HomeMy WebLinkAboutCBPR-5-10-5509 Plan Review Comments 07-29-10.tif I
MACKIE JOHNSON, ARCHITECT
OFFICE: 828 -464 -1028 FAx: 828 - 465 -4562
MAILING ADDRESS SHIPPING ADDRESS
P.O. Box 428 114 TH AVENUES W
_ CONOVER, N. C. 28613 ONOVER, N. C. 28613
MJA p@MACKIEJOHNSON.COM
JULY 29, 2010 661 A 5 " SS l
PROJECT CONSTRUCTION MEMO PLAN REVIEW COMMENTS
NUMBER (RESPONSE TO CODE COMMENTS DATED 06- 29 -10)
DELIVERY: HAND DELIVERY - ONLY
PROJECT: PALLIATIVE CARE CENTER & HOSPICE OF THE CATAWBA VALLEY
3975 ROBINSON ROAD
NEWTON, NORTH CAROLINA 28658
CONTRACTOR: N/A
FROM: BARRY (CARD, AIA - MACKIE JOHNSON, ARCHITECT
TO: CATAWBA COUNTY— CLARA COULBOURNE
HICKORY DEVELOPMENT ASSISTANT CENTER
COPY TO: CLARK ISAAC -ISAAC CONSTRUCTION
DAVE CLARK- HOSPICE OF THE CATAWBA VALLEY
REFERENCE: REPLY TO REVIEW COMMENTS DATED 06 -29 -10
BUILDING STATUS: (COMPLETE - DISAPPROVED)
Comment # 1:
A written response to the comments in the order they appear in this correspondence as
well as appropriate clouded revisions to the plans shall be provided.
(We shall comply)
Comment # 2:
This review does not constitute a check of all technical code items and does not prevent
the code official from requiring further additions and /or corrections.
(We shall comply)
Comment # 3:
This review does not relieve the design professional of full responsibility for compliance
with all the provisions of the technical codes and other pertinent laws or ordinances.
(We shall comply)
PAGE 1 OF 6
t
;' Y
Comment # 4:
i All utilization equipment either Gas or Electric is required to be Listed and /or Labeled by
a Nationally Recognized Testing Laboratory approved by the North Carolina Department
of Insurance.
(We shall comply)
Comment # 5:
No person shall be permitted to occupy this building or any portion thereof prior to
! approval by the Building Official.
± (We shall comply)
Comment # 6:
All interior finishes shall comply with Table 803.5 of the North Carolina Building Code.
(We shall comply)
Comment # 7:
Adequacy of egress illumination and exit signage shall be verified in the field.
(We shall comply)
Comment # 8:
The integrity of all fire- blocking and draft - stopping shall be maintained using approved
materials and methods per section 717 of the North Carolina Building Code.
(We shall comply)
Comment # 9:
The surface of all toilet room walls and floors shall comply with section 1210 of the North
Carolina Building Code. (We shall comply)
Comment # 10:
All indirect waste piping that exceeds 2 feet (610 mm) in developed length measured
horizontally, or 4 feet (1219 mm) in total developed length, shall be trapped per Section
802.2 of the 2009 NC Plumbing Code. (We shall comply)
Comment # 11:
Sheet CS1: Under Allowable Area — Square footage shown under "Area for sprinkler
increase" is incorrect. Correct.
(See revised drawing CS -1)
Comment # 12:
Sheet CS2: UL Design No. U419 is for metal studs. Provide a design for wooden studs.
(See U.L. Design 0309 on drawing CS -2)
Comment # 13:
Sheet CS3: All "fire barrier" walls and `'smoke barrier" walls shall be continuous from the
slab to the underside of the roof deck above per 2009 NCBC 706.5 and 709.4.
(See revised drawing CS -3 showing wall type "3" continuous to underside of plywood
deck)
Comment # 14:
Sheet Cl: Provide a "passenger loading zone" per 2009 NCBC 1106.7.2 and ICC /ANSI
A117.1 -2003 Section 503
(RESPONSE: DRAWING C1 HAS BEEN REVISED TO SHOW `PASSENGER LOADING ZONE"
ON THE PLANS. THIS AREA IS AT THE COVERED ENTRANCE AT THE REAR OF THE
BUILDING.)
Comment # 15:
Sheet Cl: Handicap parking spaces are to be the closest spaces to the entrances per
2009 NCBC 1106.6. Revise the two located on the East end of the front row parking.
(RESPONSE: DRAWING C1 HAS BEEN REVISED TO SHOW ALL ACCESSIBLE PARKING
SPACES AT THE FRONT)
PAGE 2 OF 6
ti
I
y Comment # 16:
Sheet Cl: Provide the purpose of the fenced area on the South side of the building near
the sunroom.
(RESPONSE: DRAWING C1 HAS BEEN REVISED TO SHOW THAT THE AREA OUTSIDE THE
SUNROOM AT THE REAR OF THE BUILDING IS AN ACCESSIBLE, OPEN PATIO WITH NO
GATES OR RESTRICTIONS TO EGRESS FROM THE BUILDING.)
Comment # 17:
r Sheet A1.0: Provide a layout and details of the fenced area outside the sun room.
(RESPONSE: REFERENCE NOTE: 16 RESPONSE.)
Comment # 18:
Sheet A1.0: All "fire barrier" and "smoke barrier" wall shall be continuous from the slab to
the underside of the roof deck per 2009 NCBC 706.5 and 709.4.
(See revised drawing A1.0 showing wall type "3" continuous to underside of plywood
deck)
Comment # 19:
Sheet A1.0: Soiled utility room walls to be 1 hour rated per 2009 NCBC Table 508.2.
(See revised drawing A1.0)
Comment # 20:
Sheet A2.0: Provide door number for door to exterior near soiled utility room.
(See revised drawing A2.0)
Comment # 21:
Sheet A2.0: Fire barrier and smoke barrier walls to be continuous from the slab to the
underside of the roof deck per 2009 NCBC 706.5. and 709.4.
(See revised drawing A1.0 showing wall type "3" continuous to underside of plywood
deck)
Comment # 22:
Sheet A2.0: Fire barrier, smoke barrier and smoke partition walls to be permanently
identified per 2009 NCBC 703.5. Provide detail for identification.
(See revised drawing CS3, A1.0, and A2.Oshowing note that all Fire barrier, smoke
barrier and smoke partition walls to be identified above ceiling)
Comment # 23:
Sheet A2.0: Doors # 108A and 107B to be 45 minute rated doors per 2009 NCBC Table
715.4.
(See revised drawing A2.0)
Comment # 24:
Sheet A2.1: Provide detail of recessed can light in rated ceilings. Specify materials to be
used to maintain rating.
(See electrical drawings)
Comment # 25:
Sheet A2.4: Provide details for kitchen hood installation. Provide section thru hood
continuous thru the roof with dimensions showing how the required 18 inch clearance
will be maintained thru the wood trusses and wood studs.
(All Kitchen Hood ductwork to have "0" clearance wrap or approved equal. See detail
6/A6.0 for schematic kitchen hood installation. A final set of manufacturer installation
shop drawings will be provided before kitchen hood is installed.)
Comment # 26:
Sheet A4.0: Verify that attic access doors are large enough to allow removal of
equipment per 2009 NCMC 306.3.
(We have verified that attic access doors comply)
PAGE 3 OF 6
L
t
Comment # 27:
Sheet A4.0: Provide section thru access flooring showing space for R30 insulation and
required head clearance per 2009 NCMC 306.3.
_ (See detail 7/A6.1 showing required clearance)
i Comment # 28:
Sheet A5.0: Typical roof construction note states 1 /2 inch OSB while the section drawings
state 5/8 inch CDX. Coordinate and revise as necessary.
(See revised drawing A5.0)
Comment # 29:
Sheet A6.1: UL Design 0309 requires gypsum board on both sides of studs. Clarify how
you will accomplish this and revise all details to show gypsum board on both sides.
(See revised drawing A6.1. Per conversation with Steve Deitz, we will use U.L. design
U419 as shown on Drawing A2.1 on required rated ceiling and will attach temporary
attach gypsum board on bottom chord of trusses then add metal studs then attach
f
gypsum board as required thru opening in bottom chord trusses)
Comment # 30:
Sheet A7.1: UL Design P538 is not approved for steel beams. Provide approved design.
(See revised drawing A71. Using calculated fire resistant construction as indicated in
Table 720.1(1))
Comment # 31:
Sheet A7.2: UL Design P538 requires gypsum board to go to the end of the truss (freeze
board).Provide details showing it extending to end of truss and clarify how you will
provide ventilation. Typical all sections.
(Per conversation with Steve Deitz, U.L. Design does not indicate gypsum board going
3
to Freeze Board)
Comment # 32:
Sheet A7.3: Section # 1 has notes about block wall ties that are pointing at a stud wall.
Remove as required.
(See revised drawing A7.3)
Comment # 33:
Sheet A7A Provide a UL Design for protection of the steel beam as it is required to be
protected per 2009 NCBC Table 601. Typical all sections showing steel beams.
(See revised drawing A7.4. Using calculated fire resistant construction as indicated in
Table 720.1(1))
Comment # 34:
Sheet S1: Clearly indicate all shear walls. General note # 4 under structural notes
mentions external and interior shear panels. Only one (1) shear wall is labeled (kitchen
area).
(RESPONSE: DRAWING S1, S2 AND S3 HAVE BEEN CHANGED TO CLEARLY INDICATE
WHICH WALLS ARE SHEAR WALLS AND HOW THEY ARE CONNECTED TO THE OTHER
STRUCTURAL ELEMENTS.)
Comment # 35:
Sheet S2: Provide UL Design for protection of steel beam per 2009 NCBC Table 601.
(RESPONSE: A NOTE HAS BEEN ADDED TO DRAWING S1 THAT DIRECTS READER TO
ARCHITECTURAL DRAWINGS FOR FIRE PROTECTION DETAILS.)
Comment # 36:
Sheet S3: Provide R 38 insulation over top of 3'/2 inch bait insulation.
i
(RESPONSE: DETAIL 4/S3 HAS BEEN MODIFIED TO SHOW R38 OVER WATER PIPING.)
PAGE 4OF6
I
i
s
i
f
Comment # 37:
Sheet S4: All roof construction required to be protected by 1 hour construction per 2009
NCBC Table 601.
(RESPONSE: NOTES HAVE BEEN MODIFIED ON SHEET S2 TO INDICATE THAT ROOF
ASSEMBLIES AND EXPOSED STRUCTURAL ELEMENTS ARE REQUIRED TO HAVE 1 HOUR
�► FIRE PROTECTION RATING AND TO REFERENCE THE ARCHITECTURAL DRAWING FOR FIRE
PROTECTION DETAILS.)
Comment # 38:
Sheet P2: Provide trap primer at the floor drain in the kitchen or provide a hose bibb per
2009 NCPC 412.6.
(See attach response from Brittain Engineering)
Comment # 39:
Sheet P2: Water service pipe to connect to public water supply line per 2009 NCPC
602.3.
(See attach response from Brittain Engineering)
Comment # 40:
Sheet P3: Generator to have dual fuel sources per 2008 NEC 700.12(B)(3).
(See attach response from Brittain Engineering)
Comment # 41:
Sheet M1: There is a return grille in the med room that appears to not be connected to
anything. Clarify.
j (See attach response from Brittain Engineering)
Comment # 42:
Sheet M1: Provide fire dampers in duct penetrating walls / ceilings of the soiled utility
room, clean utility room, soiled linen storage area per 2009 NCMC 607.5.2.
(See attach response from Brittain Engineering)
Comment # 43:
Sheet M1: Locate hood remote manual activation device per 2009 NCBC 904.11.1.
(See attach response from Brittain Engineering)
E Comment # 44:
Sheet M1: Verify fuel / electrical shutoff are interconnected with the hood fire
suppression system per 2009 NCBC 904.11.2.
(See attach response from Brittain Engineering)
Comment # 45:
Sheet M2: Provide outside air for patient bedrooms at 1 person per bedroom.
(See attach response from Brittain Engineering)
Comment # 46:
Sheet E2: Water service line to connect to public water supply. Well cannot be used for
the building.
(See attach response from Brittain Engineering)
Comment # 47:
Sheet E5: What is the purpose of panel "L" (there is nothing in it, all spares)?
(See attach response from Brittain Engineering)
PAGE 5OF6
r
I y
i
4
R
ENVIRONMENTAL HEALTH REVIEW REFERENCE EHPR -5 -10 -5513
9 -
• On site waste water plans have been revised per separate comments from Luke Sears.
• All items noted by Scott Carpenter with respect to plan submittal, kitchen equipment
gspecs and food application have been taken care off.
FIRE STATUS: (PLAN RECEIVED - APPROVED WITH NOTES)
Y
Comment # 1:
Provide Knox box entry system for Fire Department access. Order forms and information
can be obtained from the Sherrills Ford - Terrell Fire & Rescue Department at 828 -478-
; 2131.
(See revised drawing CS3, A1.0, and A2.0 showing location of Knox Box)
Comment # 2:
Adequacy of egress illumination & exit signage will be verified at final inspection.
(We shall comply)
Comment # 3:
Provide detailed sprinkler plans.
(RESPONSE: DETAILED SPRINKLER PLANS WILL BE SUBMITTED FOR REVIEW AND
APPROVAL WHEN PREPARED AND SUBMITTED FOR PERMIT.)
Comment # 4:
Provide detailed kitchen layout with hood, and fire suppression system plans.
j (RESPONSE: DETAILS KITCHEN HOOD AND FIRE SUPPRESSION PLANS WILL BE SUBMITTED
FOR REVIEW AND APPROVAL WHEN SUBMITTED FOR PERMIT.)
Comment # 5:
Provide an additional smoke in linen room 112.
(RESPONSE: DRAWING E4 HAS BEEN MODIFIED TO SHOW SMOKE DETECTOR ADDED TO
I
LINEN ROOM.)
Comment # 6:
Fire Alarm and Sprinkler Installers must call for rough -in and final inspections. Have
contractor for both on site for testing at final inspection.
(RESPONSE: CONTRACTORS WILL BE PRESENT FOR TESTING.)
ZONING REVIEW REFERENCE ZON -5 -10 -5511
NOTES: 30 -36 RESPONSE: A DETAIL LANDSCAPE PLAN SHEET C7 HAS BEEN ADDED.
OTHER: A LETTER FROM THE CITY OF HICKORY INDICATING THAT PUBLIC WATER IS AVAILABLE
ON SHERRILLS FORD ROAD AND A COPY OF THE COMPLETED AND SUBMITTED WATER
APPLICATION TO THE COUNTY IS BEING SUBMITTED.
ATTACHMENTS: FOUR SETS OF REVISED DRAWINGS ONLY
PAGE 6OF6
END OF PROJECT CONSTRUCTION MEMO NUMBER ONE
L
E
I
{
BRITTAIN ENGINEERING, INC.
P.0 BOX 939 828 -328 -1813
HICKORY, NC 28603 FAX 828 -328 -1814
Item 24: See attached cut - sheets for the fixtures to be installed in the rated ceilings. (Fixtures H,
J, OA, I, and H/L)
Item 26: The largest gas furnace that is specified has a dimension of 21 "; therefore, the furnace
should fit between the roof truss spacing and down through the access stairs.
Item 38: Sheet P2 — A hose bib has been added in the kitchen area per NCPC 412.6.
i
Item 39: Sheer P2 - Domestic water service pipe has been connected to public water supply per
G 2009 NCPC 602.3 (See sheet C.6).
Item 40: Generator will have dual fuel sources — natural gas and LP gas. LP gas piping and tank
to be supplied by owner.
I
i
Item 41: Sheet M 1 — The return grille has been connected to the main return duct.
i
Item 42: Sheet M1— There are no fire damper penetrations of rated walls. The ceilings are the
only penetrations that are required and ceiling radiation dampers will be installed those
penetrations.
Item 43: Sheet M1 - The kitchen hood and related components shall be furnished and installed
by the owner. The manual activation device will be installed on the wall beside the
hood according to conversation with the installer.
Item 44: Sheet M1— The kitchen hood installer will provide the automatic shut -off valve and the
MC will install the valve in the piping. The hood installed will be responsible for all
interlock wiring for fuel shut -off valve.
Item 45: Sheet M2 — The outside air calculations are calculated for each bedroom and they are
for a typical bedroom. (50 cfm outside air is being supplied to each bedroom)
Item 46: Sheer E2 — The water service is connected to a public water supply. The existing well
will be used for irrigation purposes.
Item 47: Sheer E5 — Panel "L" is shown for a future expansion and is being installed to avoid
installing conduit, wire, etc. in the attic space at a later date.
CONSULTING MECHANICAL AND ELECTRICAL ENGINEERS
v
9
I
E
b arrier
X. f
i
' FIRE -RATED
{
Fire -Rated Exhaust
Fan /Light Enclosure
INSTALLATION INSTRUCTIONS
`s
1. Parts Provided:
j A) Fire rated enclosure with intumescent material
B) 3M PPD Ring — installed
C) 3" PVC Pipe — approximately 12" long
D) Air Duct reducer — attached to PVC Pipe
2. Take the 3" PVP Pipe (C) with the air duct reducer facing left and place it inside the fire rated enclosure
(A) and gently run it through the 3M PPD Ring (B) and through the enclosure opening. Be sure to slide
it through carefully so you don't damage the intumescent material inside the 3M PPD Ring.
3. Place enclosure on work bench with the opening facing up to be able to affix the exhaust fan to the
enclosure on two sides by using four tek screws.
4. To secure exhaust fan firmly to two sides, bend in the extended mounting bracket to be flush against the
exhaust fan.
5. Prior to mounting, tap out hole on back of enclosure (A).
6. Prior to mounting, run electrical wire from exhaust fan through tap out hole.
7. Mount the exhaust fan to the enclosure (A) on two sides using the four tek screws.
8. Assemble exhaust fan per product instructions. Once assembly is complete, slide air duct reducer over
exhaust fan duct connector until it fits flush.
9. Close 3M PPD Ring (B) by locking and securing per 3M instructions
10. Secure duck work to 3" PVC Pipe (C) outside opening.
(Installation instructions may vary slightly depending on type of fan model and size being installed in enclosure.)
20777 kensington Blvd. www.ezbarrier.com
Lakeville, MN 55044
Ph.952.985.8851 Fax 952.469.6565 Proudly made in the USA
sales @ezbarrier.net CIE—=
y
Fire Rated Bathroom exhaust fans - e z Barrier Page 1 of 2
Home I Code Requirements I Cer4ifications I FACs Rep Groups I Credit App I Request Ouote I About Us I Contact Us
T Fire Rated Bathroom exhaust fans
�I "Colo
Fire -Rated Exhaust Fan /Light
Enclosure - Bathroom.
The e.z. barrier enclosure makes it easy
for architects, specifiers and installers
to maintain the integrity of fire -rated
;..
ceil- ings for one -hour when penetrated
by an exhaust fan or fan /light R°
combination. Can be used for bathroom rg6
or kitchen.
Download PDF Sell Sheet for
Fire Rated Exhaust Fans Exhaust Fan & Fan /Light Corrbination
Enclosure Model # ezb 16 -24 -9exh (does not
include fan)
From our knowledge of fire codes and patented designs to our fabrication and quality
9 P 9 q Y
materials, we make enclosures that you can trust.
Install an exhaust fan in a fraction of the time it takes to hand -build an enclosure by using the
e.z. barrier enclosure that works with both an exhaust fan & fan /light combination. With four
knockouts, you have easy access from any direction. You'll save time and labor costs while
ensuring compliance to building codes. And, our product contains intumescent material that
provides sound reduction.
When it comes to one -hour fire -rated enclosures, count on e.z. barrier solutions from
the fire -rated enclosure experts.
We make it easy for you:
EZ to install.
EZ to save money.
EZ to meet the fire code.
Product Features for Model # ezb 16 -24 -9exh
• Works with both an exhaust fan and fan /light combination
• Fits both 16" and 24" on- center applications
• Features 4 knockouts for wiring flexibility with easy access from any direction
• Fits both 3" and 4" duct work (contact e.z. barrier for other sizes)
• Features intumescent material that helps maintain the acoustic integrity of the ceiling
• Maintains vapor barrier integrity to meet new "tight building" codes
• Maintenance free
• Affixed directly to the structure
Meets One -Hour Fire - Rating Enclosure Codes
Contains fire, gas, smoke and heat within the enclosure for 60 minutes, preventing leakage
through the assembly into duct work. Meets the following codes:
�pA r
..> r y
• ASTM El 19 -05a Certified by Omega Point Laboratories
• UL 263wiaio
• UBC 7 -1
• NFPA 251
• ANSI A2.1 •`•�`
• ULC S101 6 us Certified by Intertek & Warnock Hersey
r
http: / /www.ezbarrier.net/one- hour - fire - rated - enclosures /exhaust -fan 7/7/2010
Fire Rated Bathroom exhaust fans - e z Barrier Page 2 of 2
Specifications
r Flanges: 2 -5/8" wide for easy mounting
• Material: Corrosion - resistant metal
I Internal Dimensions: 19 -3/4" long x 11 -3/4" wide x 9 -3/8" deep (includes intumescent
§ material)
e.z. barrier Enclosure Prevents Fire From Escaping
The e.z. barrier enclosure
has been designed to In addition, a 3M intumescent
E prevent fire, gas, smoke lined metal ring is installed
and heat from escaping around the PVC duct exten-
and travel- ing into the y I''" sion pipe. As the PVC pipe
ductwork. In the event of a melts, the intumescent lining
fire, the 3M -r m* intu - ''
v in the ring expands to com-
mescent lining in the enclo p - pletely seal off the hole in the
sure expands up to five enclosure and prevent the
times its original size to µ leakage of fire, gas, smoke
contain the fire, gas, smoke and heat into the ductwork.
and heat.
i
3M is a registered trademark of 3M Company.
t
S
i
€ i
i
F Sitemap
Al
L
http: / /www.ezbarrier.net/one- hour -fire- rated - enclosures /exhaust -fan 7/7/2010
:1
i
5
'Y
3
F i reTi g htT1 DATE: TYPF
® s
FT6CF2 FIRM NAME:
+ *M PROJECT
u
6
2 -Hour Fire Resistant, AirShield
New Construction Vertical
Compact Fluorescent Downlight
� A l _
Non 1C Rated •
•' 1 20V 277V Aperture: Nominal 6"
i Ceiling Cutout: 6' /o"
Maximum Ceiling Thickness: 2"
For conversion to millimeters,
multiply inches by 25.4
Weight: 14 Ibs,
q APPLICATIONS: HOUSING: Not to Scale
3 Suitable for fire rated a3sem6lies in new Galvanized stool outer housing with lull wrap
construction where insulation, if present, around galvanized steel plaster frame Hous-
is not installed above or within 3" of the ing adjusts from !fie" to 2" for thick ceilings.
( fixture. The FT6CF2H can accommodate (1) Notched mounting frame for easy alignment. o
I 26W or 32W triple tube compact fluores- S ixpiecesofULclossilied fire resistant gypsum
cent lamp in a vertical orientation. Ideal for board attached to housing. Fiberglass gasket
hospitality, multifamily, office spaces, build- on bottom of frame to minimize heat transfer n
ings, and insitutional applications. into ceiling cavity. 9 9h
REFLECTOR: Housing includes knockout -free integral Romex
r
Trims accept o torsion spring in the housing clamps, oversproy protection, universal J-box
which has o positive upward spring action to with snap-out sides, '' /z" and 1 / 4 " knock outs for
ensure a snug fit to the ceiling plane, elimi- rigid conduit or BX fittings, thermal protector,
noting unwanted light leaks and sagging and a grounding pigtail. Rated for (8) tf 12
time. Trims come standard with a painted 90" conductors 14 in /4 out). Access door in
while trim ring. housing for field inspection of wiring. 13 1/
LAMP /SOCKET: LABELS:
Use one (1) 26W or 32W (GX24q - base Non-IC rated. Insulation, if present, must
J 4-pin triple tube compact fluorescent lamp. be spaced 3" away from housing. UL,
Olher 26W and 32W lamps with same CUL listed for damp location and through
f base may be used (check back page for wiring (wet location with lensed trims),
t max allowable lamp length). One (1) injec. AirShieldTm rated. Thermally protected SfC 9"
tion molded socket suitable for 26W or rated to maintain sound ratings.
32W triple tube lamps. Socket snaps into UL Classified to maintain fire rating up to Q
trim carrier to place lamp in proper posi- 1 hour for all UL P200 and P500 series
tion ensuring consistent appearance and fire rated roof /ceiling assemblies; UL _ O j
performance. Refer to trim for specific lamp classified to maintain fire rating up to 2 I
information. Lomps furnished by others, hours on ail UL D200, G200, L200, D500,
INSTALLATION: G500, end L500 series fire rated floor/
Bar hangers with integral T - Rat mounting
ceiling assemblies. c �L s c ®w rtsT®
Ky
clips and nail lob for wood joist construction.
Accommodates up to 24" nn center ceiling
joists. Shipped with four clips for installation I
to furring channels. I
s
- -- US Paiem Nos, 6,. 004,0 1;
5,750 6,OO J,01 I
CATALOG NUMBER. EXAMPLE: FT6CF2H -TB60
HOUSING TRIMS T RIMS TR IMS T RIMS A CCESSORIES
GT FT6CF2H BAffLE LENSED O?X WALL WA5H 0 G6
❑ CDN 120V G TS60 0 TL63 M T06 ❑ TW61 BI Ceiling gasket for 6"
Canadian Electrical 0 TBW60 0 TL64 ❑ T060B ❑ TW61'A DF line voltage trim. Ceiling
code compliant 0 TB61 U T060C gasket seals housing to p
ballosl disconnect 0 TBW61 U T060G drywall opening as an tt(
❑ T862 ❑ T061 option for Washington
0 TBW62 0 7062 State Energy Code
(WSEC) compliance
7
I
,�t rescol ite
In a continuing effort to offer the best product possible we reset• 3 the right to change, without
notice, specifications or materials that in our opinion will not all r the function of the product. e
A Division of Hubbell Lighting, Inc. Web: www.prescolife.com • Tech Support: (888) 177 FT:CFL - 002 t
L
a
F
E
Z'ol 9090 +1tib +8a8 ONI S311:3I00SSH 1H9IH19313 eal:60 01 g0 2nd
TRIMS &FINI FireTightT"' - FT6( F2H Vertical Compact Fluorescent
2 Hour :ire Resistant Recessed Downlight
i
Baffle Lensed Open Wall Wash
Q
4
T860 TL63 T06
Stepped block baffle. While domed polycorbonale shower While cone trim. TW61 BF
Max. 26W Triple Tube tense. O.D. 8'/4" dio. Wet location Max, 26W Triple Tube Block baffle wall wash.
approved. Max 26W Triple Tube Max. 26W Triple Tube
TBW60 T060B
Stepped while baffle. Specular block Alzokm rcflector. TW61 WBF
Max. 26W Triple Tube TL64 Max. 26W Triple Tube White baffle wall wash,
White olbolite flush glass lensed trim Max. 26W Triple Tube
Metal flonge Wet location approved.
Max. 26W Triple Tube
TB61 T060C
Black spray baffle. Specular clear Alzak reflector.
Max. 26W Triple Tube Max. 26W Triple Tube
TBW61 T060G
While spray baffle. Specular gold Alzak reflector
Max. 26W Triple Tube Max. 26W Triple Tube
TB62 T061
Black deep baffle. OD 8' / e" dio. White open splay trim.
Max. 26W or 32W Triple Tube Max. 26W Triple Tube
TOW62 l T062
White deep bolffe. O.D. 8 dia. High wattage while open trim.
Max. 26W or 32W Triple Tube O.D. 8 dio. {
Max. 26W or 32W Triple Tube b
(
T1 I[ 14UMBERS BELOW SHOW THE MAXIMUM
LE JGTH THAT WILL PHYSICALLY FIT INTO THE 1
CC \1SULT MANUFACTURER'S LAMP DATA FOR
IN ORMATION I
KC L. = MAXIMUM OVERALL LENGTH I
1
i
M.O.L�
_ I
TRI A NO. LAMP M. O.I.
W ', 1BW62,10 5.9' Ok 5.15/16'
TBE 1, TB61, TBW60, TBW61 5.5' OR 5.1/2"
TO, .106 1, TW61BF, TW61 BF $
Refer to www. epr scolile.com for photometrics. TL6 _TL61 /16 — I
116 .3" 0 4" P
k
Web: www.prsseolite.com • Tech Support: (888) 777.4832
r e s e o I i
te 701 Millennium Boulevard • Greenville, SC 29607 U.S.A. • Phone 18641678 -1000 HUBBELL
eopy,gM U7010 Re.<dn•- Y,c., a dii.ien of Mu66•II ugh", Inc AY RigHt. Re,r.•d
Spealicmonr -bpd to 64%e vrirfioa notes. • Pdnkd in U.SA. - FTOI-W2 - 5/18110 Hubbell Ughling, Inc.
k
E • d 9090+ I t'6 +BZB DWI S31d I30SSd IUO I NI3313 eZ I : EO 01 g0 2nd
TYPE
New Construction DATE: _ _
- FIRM NAME:
FT4LV
PROJECT. ,T /aSDi Ce,
4" Fire Resistant
Low Voltage
i4A Incandescent Downlight Fire
' One 50W MR -16 Lamp
Non Rat Aperture: 4"
Iv " Ceiling Cutout: 4'/2"
12V Maximum Ceiling Thickness: 2
For conversion to millimeters,
multiply inches by 25.4
Weight: 16.5 lbs.
APPLICATIONS INSTALLATION Not to Scale
Suitable for fire rated assemblies in new Bar hangers with integral T-bar mounting
construction where insulation is not present clips and nail tab for wood joist construc-
or is spaced 3" away. The FT4LV is ideal tion. Accommodates up to 24" on center
for applications that require low profile, ceiling joists. Captive bar hangers will lock
uncluttered ceiling planes and dramatic to secure housing in place. For installation
llumination of featured items such as art- of bar hangers to furring channels, order -
work and furnishings. Specify the FT4LV to FTFCC furring channel clips. -
a
accent items of interest in commercial HOUSING
office, retail and hospitality spaces, and Steel housing adjusts vertically to accom- Al e
residential multifamily bedrooms, living modate ceilings up to 2%" thick. Two (2)
rooms, foyers, and hallways. snap-on covers provide easy access to 10 14e \ a
REFLECTOR splices. Integral Romex clamp. Six pieces 0
Trims feature three simple spring retention of UL classified fire resistant gypsum board °
clips to ensure a snug fit to the ceiling plane, attached to housing. Fiberglass gasket on s
eliminating unwanted light leaks and sag- bottom of frame to minimize heat transfer °
ging over time. All trims are made of high into ceiling cavity.
quality stamped steel and have an integral J -BOX
trim flange. Reflectors are anodized to
ed steel junction box with
reduce the risk of yellowing, cracking or 9 own removed
v
warping. Matte white trim ring standard. g froround wire. Housing may be removed
m plaster frame after installation to pro -
LAMP /SOCKET vide access to 1 - box.
Lamp snaps into the trim carrier, placing LABELS
the lamp in the proper position to ensure Non -IC rated. Insulation, if present, must be
consistent appearance and performance. spaced 3" away from housing. U.L. and
Thermal protector prevents fixture From CUL listed for damp locations and through
overheating when improperly installed or wiring. Thermally protected. UL classified to
over - tamped. Refer to trim for specific lamp maintain fire ratings up to 1 hour for all UL �- 1
information. Lamp furnished by others. P200 and P500 series fire rated roof /ceil- °0
TRANSFORMER ing assemblies. UL classified to maintain_L�
Integral 12V electronic transformer. Trans- fire ratings up to 2 hours in all D200,
former is serviceable from below ceiling. G200, L200, D500, G500, and L500
series fire rated floor /ceiling assemblies.
e YL us a �L us trsnn
US Patent No. 6,357,891
CATALOG NUMBER: EXAMPLE: FTAV- -TAl2C
HOUSING TRIMS TRIMS ACCESSORIES
4 ❑ FT4LV ADJUSTABLE ADJUSTABLE BAFFLE ❑ FTFCC
❑ TAl2(C)(G) ❑ TAl2BF 4 clips to install bar
❑ TAl2E ❑ TAl2WBF hangers to furring
❑ TAl2PS channels
❑ TAl2SL ❑ ICBOX
Recessed enclosure
for IC applications.
Refer to specification
sheet FT4NC -005
4res In a continuing effort to offer the best product possible we reserve the right to change, without
notice, specifications or materials that in our opinion will not alter the function of the product.
A Division of Hubbell Lighting, Inc. Web: www.prescalite.com • Tech Support: (888) 777 -4832 FT -INC -001
i
FireTight - FT4LV 4" Low Voltage
TRIMS & FINISHES Fire Resistant Recessed Dow
Adjustable Adjustable Baffle
F
TAl2C
E Specular clear anodized reflector with TAl2BF
t 360 °H x 30eV adjustment. Black spun baffle with
Max. 20-50W MR -16, 12V 360eH x 30 °V adjustment.
9 Max. 20-50W MR -16, 12V
I
TAl2G
Specular gold anodized reflector with
360 °H x 30eV adjustment. TAl2WBF
Max. 20-50W MR -16, 12V White spun baffle with
360aH x 30 °V adjustment.
s Max. 20-50W MR -16, 12V
TAl2E
Eyeball, black interior with
360eH x 30eV adjustment.
Max. 20-50W MR -16, 12V
TAl25L
Oval slot with 360aH x 30 °V adjust-
ment.
Max. 20-50W MR -16, 12V
TAl2P5
Pinhole spot, spun black baffle cone
with 360eH x 30aV adjustment.
Max. 20-50W MR -16, 12V
Refer to www.prescolite.com for photometrics.
Web: www.prescolite.com • Tech Support: (888) 777 -4832
701 Millennium Blvd., Greenville, SC 29607 U.S.A. • Phone (864) 678 -1000 HUBBELL
r e s c o I I t e Copyright 02007 P—olite, Inc., a division of HubboU lighting, Inc AN Rights Reserved
4Specificat,ons subject to chmge without notice. • Primed in U.S.A. • FANC-001 • 09/27/07 Hubbell Lighting, Inc.
F i reTi g h tT" DATE'. TYPE 0�
AM x
FT6CF2H FIRM NAME: 6" 2 -Hour Fire Resistant AirShieldT" PROJECT:
New Construction Vertical
Compact Fluorescent Downlight
Non -IC Rated •
120V 277V Aperture: Nominal 6"
Ceiling Cutout: 6 7 /8"
Maximum Ceiling Thickness: 2"
For conversion to millimeters,
multiply inches by 25.4
Weight: 14 lbs.
APPLICATIONS: HOUSING: Not to Scale
Suitable for fire rated assemblies in new Galvanized steel outer housing with full wrap -
construction where insulation, if present, around galvanized steel plaster frame. Hous-
is not installed above or within 3" of the ing adjusts from 1 /2" to 2" for thick ceilings.
fixture. The FT6CF2H can accommodate (1) Notched mounting frame for easy alignment.
26W or 32W triple tube compact fluores- Six pieces of UL classified fire resistantgypsum
cent lamp in a vertical orientation. Ideal for board attached to housing. Fiberglass gasket
hospitality, multifamily, office spaces, build- on bottom of frame to minimize heat transfer
ings, and insitutional applications. into ceiling cavity. 9 9/16..
REFLECTOR Housing includes knockout -free integral Romex
Trims accept a torsion spring in the housing clamps, oversproy protection, universalJ -box ®ao
which has a positive upward spring action to with snap-outsides,' / and '/4" knock outs for
ensure a snug fit to the ceiling plane, elimi- rigid conduit or BX fittings, thermal protector,
nating unwanted light leaks and sagging and a grounding pigtail. Rated for (B) #12
time. Trims come standard with a painted 90° conductors (4 in /4 out). Access door in
white trim ring. housing for field inspection of wiring. 13 1 /4 n
LAMP /SOCKET: LABELS:
Use one (1) 26W or 32W (GX24q -3 base) Non -IC rated. Insulation, if present, must
4 -pin triple tube compact fluorescent lamp. be spaced 3" away from housing. UL,
Other 26W and 32W lamps with some CUL listed for damp location and through
base may be used (check back page for wiring (wet location with lensed trims).
max allowable lamp length). One (1) injec. AirShieldTM rated. Thermally protected. STC 91
tion molded socket suitable for 26W or rated to maintain sound ratings. CM CM
32W triple tube lamps. Socket snaps into UL Classified to maintain fire rating up to
trim carrier to place lamp in proper posi- 1 hour for all UL P200 and P500 series O
tion ensuring consistent appearance and fire rated roof /ceiling assemblies; UL
performance. Refer to trim for specific lamp classified to maintain fire rating up to 2
information. Lamps furnished by others. hours on all UL D200, G200, 1.200, D500,
INSTALLATION: G500, and L500 series fire rated floor /
Bar hangers with integral T-Bar mounting ceiling assemblies. ' g, us c VL us tlstto
clips and nail tab for wood joist construction.
Accommodates up to 24" on center ceiling
joists. Shipped with four clips for installation
to furring channels.
US Patent Nos. 6,357,891;
5,758,959; 6,004,011
CATALOG NUMBER: EXAMPLE: FT6CF2H -TB60
HOUSING TRIMS TRIMS TRIMS TRIMS ACCESSORIES
—� ❑ FT6CF2H BAFFLE LENSED OPEN WALL WASH ❑ G6
❑ CDN 120V ❑ TB60 ❑ TL63 ❑ T06 ❑ TW61 BF Ceiling gasket for 6"
Canadian Electrical ❑ TBW60 ❑ TL64 ❑ T060B ❑ TW61 WBF line voltage trim. Ceiling
code compliant ❑ TB61 ❑ T060C gasket seals housing to
ballast disconnect ❑ TBW61 / ❑ T060G drywall opening as an
❑ TB62 . i T061 option for Washington
❑ TBW62 ❑ T062 State Energy Code
(WSEC) compliance.
r e s c o I i t e In a continuing effort to offer the best product possible we reserve the right to change, without
notice, specifications or materials that in our opinion will not alter the function of the product.
A Division of Hubbell Lighting, Inc. Web: www.prescolite.com - Tech Support: (888) 777 -4832 FT -CFL -002
i
TRIMS &FINISHES FireTight"m - FT6CF2H Vertical Compact Fluorescent
2 Hour Fire Resistant Recessed Downlight
Baffle Lensed Open Wall Wash
•
TB60 TL63 T06
Stepped block baffle. White domed polycarbonate shower White cone trim. TW61 BF
Max. 26W Triple Tube tense. O.D. 8' /4" dia. Wet location Max. 26W Triple Tube Black baffle wall wash.
i approved. Max. 26W Triple Tube Max. 26W Triple Tube
i
l
i
s
TBW60 T060B
Stepped white baffle. Specular black Alzake reflector. TW61 WBF
Max. 26W Triple Tube TL64 Max. 26W Triple Tube White baffle wall wash.
White albalite flush glass lensed trim. Max. 26W Triple Tube
Metal flange. Wet location approved.
Max. 26W Triple Tube
TB61 T060C
Black spray baffle. Specular clear Alzak reflector.
Max. 26W Triple Tube Max. 26W Triple Tube
TBW61 T060G
White spray baffle. Specular gold Alzak reflector.
Max. 26W Triple Tube Max. 26W Triple Tube
TB62 T061
Black deep baffle. O.D. 8' /4" dia. White open splay trim.
Max. 26W or 32W Triple Tube Max. 26W Triple Tube
TBW62 T062
White deep baffle. O.D. 8'/." dia. High wattage white open trim.
Max. 26W or 32W Triple Tube O.D. 8'/." dia.
Max. 26W or 32W Triple Tube
THE NUMBERS BELOW SHOW THE MAXIMUM
LENGTH THAT WILL PHYSICALLY FIT INTO THE 1
CONSULT MANUFACTURER'S LAMP DATA FOR
INFORMATION
M.O.L. - MAXIMUM OVERALL LENGTH
— M.O.L
TRIM NO. LAMP M.O.L.
TB62 TBW62 T062 5.9' OR 5.15/16'
T860, TB61, TBW60, TBW61 5.5' OR 5-1/2'
T06, T061, TW61 BF, TW61 BF
Refer to www.prescolite.com for photometrics. TL60, TL64
TL63 4'
r Web: www.prescolite.com • Tech Support: (888) 777 -4832
r e s c o I I t e 701 Millennium Boulevard • Greenville, SC 29607 U.S.A. • Phone (864) 678 -1000 HUBS @LL
Copyright ®2010 P — lite, Inc., o diviswn d Hubbell Lighting, Inc. M Rights Reserved
Specificanons subject b change wiihom nice. - Printed in U.S.A. • FT{FL - 5/18 Hubbell Lighting, Inc.
New Construction DATE: TY
FT6 FIRM NAME:
E NiE \
1 6" Fire Resistant, AirShield PR OJECT:
- a Line Voltage
Incandescent Recessed Downlight
A] FireTight
ry . Non -IC Rated Aperture: Nominal 6"
VMV 1 20V Ceiling Cutout: 6' /8"
Maximum Ceiling Thickness: 2"
For conversion to millimeters,
multiply inches by 25.4
Weight: 14 lbs.
Not to Scale
APPLICATIONS: HOUSING:
Suitable for fire rated assemblies in new Galvanized steel outer housing with full wrap-
construction where insulation, if present, around galvanized steel plaster frame. Hous-
is not installed above or within 3" of the ing adjusts from '' /z" to 2" for thick ceilings.
fixture. The FT6 can accommodate up to Notched mounting frame for easy alignment.
150W. Ideal for hospitality, multifamily, Six piecesofULclassified fire resistantgypsum app
office spaces, buildings, and insitutional board attached to housing. Fiberglass gasket °
applications. on bottom of frame to minimize heat transfer
into ceiling cavity. s
REFLECTOR: 9916„
Trims accept a torsion spring in the housing Housing includes knock out free integral (�
which has a positive upward spring action Romexclamps, overspray protection, universal
to ensure o snug fit to the ceiling plane, J -box with snap-out sides, '' /z" and 3 /4" knock °
eliminating unwanted light leaks and sag- outs for rigid conduit or BX fittings, thermal
ging over time. Trims come standard with a protector, and a grounding pigtail. Rated
painted white trim ring. for (8) #12 90° conductors (4 in /4 out).
LAMP /SOCKET Access door in housing for field inspection
Porcelain socket with brass or copper of wiring.
screw shell. Socket snaps into trim carrier LABELS:
to place lamp in proper position ensuring Non-IC rated. Insulation, if present, must
consistent appearance and performance. be spaced 3" away from housing. UL, CUL
Thermal protector prevents fixture from listed for damp location and through wir-
overheating when improperly installed or ing. Wet location when used with lensed
overaamped. Refer to trim for specific lamp trims T063WL and T064W1. AirShieldTM 93/16
information. Lamps furnished by others. rated. Thermally protected. STC rated to I —
maintain sound rati
INSTALLATION: I Q
Bar hangers with integral T-Bar mounting UL Classified to maintain fire rating up to 1 o j ° 0
clips and nail tab for wood joist construction. hour for all UL P200 and P500 series fire — J
Accommodates up to 24" on center ceiling rated roof /ceiling assemblies; UL classified
joists. Shipped with four clips for installation to maintain fire rating up to 2 hours on
all a UL D200, G200, L200, D500, G500,
to furring channels. 0V
and L500 series fire rated floor /ceiling 4 4L us gnus tarty
assemblies.
US Patent Nos. 6,357,891;
5,758,959; 6,004,011
CATALOG NUMBER: EXAMPLE: FT6-TB60
i
HOUSING TRIMS TRIMS TRIMS TRIMS TRIMS ACCESSORIES
f ❑ FT6 ADJUSTABLE BAFFLE LENSED OPEN WALL WASH 0 G6
-)❑ TA60 ❑ TB60 ❑ TL60 ❑ T06 ❑ TW61 BF Ceiling gasket for I
❑ TA65 ❑ TBW60 ❑ TL61 ❑ T060B ❑ TW61 WBF 6" line voltage trim.
❑ TAW65 ❑ T661 ❑ TL62 ❑ T060C Ceiling gasket seals
❑ TBW61 ❑ TL63 ❑ T060G housing to drywall
❑ TB62 ❑ TL64 ❑ T061 opening as an option
❑ TBW62 ❑ T062 for Washington
OPEN SHOWER State Energy Code
❑ T063WL (WSEC) compliance.
❑ T064WL ❑ ICBOX
Recessed enclosure
for IC applications.
Refer to specification
sheet FTINC -005
4 re scol i te In a continuing effort to offer the best product possible we reserve the right to change, without
notice, specifications or materials that in our opinion will not alter the function of the product.
A Division of Hubbell Lighting, Inc. Web: www.prescalitte.com - Tech Support: (888) 777 -4832 FT-INC-004
- TRIMS &FINISHES Firelight - FT6 Incandescent Line Voltage
Fire Resistant Recessed Downlight
Adjustable Baffle (cont.) Open
Wall Wash
TA60 T862 T06
White eyeball. Block stepped baffle. O.D. 8'/4" dia. White cone trim. TWbI BF
Max. 75W PAR -30, 85W BR -30 Max. 150W /PAR -38, 120W BR -40 Max. 150W PAR -38, 120W BR-40, Black baffle wall wash.
Adj. 358 "H x 30 °V 100W A -19 Max. 40W A -19
TBW62
TA65, TAW65 White stepped baffle. O.D. 8 dia. TO60B TW61 WBF
Black (TA65) or while (TAW65) re- Max. 150W /PAR -38, 120W BR -40 Specular block Alzak reflector. White baffle wall wash.
gressed baffle eyeball. Max. 150W PAR -38, 120W BR-40, Max. 40W A -19
Max. 75W PAR -30, 85W BR -30 100W A -19
Adj. 350aH x 30eV Lensed
Open Shower
Baffle
TO60C
TL60 Specular clear Alzak reflector.
Shower light with glass dropped opal Max. 150W PAR -38, 120W BR-40, TO63WL
tense. Nowetallic flange. Wet location 1 OOW A -19
approved. White open shower trim. Metal flange. High Wet location approved.
Max. 75W PAR -30, bOW A -19
High wattage stepped block baffle. Max. 50W PAR -30L
Max. 150W PAR -38, 100W A -19, -
120W BR -40''
TO60G
Specular gold Alzak reflector.
TL61 Max. 150W PAR -38, 120W BR-40,
Shower trim with dropped opal glass l OOW A -19 TO64WL
tense. O.D. dia. Metal flange. High wattage white open shower trim.
Wet location n approved. ''
TBW60 Max. 75W A -19 O.D. 8 dia. Metal Flange. Wet loca-
tion approved.
High wattage stepped white baffle. Max. 75W PAR -38
Max. 150W PAR -38, 120W BR -40,
I OOW A -19 TO61
White open splay trim.
Max. 75W PAR -30L, 85W BR -30, 75W
TL62 A -19
Fresnel glass shower lense. Wet location 1
approved. Non - metallic flange.
Max. 50W PAR -30
TB61
Black stepped baffle.
Max. 75W /PAR -301, 85W BR30,
75W A -19 TO62
High wattage white open trim.
TL63 O.D. 8' /4" dia.
While domed polycarbonate shower Max. 150W PAR-38,120W BR-40
lense. O.D. 8'/4" dia. Wet location
approved.
Max. 60W A -19
TBW61
White stepped baffle.
Max. 75W /PAR -301, 85W BR -30,
75W A -19
TL64
White albalite flush glass lensed trim.
Metal flange. Wet location approved.
Max. 40W A -19
Refer to www.prescofite.com for photometrics.
i
4resc Web: www prescolite.com •Tech Support: (888) 777 -4832
701 Millennium Blvd., Greenville, SC 29607 U.S.A. - Phone (864) 678-1000 HUBBELL
Copyright ®2009 Pnocolite, Inc., a division of Hubbell Lighting, Inc. AN Rights Reserved
olite
Specification, subject to change v i"t notice. - Primed in U.S.A. - FTINC-0o4 - 6/24/09 Hubbell Lighting, Inc,
I