October 18, 2010
t
{
Catawba County Permit Center
P.O. box 589
/fewton, /YC 28658
Re: Dandy's Crossroads Volunteer Fire Dept. #5
4849,/ /YC 16 HWY
Maiden, /Yorth Carolina 28609
#15LDC -9 -10 -11519
Thank you for reviewing our project. We have tried to address each of your comments
or concerns and have revised drawings as required.
Catawba County Fire - FIRE -9 -10 -7497
1. Emergency and exit lighting to be verified in field. `
2. Complete sprinkler plans will be provided prior to beginning installation.
5. Complete fire alarm plans will be provided prior to beginning installation. 5
4. Yee sprinkler drawings for details.
i
5. Ytove is to be a residential model.
6. Hood and duct detection shall be interconnected with the building's fire alarm system.
7. Tactile exit signage to be in accordance with 1011.5
8. K/1OX box will be provided per /1CFC 506.1.
9. building will have proper address numbers in accordance with /YCFC 505.1
Zoning ZON -9 -10 -7496 5
1. Yee 5heetYP -2 showing driveway landscaping to meet- fection 44- 525(c).
2. -fee 5heetYP -2 showing parking island to meet_fection 44- 523(e).
3. Yee 5heetYP -2 showing parcel perimeter buffer to meet_fection 44- 525(f).
4. /ICDOT driveway permit will be provided perfection 44- 515(8).
Nildina CDPR -9 -10 -7494
1. Yee sheet T -1 showing corrected exit number.
2. On sheet T -1 the U -value of 0.077 with perimeter insulation equal the R -15 Value. R = 1 /U.
5. Yee 5heetYP -2 identifying the location of the accessible parking space, aisle and route.
4. Yee sheet A -1 showing proper width of floor space in front of accessible transfer type
shower as per section 608.2.1 of A117. k
5. Yee sheet A -2 indicating location of required safety glass.
6. Yee sheet A -6 coordinating joint reinforcing with structural sheet.
7. Yee sheet A -6 showing corrected corbelled masonry per section 2104.2 of the /ICDC. g
8. Yee sheet A -6 showing thru -wall flashing and weeps as per 1405.5.2 of the NCDC.
d
Member of the American Institute of Architects • National Council of Architectural Registration Boards Certified
s
r
9. fee sheet A -7 showing thru -wall flashing and weeps at structural locations as per section
1405.3.2 of the ACK,
10. Jee sheet A -9 showing corrected exit width of accessible transfer type shower as per
section 608.2.1 of A117.
11. Jee sheet A -9 showing minimum knee space to be 27 inches as per section 306.3.1 of
A117.
12. Jee sheet A -9 showing details of accessible shower.
i 13. Jee sheet A -10 showing the maximum height of cabinets to be 34" per section 902.3 of
Al 17.
k 14. fee sheet A -12 indentyfing equipment, vents and plumbing vents.
15. fee sheet P -2 trap primers were eliminated and hose bibs provided in floor drain
s locations.
16. Jee sheet P -5 showing location and size of gutter downspouts.
17. fee sheet P -5 note has been added to refer to General Contract Drawings for locations
of primary roof drain termination point. Jecondary roof drains terminate at outside wall -
mounted downspout nozzle
18. Jee sheet M -1 range is residential type. Therefore, a residential range hood and exhaust
fan were provided.
19. Jee sheet M -2 Manufacturer's venting instructions are included with this letter.
20. fee sheet E -2 showing short circuit calculations for the service panels.
21. fee sheet E -3 showing outdoor emergency illumination at all marked exits.
i
Thank you for your time reviewing our project. Please call if you have any further questions or
concerns.
4
incerely,
" 'Y Witis
J. n Winstead, AIA 6$