June 29, 2010 E
MOSER
Mr. James Lamb MAYE R
Catawba County Plan Review PHOENIX
76 North Center Street ASSOCIATES, PA
Hickory, NC 28601
Re: Verizon Wireless Cellular Sales
Hickory North Carolina
� Architecture
MMPA Project No. 10 113. 00 Engineering
In Desi n
Dear Mr. Lamb: g
Site Services
Moser Mayer Phoenix Associates has received and evaluated the comments related
to the proposed Verizon Renovation Project and is responding to each comment.
1. Sheet ALL, Appendix B: The floor area per occupant for mercantile, grade level i
is 30 square feet gross per Table 1004.1 of the 2009 NC Building Code.
Response: We have changed our figure of 60gsf/person to 30 and have added
a line for the back of house occupancy based on the most
restrictive figure of 100gsf /person. The occupancy has increased.
Please note we had intended to provide 2 exits due to the path of
travel distance, but had not identified the rear door as an exit.
2. Sheet ALL and ELP1.1: Two exits are required per Section 1019.2 of the 2009 s
NC Building code. The appendix, exit requirements show two exits. However,
only one exit is designated with exit lights /signs. 3 2 8 E a s t
Market Street
Response: Our reflected ceiling plan and electrical drawings now show the S u i t e z 0 0
required exit signs directing the occupants to 2 separate exits. G r e e n s b o r o
North Carolina
3. Sheet ALL, detail 3: Provide vertical grab bars at the water closets complying 2 7 4 0 1
with Section 604.5.1 of ICC /ANSI A117.1 -2003 Accessible and Usable
Buildings and Facilities.
P 336.373.9800
C
Response: This required vertical grab bar has been added to the drawings. F 336.373.0077
4. Sheet P1.1: The break room sink is required to be accessible per Section 1109.3
of the 2009 NC Building Code and shall comply with Section 606 of ICC /ANSI
Al 17.1 -2003 Accessible and Usable Buildings and Facilities.
Response: We have added a note to the architectural drawings requiring a
clear floor space under the break room sink which complies with
www.mmpa.com
code. SK -1 has been scheduled as a 6' /Z" deep sink. r
a
Mr. James Lamb - Catawba County Plan Review
Verizon Wireless Cellular Sales - Hickory, North Carolina
5. Sheet P1.1: The minimum diameter for waste piping underground is 2 inches per footnote F tQ 1
Table 710.1(2) of the 2009 NC Building Code. The waste piping form the lavatories to the
building drain is shown to be 1-1/2 inches.
Response: 1 -'/z" diameter waste piping underground is now changed to 2" waste
underground on sheet P1.1.
6. Sheet P1.1: The dry vent upstream of the two water closets does not comply with Section 905.4 i
of the 2009 NC Building Code.
Response: Detail 5/P1.1 has been added to show a 4" combination Y & eighth bend with a
horizontal to vertical rise of 90 degrees reducing to a 2" vent vertically to
comply with Section 905.4 of the 2009 Code.
Please do not hesitate to contact me if there are additional items that need to be addressed. We look
forward to receiving comments and approval for the current design.
Sincerely,