested. 14. The referenced Fire Damper has been added as requested. 15. Return air not required as air is exhausted and or necessary for building pressurization. See 2009 NCBC 1017.4 Exception 1 and 2009 NCMC 403.2.2. L. Michael Ward, PE. • James C. Griffin, RE. • J. Craig Champion, RE. Mark R Arrington, RE. • Michael W. Harper, RE. David G. Pearce, PE. • Donald H. Babcock. PE. Mr. David Deitz December 1,2010 Page 2 If you have any questions, please advise. Sincerely, Mcknight smith ward griffin engineers, incorporated L. Michael Ward, P.E. LMW/dc cc: Mr. Rick Sain Mr. Steve Walker BOLLARD ASSOCIATES E MFMO 1 Water Thaish Road E-mail: baengineers@aol.com To: Company: From: Project Name: Message: steve Walker, AIA CBSA ARCHITECTS Connor Bullard, PE WEBB A. MURRAY ELEMENTARY SCHOOL Date: 01 December 2010 ELECTRICAL 'TEMS contained in the 'etter of review from Catawba County 17. Sheet Ell: Conductor sizes feeding panels "LA" and "PB" have been adjusted to comply with the overcurrent protection for these panels. 18. Sheet E12: Loading on motor control center "MCC2" has been reduced by 3 horsepower The 15HP motor that was shown feeding from this motor control center is now being fed from the existing main service switchboard "MDS." See revisions to sheets El OP and El 1 for details on this change. 19. Sheet El 2: Total load on existing main switchboard after modification has been added -see sheet Ell. 20. Sheet E12: Breaker size for Panel "PB" has been added to Panel "MB." 21. Sheet E12: Panel "LB" was deleted from the plans, but the breaker feeding it was not removed from Panel MB. It now now has been removed and made a "space only." Let me know if you have any questions. Connor Bullard, PE Page 1 of 2