FROM 03 28 2064 17:06/ST.17:06 P002 WILLIAM ROBERT WAKEHAM ARCHITECT 107 LAKE CLIFF COURT ■ CARY, NORTH CAROLINA 27513 TELEPHONE 919 460-7220 December 6,2010 Via E-MaiI with Hard Copy
to Follow via USPS Jeffrey N. Hinkle, Plan Review Supervisor CATAWBA COUNTY BUILDING SERVICES 76 North Center Street Hickory NC 28601 RE: Grayson: Reference #CBPR-12-10-8486 Dear Mr.
Hinkle: Thank you for the thorough Express Plan Review conducted on 1*2/1/10. The following are our written responses to the Building Review comments: 1. ,^-Site Plan. Please refer to
attached responses from LandDesign. Revised Sheets C-3.2 and C-8.0 are included with plans package. 2. ^Slwct T2, Fire Protection Requirements Table deleted. Fire Resistive Information
revised to indicate non-combustible fire wall, U4.12. Requirement for standpipe deleted in General Building Data. 3. '^Sheet Al. Footing for fire wall added. 4. -'-'Sheet Ala. Ceiling
access panel Det 6/Ala revised to indicate 3/4 Hr rajed with closer and latch; insulated. 5. t^Sheet A5 & A10. Porch framing revised to HT as we discussed. Also revised Sheet A2 to indicate
HT porch framing. 6. v^Sheet A5. Note added to indicate accessible washers and dryers. 7. ^fy*®-A^' Revised to indicate solid wall between stair runs. 8. A^heet A8. Revised to include
labeled stair door numbers. Sheet A13 also revised accordingly. 9. Sh^et A9. Revised to indicate rated corridor on First Floor. ? 10. "^-Sheet All. Revised to indicated non-combustible
fire wall, U412. 11. '--Sheet All. Braced wall panel locations shown on Sheet A3. 12. tgfipet Al 1. Revised to indicate weeps at all locations noted. 13. ^Sheet Al 3. Revised to indicate
self-closing hinges must latch doors. 14-37. Please refer to attached response letter from HDM Associates, Inc. Four complete sets of revised plans will be delivered to you by Accent
Imaging. All revisions have been clouded and dated. Sincerely, William Robert Wakeham, Architect
FROM 03 28 2064 17:07/ST.17:06 P004 Horn ASSOCIATES, INC. Professional Engineering Services 135 Hanbury Road WesC Suite D Chesapeake, Virginia 23322 Phone: 7S7-410-0682 Fax:757-410-1537
E-mail; hdm@hdm.hrcoxmiiil.com MEMO Date: To: From: Project: December 6, 2010 Bob Wakoham Richard Thome Grayson Elderly Housing HDMNo.: 08116 RE: Hickory Fire Prevention Bureau Plan
Review Comments In response to the Hickory Fire Prevention Bureau's plan review comments, HOM Associates has made the following revisions: General Comments: 1. Sheet FP-1 was revised
adding Inspector's Note #1 concerning the site and grading plan reviews must be incorporated into this documents. 2. Sheet FP-1 was revised adding Inspector's Note #2 concerning maintenance
of the access road and the fire protection prior to beginning to construction, 3. Sheet FP-1 was revised adding Inspector's Note #3 concerning relocating the FDC to the island adjacent
to hydrant and protecting with a bollard. 4. The Architect is revising the documents to indicate indicate an approved fire wall, 5. The Architect will specify all signage. 6. The Architect
will specify the requirements to identify the fire walls. 7. There are currently no assembly spaces in Ihe facility. 8. There are currently no assembly spaces in the facility. 9. The
Architect and the Owner will provide building signs. 10. The Architect construction documents indicate the portable fire extinguisher locations. 11. Sheet FA-1 indicates the location
of the knox box at the front entrance. The owner will provide the required keys. 12. The location of the ARA master control panel is at the main entrance. See Sheet E-11. 13. Per the
statement made in the express review, the access control system does not require a permit because there are no magnetic locks. 14. The owner will be advised about the LP gas grille locations.
15. The owner will be advised about the charcoal grilles locations. 16. Sheet FP-1 was revised adding inspector's Note #4 concerning site safe guard requirements during construction.
17. Sheet FP-1 was revised adding Inspector's Note #5 concerning building occupancy permit requirements. 18. Sheet FP-1 was revised adding Inspector's Note #6 concerning fire department
use permit requirements. 19. Revised construction documents will be submitted for approval prior to construction beginning. 20. All modifications to the construction documents will be
"clouded" to clearly represent the revisions and a detailed written description will be attached explaining all the revisions. 1 or2 O:\200iftOU11iaMonvjs\uomQ. Hickory Rro wnvwllon
Bureau CommwtB 12-C-10.doc
FR0M 03 28 2064 17:07/ST.17:06 P005 Fire Alarm System 1. 2. 3. 4. 5. 6. Refer to 7. 8. 9. 12. 13. 14. in the Sheet has it sh<" own and recall not Fire Protection Comments: 1" IsindSS^^
" NPPA13R System in rcsidGntial ««« and NFPA 13 system in core area 2' .SnsD?ction'rlau?rLrfniS?h addj"9 '"^^'o^ Note #7 concerning flushing of sprinkler run-in of wkness InsSn if■ t^T
W9S reviSed addina lnsPector's N^e #8 concerning verification s »,«* /D '"spection prior to making connection to the sprinkler run-in. ^ concerning the sprinkler coverage shall be in
' ' ^t" m^i^ a-i^ff in i j—i m iu 11 i^^i li ji _^i ii i i r~^r ^" irLTinnn 4. Note #1°eonc8minB instai!ation accordin91° nfpa-^'^ lnspect0l's Note #11 «>n^rning sprinkler system connection
to fire N°t0 #12 C°nCGmin9 SPrinkler s^m ****** 7. Not applicable. There is not a Standpipe In the facility. 5, Sheet FP-1 was revised adding Inspector's Note #13 concerning 11. If you
have any questions, please contact our office. Thank you. Note #1S |rp-1 waf revlsed addin9 Inspector's Note #16 concerning the Installation of underground fC°rdanCe W"h PUW|C UtIliticS
D°P^ment requirements and NFPA sSnSard 24 9 asssrNote #17 concernin9 inspection
Fire Alarm System: 1 SfS W3,S ^l86!10 ?'°cate audible devices in the units t0 accommodate required audible levels at pillow level for the sleeping rooms. 2. Sheet FA-6 was revised to
remove audible/visual device for sprinkler flow from plan 3. Sheet FA-6 was revised to show horn/strobe added to maintenance room i' ftee! £Ai WaS revised t0 show additional tar"per
and flow switches for sprinkler monitorinq 5. Sheet FA-6 was revised to show smoke detector in elevator pit 6. Refer to mechanical sheet M-7. Sheet has been revised to'show diffuser
moved into sprinkler room FA"l7S revi8ed.!° '"elude note statin3 ■Installation of the lire alarm system and device %S&£>£* 72 (2002 edSion)'SeMion 907 of the NC Bulldin9 Code and room.
78-tsxts, o^s^ss;^ se sassr-^wlth nfpa ' 9. Sheet FA-1: Requirement for fire alarm contractor to submit shop drawings to engineer is outlined in Mre Alarm Specification. 10. Sheet FA-1
was revised to include note stating Tire alarm contractor shall obtain a permit from the Fire Prevention Bureau prior to any installation of the fire alarm system " \\ IJee! SI "T? reV'Sed
t0 Sh0W smoke and heat detectors for elevator shutdown and recall nfS 7? Sn9 height requirements for wall mounted fire alarm devices are shown in the NFPA 72 and ADA Device Installation
Requirements detail. 13. Sheet FA-1: Mounting height requirements for manual fire alarm boxes are shown in the NFPA 72 and ADA Device Installation Requirements detail. 14. Sheet FA-1
revised to include note stating "Smoke detector shall not be located closer than 3 feet from any air supply diffuser or return air opening per NFPA 72." Fire Protection Comments: 1.
The sprinkler system is a NFPA 13R system in residential areas and NFPA 13 system in core area as indicated on the construction documents. If this changes the Hickory Fire Prevention
Bureau will D6 not ITISO. 2. Sheet FP-1 was revised adding Inspector's Note #7 concerning flushing of sprinkler run-in inspection requirement. Sheet FP-1 was revised adding Inspector's
Note #8 concerning verification of witness inspection prior to making connection to the sprinkler run-in 3 ss^s^^rsssss'^i"concernin9 the was revised j Code and NC 5. Sheet FP-1 was
revised adding Inspector's Note #11 concerning sprinkler system connection to fire siaiin systsm. 6. Sheet FP-1 was revised adding Inspector's Note #12 concerning sprinkler system supervision
7. Not applicable. There is not a Standpipe in the facility. q' Qh66! SIWaS reV'Sed adding lnsPectorls Note #13 concerning FDC signage requirements y. bheet FP-1 was revised adding Inspector's
Note #14 concerning sprinkler room and equipment signage requirements. «M"'H"«s"i 1°" requirements "** ^^ ^^ lnSpeCt0'S Note #15 concemin9 sprinkler system permit 11 St!*et FP"1 waf
^ised adding Inspector's Note #16 concerning the installation of underground £?« accordance Wltn Public util|ties Department requirements and NFPA Standard 24 TS ^SXKaSS? Nt #1? i If
you have any questions, please contact our office. Thank you. O:\2008\08116\Memos\Memo-Hickory Fire Prevention Bureau Comments 12-6-IO.do?6
FROM 03 28 2064 17:07/ST. 17:06 P006 II Dill 135 Hanbury Road West, Suite D Chesapeake, Virginia 23322 Phone: 757-4! 0-0682 Fax:757-410-1537 MEMO Date: To; From: Project: Decembers,
2010 Bob Wakeham Richard Thome Grayson Elderly Mousing HDM No.: 08116 RE: County of Catawba Plan Review Comments In response to the County of Catawba's plan review comments, HDM Associates
has made the following revisions: Building Review Comments: 1-13,To be answered by others. -fck'Sheet P-1 specification #24 was revised to state: "Water piping shall be cross-linked
polyethylene/aluminum/cross-linked polyethylene or cro$s-linked polyethylene/aluminum/highdennsit polyethylene. ASTM F1281 OR ASTM F1986. All shall be installed with approved fittings."
■K5rSheet P-1 specification #24 was revised to state: "Water piping shall be cross-linked polyethylene/aluminum/cross-linked polyethylene or cross-linked polyethylene/aluminum/highdennsit
polyethylene. ASTM F1281 OR ASTM F1986. All shall be installed with approved fittings." 1<6TSheet P-9 was not revised. Sheet P-15 was revised by adding fire penetration details F-C 2029
and moved fire detail from sheet P-16 to P-15. 17<Sheet P-9 was not revised. Sheet P-16 was revised by adding a sink piping detail to the fire oe'netration detail WL1001. TSTSheet P-13
was revised by adding a square around the water heater (WH-2) to indicate a pan, note #10 was revised to state: "Provide electric water heater (WH-2), located in pan on floor. See water
beater detail." i9TjKeet P-15 already indicates how the water heater pan drains will terminate to the waste piping. 29/Sheet P-14 was revised by taking away the extra riser diagrams
that were already indicated on the sdine sheet. Sheet P-15 was revised by moving unit H risers to sheet P-14. 2<l/Sheet P-12 was revised by adding trap primers for the floor drains on
each floor and two notes were added telling the contractor to provide trap primers for the floor drains. 22/Sheet P-1 currently has a water heater schedule stating the capacity of the
water heaters. Sheet Pr13 was revised by adding the water heater capacities to the title of the detail. 23."5heet P-1 water heater schedule has been revised by stating the water heater
has integral heat traps. P-13 water heater detail was revised stating integral heat traps. 24.^6 secondary drain requirement is indicated on the Vertical Air Handling Unit Detail on
sheet M-8. Tbro secondary drains were replaced with overflow switches. 25.'«fieet M-5, M-6, M-7, and M-8 were revised indicating the use of dryer vent boxes in the wall and a maximum
length of dryer vont is 45 feet 26. Sfteet M-8 was revised to indicate smoke detectors in air handling units AHU-1 thru AHU-6. Page 1 of2 O:\2O08\D8118\MOtno5\Mom«p. Courtly d CaiSnOJ
Commons 12^.1 U-(J«
FR0M 03 28 2064 17:07/ST.17:06 P007 27/sheet M-7 indicates a transfer grille between the laundry room and adjacent space Sheet M-S and M-6 were rev.sed indicating transfer grilles between
the laundry rooms and adjacent corndor is not a ft z s^rsi9n at the K'Vto^n^ Det3" WaS reviSSd indicating a *** vent box t0 bc installed in wall. J ^ . ^ c Ot n■ e"ier9,ency •9'»» fixture.
The "S" fixture is the emergency egress fixture and the Light Fixture Schedule indicated there are 2 lamps 9 taS2*E1ihE1i«S ** W6re riVi3®d t0 Sh0W illuminated Af^ signage at the area
of rf S2Sschedule WaS reVl to C'Ude th° "^ °f refU9e illuminat'd ^™S* in the nnT T9 TJTHFJ0 **™ 0) aMitional receptacle in the living area of units A, B and O. A j£5{!$) "9 reqU'nri9
°Utlet$ t0 ^ SPaC6d aCCOrdin9 t0 NEC Article 2 334<<Sheet E-9 was revised to show smoke detectors in the living areas per Section 907.2.10.1.2 of S£|heet E-10 was revised to provide
exit signage in second and third floor of core areas. Sfw2.D "f? '°ad calculations werc ch0<*cd and arc in compliance with Article 220 of the 2008 NEC Panel board schedules and load
summaries are provided for all panels. Vf. Sheet E-1 indicates the bussing In the motor center. If you have any questions, please contact our office. Thank you. O:\20Wn0H 11
M-7 indicates a transfer grille between the laundry room and adjacent space. Sheet M-5 and were revised ind.cating transfer grilles between the laundry rooms and the adjacent hall vg*
The wall between the storage and the adjacent corridor is not a full height. Therefore the return air is freely communicated between the spaces. JLh<;et M"8' °7!,r Ve?l H°Okup Detail
was revised indicating a sign at the dryer vent stating the is concealed and has a developed length of 40 feet ™Dfyer Ve/iHookuP Detail was revised indicating a dryer vent box to be
installed in wall »^ fixture is not the emergency egress fixture. The "S" fixture is the emergency egress fixture the Light Fixture Schedule indicated there are 2 lamps . Sheets E-2
E-3 & E-4 were revised to show illuminated ARA signage at the area of refuge locations. Sheet E1 was revised to include the area of refuge illuminated signage in the lighting I/33. Sheet
E-9 was revised to show (1) additional receptacle in the living area of units A B and D A n^W!f added t0 t0 the drawing requirir|g out'ets to be spaced according to NEC Article 210 52
(AD feviSed t0 Sh0W smoke detectors in tne living areas per Section 907.2.10.1.2 of Sheet E-10 was revised to provide exit signage in second and third floor of core areas ,leo111 n !*?
l0ad calculations were checked and are in compliance with Article 220 of the ^008 NEC. Panel board schedules and load summaries are provided for all panels Sheet E-1 indicates the bussing
in the meter center. If you have any questions, please contact our office. Thank you. O:\2008\08116\Memos\Memo-County of Catawba Comments 12-6-10.doc ^ °
HDffl 135 Hanbury Road West, Suite D Chesapeake, Virginia 23322 Phone:757-410-0682 ASSOCIATES, INC. . , h/4 ^ Fax 757-410-1537 Professional Engineering Services mail: hdNShdm.hrcaxmail.com
MEMO Date: To: From: Project: December 6, 2010 Bob Wakeham Richard Thome Grayson Elderly Housing HDM No.: 08116 RE: County of Catawba Plan Review Comments revjsjons. ' of Catawba's plan
review comments, HDM Associates has made the following Building Review Comments: 1-13.To be answered by others. nniSh P~1 ?PeciTlcat]°n *24 was revised to state: "Water piping shall
be cross-linked polyehylene/aluminum/cross-hnked polyethylene or cross-linked polyethylene/aluminum/highdennsit po yethylene. ASTM F1281 OR ASTM F1986. All shall be installed with approved
fittings " ™i »,i ,spec!ficatl0n *** was revised to state: "Water piping shall be cross-linked polyethylene/aluminum/cross-linked polyethylene or cross-linked polyethylene/aluminum hiahdennsit
polyethylene. ASTM F1281 OR ASTM F1986 All shall b-i-JL,? IZ"!:!! ™ iTl.9,, p^ detail t0 the 18. Sheet P-13 was revised by adding a square around the water heater (WH-2) to indicate
a pan note T'S t0 ^ "^^ ^^^ he3t (WH2) '*d in pan on £?£ In lUf! d'Ia a'ready ind^teS h°W the Water heater pan drains wi" terminate to the waste piping famp fhit Th Tp « by takin9 3^ay
the eXtra riser dia9rams that were already indicated on the same sheet Sheet P-15 was revised by moving unit H risers t ht P14 famp fhit Th Tp « y n9 3^ay the eXtra riser dia9rams that
were sheet. to sheet P-14 IfJll WS re)?Sed b/3dding trap i f th fl d y moving unit H risers to sheet P-14 If-Jlnl tWnS ret)?Sed b/3dding trap primers for the floor drains on each floor
and two notes were added telling the contractor to provide trap primers for the floor drains I JfvL1 St h3L3 Wler h6ater SChedU'e Stating the capacity of the water Waters. Sheet P-13
was revised by adding the water heater capacities to the title of the detail traDSetPP"i13 w^rh^f H°hedUle h3Sbe!n r6ViSed by Stating the water heater has integral heat traps. P-13 water
water heater detail was revised stating integral heat traps 24. The secondary drain requirement is indicated on the Vertical Air Handling Unit Detail on sheet M-8 /The secondary drains
were replaced with overflow switches ~SL51 ^f'^ idi v-26. Sheet M-8 was revised to indicate smoke detectors in air handling units AHU-1 thru AHU-6. O:\2008V08116\Memos\Memo-County of
Catawba Comments 12-6-10.doc ^ °
ii pm ASSOCIATES, INC. Professional Engineering Services 135 Hanbury Road West, Suite D Chesapeake, Virginia 23322 Phone:757-410-0682 Fax:757-410-1537 E-mail: hdm@hdm.hrcoxmail.com MEMO
Date: To: From: Project: HDM No.: RE: December 6, 2010 Bob Wakeham Richard Thome Grayson Elderly Housing 08116 Hickory Fire Prevention Bureau Plan Review Comments ^ Prevention Bureau's
Plan review comments, HDM Associates has made the General Comments: Note #1 concerning the site inusi ue ingurporaxea into mis documents 2. 3. Sheet FP-1 was revised adding Inspector's
Note #3 concerning relocating the FDC to the island adjacent to hydrant and protecting with a bollard. 4. The Architect is revising the documents to indicate an approved fire wall 5.
The Architect will specify all signage. 6. The Architect will specify the requirements to identify the fire walls. 7. There are currently no assembly spaces in the facility. 8. There
are currently no assembly spaces in the facility. 9. The Architect and the Owner will provide building signs. ]?' Vle /^it?ct construction documents indicate the portable fire extinguisher
locations n. Sheet FA-1 indicates the location of the knox box at the front entrance. The owner will provide the r6C|uir&Ci Ksys. 12. The location of the ARA master control panel is
at the main entrance. See Sheet E-11 13. Per the statement made in the pvnr«« rew^.., «„, access contro| system does not requjre a 14. The owner will be advised about the LP gas grille
locations 15. The owner will be advised about the charcoal grilles locations 1* Sh1FP1W7id "^ ' 1?' "**"* Safe guard lnspector's Note #5 concerning building occupancy permit 18" feq^rements*88
lnspector's Note m concerning fire department use permit 20 A?^ifi^^i0!lhd0CUmf^ Wi" be submitted for aPProval Prior to construction beginning. aiJZS f T u I construct|on documents will
be "clouded" to clearly represent the revisions and a detailed written description will be attached explaining all the revisions O:\2008\08116\Memos\Memo-Hickory Fire Prevention Bureau
Comments 12-6-IO.d^6 ^ °f 2
Case #: Comments: CBPR-12-10-8486 10. Sheet CATAWBA COUNTY REfI^c1VSNP2T,E0S8486 Status: DISAPPROVED 2009NCP^bil7cJ**" "* "M-7-d 7,5.4.7.1 ofthe NCBC using 4. spring *""°'«""■*"ith**°°«»rMb605.4of,he
wal. 18. Sheet P-13: Provide a safety pan and pan drain for WH-2 ll per section 504.7, 2009 NCPC Shell P MITT8 T ^u™ ^^^ {m M . Meet P-14. Labeling for unit H appears to mislabeled ^heater
p Tf^T ^ P SeCti°n 10024' 20°9 NCPC. -l and P-13: Specify water heater capacity. 24' S2 ^J3pPr0VJde h6at ^P8 PCr SCCti0n 504A ofthe 2m NC Energy Conservation Code 25' Shee M5 No/t "^
r^11^ ^^ per SCCtion 307.2.3^fthe NCMC S Per SCCtion 5046-»of *« H1 On^ be all™ed if approved by the "«» and kitchen Per -tion 210.52A1 and A2 of 335~ ShS F1 36 sLe p paces Per section
907-2-10.1.2 of the NCBC COre "^ Per section 1011 of the NCBC 37 Shee E 3 PrTn f"10" for each se^ 1» Article 220 of the 2008 NEC 37. Sheet E13. Provide a panel diagram for the two i
i i main service panels. Created from Permit BLDC-12-10-13373. END REPORT pin -plan plan review notes Notice: 12/08/2010 09:54 Page 2 of2 as one package. Each