HomeMy WebLinkAboutCBPR--09-10-7494 Architect's First Review Comments.tif WINSTEAD 0 ARCHITECTURE, PLLC 22 North Main Avenue P.O. Box 321 E -mail: winarch@ bellsouth.net Newton, North Carolina 28658 Telephone: (828) 464 -2827 Fax: (828) 464 -3229 October 18, 2010 Catawba County Permit Center P.O. P)ox 389 Newton, X 28658 r Re: P)andy's Crossroads Volunteer Fire Dept. #3 4849Y /1C 16 HWY Maiden, North Carolina 28609 #E)LDC -9 -10 -11319 Thank you for reviewing our project. We have tried to address each of your comments or concerns and have revised drawings as required. Catawba County Fire - FIRE -9 -10 -7497 f 1. Emergency and exit lighting to be verified in field. 2. Complete sprinkler plans will be provided prior to beginning installation. 3. Complete fire alarm plans will be provided prior to beginning installation. 4. _fee sprinkler drawings for details. r- 5. Rove is to be a residential model. 6. Mood and duct detection shall be interconnected with the building's fire alarm system. 7. Tactile exit signage to be in accordance with 1011.3 8. MOX box will be provided per /YCFC 506.1. 9. P)uilding will have proper address numbers in accordance with /YCFC 505.1 S Zoning ZO/1 -9 -10 -7496 1. ree 5heet,/'P -2 showing driveway landscaping to meet- ection 44- 523(c). 2. fee 5heetfP -2 showing parking island to meetfection 44- 523(e). 3. fee 5heet,/P -2 showing parcel perimeter buffer to meetfection 44- 525(f). 4. /1CDOT driveway permit will be provided perfection 44- 515(8). t Pbuilding C15PR -9 -10 -7494 1. fee sheet T -1 showing corrected exit number. 2. On sheet T -1 the U -value of 0.077 with perimeter insulation equal the R -13 Value. R = 1 /U. 3. -fee 5heetfP -2 identifying the location of the accessible parking space, aisle and route. 4. fee sheet A -1 showing proper width of floor space in front of accessible transfer type shower l s per section 608.2.1 of A117. 5. fee sheet A -2 indicating location of required safety glass. 6. fee sheet A -6 coordinating joint reinforcing with structural sheet. 7. fee sheet A -6 showing corrected corbelled masonry per section 2104.2 of the /YCP)C. 8. fee sheet A -6 showing thru -wall flashing and weeps as per 1405.3.2 of the /tC13C. Member of the American Institute of Architects • National Council of Architectural Registration Boards Certified I r 9. Jee sheet A -7 showing thru -wall flashing and weeps at structural locations as per section 1405.3.2 of the / ICE5C. 10. Jee sheet A -9 showing corrected exit width of accessible transfer type shower as per section 608.2.1 of A117. 11. Jee sheet A -9 showing minimum knee space to be 27 inches as per section 306.3.1 of A117. 12. Jee sheet A -9 showing details of accessible shower. 13. Jee sheet A -10 showing the maximum height of cabinets to be 34" per section 902.3 of A117. 14. Jee sheet A -12 indentyfing equipment, vents and plumbing vents. 15. Jee sheet P -2 trap primers were eliminated and hose bibs provided in floor drain locations. F 16. Jee sheet P -5 showing location and size of gutter downspouts. i 17. Jee sheet P -5 Note has been added to refer to General Contract Drawings for locations of primary roof drain termination point. Jecondary roof drains terminate at outside wall- ` mounted downspout nozzle 18. Jee sheet M -1 range is residential type. Therefore, a residential range hood and exhaust fan were provided. 19. Jee sheet M -2 Manufacturer's venting instructions are included with this letter. j 20. Jee sheet E -2 showing short circuit calculations for the service panels. 21. Jee sheet E -3 showing outdoor emergency illumination at all marked exits. I Thank you for your time reviewing our project. Please call if you have any further questions or concerns. f ncerely, • � n v J. n Winstead, AIA .0 �O CAR���`r i i t