2604 Willis Court, Wilson, NC 27896
Phone: 252-243-7693— Email: aqwatammysanders@gmail.com
Customer Name: Shenoy System: SSD
Inspector: Chad Allen Date of Inspection: April 28,2022
Arrival lime: Departure Time:
Drip Irrigation Maintenance Checklist
Current Readings
Pump Filter Flush Zone Flush Zone 1 Zone 2 Zone 3 Zone 4
Counter 265 284 2 136 132
Timer 13.1 1.4 0.1 17.53 17.36
Flow Meter: 9370
Previous Inspection Readings Date of Previous Inspection: 2/9/2022
Pump Filter Flush Zone Flush Zone 1 Zone 2 Zone 3 Zone 4
Counter 0 0 0 3 0
Timer 0 0 0 0.1 0
Flow Meter: 720
Elapsed Calculations Elapsed Days: 77
Pump Filter Flush Zone Flush Zone 1 Zone 2 Zone 3 Zone 4
Counter 265 264 2 133 132
Timer 13.1 1.4 0.1 17.43 17.36
Total Flow Since Last Visit: 8650 Number of Days: 77 Average Daily Flow: 112.3376623
Spin Filter: Cleaned Filtrate Return Line: Yes Closed
Zone Testing
Zone 1 Zone 2 Zone 3 Zone 4
Pre Filter(PSI) 60 60
Post Filter(PSI) 58 60
Dose Rate(GPM) 8.1 8.2
Supply PSI 40 58
Return PSI 36 54
Flush Rate GPM 12.1 14.9
Flush Supply PSI 20 20
Flush Return PSI 0 0
Inspection Comments
Inspector's Signature
r •
AOWA
The clew leader.
AQWA Inc.
2604 Willis Court,Wilson, NC 27896
Phone: 252-243-7693- Email: agwatammysanders@gmail.com
Customer Name: Shenoy Date of Inspection: 4/28/2022
Address: Shenoy-4260 4th Street Lane NW,Hickory,NC 28601 Arrival lime: 8:30:00 AM
System AX ID: AX-153461 Departure Time: 10:25:00 AM
County: Catawba
Permit No.
Inspection and Maintenance Checklist-AX-RT Sub Surface or Surface Drip Dispersal
Septic Tank Inspection
Tank At Site Tank 1 _
Tank 1 Inlet Readings Tank 2 Inlet Readings
0 Scum 10 Sludge Scum Sludge
Tank 1 Outlet Readings Tank 1 Outlet Readings
0 Scum 10 Sludge Scum Sludge
Tank Inspection Questions Tank 1 Tank 2
Clean Effluent Filter: Cleaned
Check for Influent or Effluent Blockages: Cannot see inlet pipe
Inspect Tank/Riser for Leaks: None Seen
Control Panel Inspection
Check Pump Operates In Manual Mode: Yes
Recirculation Pumps
Pump 1 Timer Settings Pump 1-Counters and Elapsed Time Meters
0.8 Dose 10 Rest 9201 CT 124.5 ETM
Dose Pumps
Pump 1 Timer Settings Pump 1-Counters and Elapsed Time Meters
8 Dose 80 Rest 265 CT 13.1 ETM
Verify Conduit Seal: Verified
AX-RT Treatment Pod Inspection u
I P G:Ita. _ dFi n,.. cat "904KI i..,rl�tak1t4 �1 '�4h�; s.'.?;'c?i�i�
Inspect for Ponding or Bridging: None
Check and Record PSI: 4.5
Verify Orifice Position and Assess for Clogging: Cleaned
Check for Odors: None
Clean,Brush,Flush Lateral: Done
Recheck and Record PSI 4.5
Flush Pod Throroughly: Done
Inspect and Clean Vents: Cleaned
Inspection and Maintenance Checklist-AX-RT Sub Surface or Surface Drip Dispersal
Recirculation Chamber Inspection
Verify Inlet Flow: No Inflow
Inspect Liquid: Normal Level
Record Scum/Sludge Levels:
Inlet Readings: Outlet Readings:
0 Scum 3 Sludge 0 Scum 0 Sludge
Inspect Tank/Riser for Leakage: None Seen Verify All Floats Work: Operating Properly
Pump Sludge to Septic Tank: Not Needed Verify Audible Alarm Works for High Water float: Works Properly
Pull Pump and Clean Screen: Cleaned Verify Neat Wrap of Float and Pump Cords: Checked
Verify No Leaking In Piping or Flex Hoses: None Seen Verify Conduit Seal: Verified
Ultraviolet Disinfection Unit inspection
Does System Have a UV? Yes
How Many UV Disinfectant Units Present? UV 1
After Disconnecting Power,Clean or Replace Bulb As Needed: Cleaned
Flush Housing Thoroughly: Flushed
Return Power and Verify Proper Function: Verified
Dosing Chamber Inspection
Inspect for Tank/Riser Leakage: None Seen
Inspect Liquid: Normal Level
Record Scum/Sludge Levels:
Inlet Readings: Outlet Readings:
0 Scum 0 Sludge 0 Scum 0 Sludge
VisuaNy Check Liquid Level: Normal Verify Audible Alarm Works for High Water float: Works Properly
Verify No Leaks In Piping or Flex Hoses: None Seen Verify Neat Wrap of Float and Pump Cords: Checked
Inspect Pump Intake: Ok Delivery Rate at Start Up: 6
Verify All Floats Work: Operating Properly Verify Conduit Seal: Verified
Drip Irrigation System Area Inspection
Areas Mowed and Clear of Obstruction: Yes
Area Free of Ponding or Surface Effluent: Yes
Curtain Drains,Ditches,Swales Functioning Property: Yes
Return Valves and Control Panel to proper settings Done
Control Panel Communication Checked: Panel called in.
Inspection Notes
Adjusted the dose floats.The way they were set was middle and top float
were at the top of the tank.I moved them down but kept the spacing they
had.
Chad Allen
Operator Operators Signature
aAOWA AQWA Inc.
The clear leader
2604 Willis Court, Wilson, NC 27896
Phone: 252-243-7693 — Email: agwatammysanders@gmail.com
Customer Name: Shenoy System: SSD
Inspector: Chad Allen Date of Inspection: August 16.2022
Arrival Time: Departure Time:
Drip Irrigation Maintenance Checklist
Current Readings
Pump Filter Flush Zone Flush Zone 1 Zone 2 Zone 3 Zone 4
Counter 470 5 4 239 MEM
Timer 40.6 2.2.5 0.2 39,46
Flow Meter: 22580
Previous Inspection Readings Date of Previous Inspection: 4/28/2022
Pump Filter Flush Zone Flush Zone 1 Zone 2 Zone 3 Zone 4
Counter 265 264 2 136 132
Timer 13 1 1.4 0.1 17.53 17.36
Flow Meter: 9370
Elapsed Calculations Elapsed Days: 110
Pump Filter Flush Zone Flush Zone 1 Zone 2 Zone 3 Zone 4
Counter 205 201 2 103 103
Timer 27.5 1.1 0.1 2193 22.12
Total Flow Since Last Visit: 13210 Number of Days: 110 Average Daily Flow: 120.0909091
Spin Filter: Cleaned Filtrate Return Line: Yes Slightly Open
Zone Testing
Zone 1 Zone 2 Zone 3 Zone 4
Pre Filter(PSI) 58 58
Post Filter(PSI) 58 58
Dose Rate(GPM) 6 6.2 ■-
Supply PSI 48 56
Return PSI 44 50
Flush Rate GPM 12.5 14
Flush Supply PSI 20 22
Flush Return PSI 0 0
Inspection Comments
Inspector's Signature
AQWA
AQWA Inc.
2604 Willis Court,Wilson, NC 27896
Phone: 252-243-7693- Email: aqwatammysanders@gmail.com
Customer Name: Shenoy Date of Inspection: 0(16,2022
Address: Shenoy-4260 4th Street Lane NW.Hickory,NC 28601 Arrival Time: 10:45.43 AM
System AO(ID: AX•153461 Departure Time: 1:20 00 PM
County: Catawba
Permit No.
Inspection and Maintenance Checklist-AX-RT Sub Surface or Surface Drip Dispersal
Septic Tank Inspection
Tank At Site rank 1
Tank I Inlet Readings Tank 2 Inlet Readings
1 Scum 12 Sludge Scum Sludge
Tank 1 Outlet Readings Tank 1 Outlet Readings
0 Scum tt Sludge Scum Sludge
Tank Inspection Questions Tank 1
Clean Effluent Filter Cleaned
Check for Influent or Effluent Blockages: Cannot see inlet pipe
Inspect Tank/Riser for Leaks. None Seen
Control Panel Inspection
Check Pump Operates In Manual Mode- Yes
Recirculation Pumps
Pump 1 Timer Settings Pump t-Counters and Elapsed Time Meters
0 8 Dose 10 _Rest 20357 CT 276.2 ETM
Dose Pumps
Pump 1 Timer Settings Pump 1-Counters and Elapsed Time Meters
8 Dose 80 Rest 470 CT 40.6 ETM
Verify Conduit Seal Verified
AX-RT Treatment Pod Inspection
Inspect for Pending or Bridging: None
Check and Record PSI: 4.5
Verify Orifice Position and Assess for Clogging: Cleaned
Check for Odors: None
Clean,Brush,Flush Lateral: Done
Recheck and Record PSI 4.5
Flush Pod Throroughly: Done
Inspect and Clean Vents: Cleaned
Inspection and Maintenance Checklist-AX-RT Sub Surface or Surface Drip Dispersal
Recirculation Chamber Inspection
Verify Inlet Flow Inflow
Inspect Liquid: Normal Level
Record Scum/Sludge Levels:
Inlet Readings: Outlet Readings:
0 Scum 3 Sludge 0 Scum 0 Sludge
Inspect Tank/Riser for Leakage: None Seen Verify All Floats Work: Operating Properly
Pump Sludge to Septic Tank: Not Needed Verify Audible Alarm Works for High Water float: Works Property
Pull Pump and Clean Screen: Cleaned Verify Neat Wrap of Float and Pump Cords: Checked
Verify No Leaking In Piping or Flex Hoses: None Seen Verify Conduit Seal- Verified
Ultraviolet Disinfection Unit Inspection
Does System Have a UV? Yes
How Many UV Disinfectant Units Present?
UV 1
After Disconnecting Power,Clean or Replace Bub As Needed: Replaced
Flush Housing Thoroughly: Flushed
Return Power and Verify Proper Function: Verified
Dosing Chamber Inspection
Inspect for Tank/Riser Leakage: None Seen
Inspect Liquid: Normal Level
Record Scum/Sludge Levels:
Inlet Readings: Outlet Readings:
0 Scum 0 Sludge 0 Scum 0 Sludge
Visually Check Liquid Level: Normal Verify Audible Alarm Works for High Water float: Works Properly
Verify No Leaks In Piping or Flex Hoses: None Seen Verify Neat Wrap of Float and Pump Cords: Checked
Inspect Pump Intake: Cleaned Delivery Rete at Start Up: B
Verify All Floats Work: Operating Properly Verity Conduit Seal: Verified
Drip Irrigation System Area Inspection
Areas Mowed and Clear of Obstruction: Yes
Area Free of Pending or Surface Effluent: Yes
Curlew Drains,Ditches,Swales Functioning Properly: Yes
Retum Valves and Control Panel to proper settings Done _
Control Panel Communication Checked: Panel called in.
Inspection Notes
When I arrived the system was completely loaded up.No lights on the board
was lit up.Found the fuse on the lop of the board was blown.Replaced with
a new slow blow fuse.The lantronics was also not working.Replaced with a
new one.System now in normal level and operating correctly.
Chad Allen
Operator Operators Signature
•AQWA
The ilea leader.
AQWA Inc.
2604 Willis Court,Wilson, NC 27896
Phone: 252-243-7693—Email:aqwatammysanders@gmail.com
Customer Name: Shenoy Date of Inspection: 10/13/2022
Address: Shenoy-4260 4th Street Lane NW,Hickory,NC 28601 Arrival Time: 1:50:00 PM
System AX ID: AX-153461 Departure lime: 3:15:00 PM
County: Catawba
Permit No.
Inspection and Maintenance Checklist-AX-RT Sub Surface or Surface Drip Dispersal
Septic Tank Inspection
Tank At Site Tank 1
Tank 1 Inlet Readings Tank 2 Inlet Readings
0 Scum 6 Sludge Scum Sludge
Tank 1 Outlet Readings Tank 1 Outlet Readings
0 Scum 3 Sludge Scum Sludge
Clean Effluent Filter: Cleaned
Check for Influent or Effluent Blockages: No Blockage
Inspect Tank/Riser for Leaks: None Seen
Control Panel Inspection
Check Pump Operates In Manual Mode: Yes
Recirculation Pumps
Pump 1 Timer Settings Pump 1-Counters and Elapsed Time Meters
0.8 Dose 10 Rest 27945 CT 379.3 ETM
Dose Pumps
Pump 1 Timer Settings Pump 1-Counters and Elapsed Time Meters
Demand Dose Demand Rest 583 CT 55.2 ETM
Verify Conduit Seal: Verified
AX-RT Treatment Pod Inspection
Inspect for Ponding or Bridging: None
Check and Record PSI: 4.5
Verify Orifice Position and Assess for Clogging: Cleaned
Check for Odors: None
Clean,Brush,Flush Lateral: Done
Recheck and Record PSI 4.5
Flush Pod Throroughly: Done
Inspect and Clean Vents: Cleaned
Inspection and Maintenance Checklist-AX-RT Sub Surface or Surface Drip Dispersal
Recirculation Chamber Inspection
Verify Inlet Flow: No Inflow
Inspect Liquid: Normal Level
Record Scum/Sludge Levels:
Inlet Readings: Outlet Readings:
0 Scum 1 Sludge 0 Scum 0 Sludge
Inspect Tank/Riser for Leakage: None Seen Verify All Floats Work: Operating Properly
Pump Sludge to Septic Tank: Not Needed Verify Audible Alarm Works for High Water float: Works Properly
Pull Pump and Clean Screen: Cleaned Verify Neat Wrap of Float and Pump Cords: Checked
Verify No Leaking In Piping or Flex Hoses: None Seen Verify Conduit Seal: Verified
Ultraviolet Disinfection Unit Inspection
Does System Have a UV? Yes
How Many UV Disinfectant Units Present? UV 1
After Disconnecting Power,Clean or Replace Bulb As Needed: Cleaned
Flush Housing Thoroughly: Flushed
Return Power and Verify Proper Function: Verified
Dosing Chamber Inspection
Inspect for Tank/Riser Leakage: None Seen
Inspect Liquid: Normal Level
Record Scum/Sludge Levels:
Inlet Readings: Outlet Readings:
0 Scum 0 Sludge 0 Scum 0 Sludge
Visually Check Liquid Level: Normal Verify Audible Alarm Works for High Water float: Works Properly
Verify No Leaks In Piping or Flex Hoses: None Seen Verify Neat Wrap of Float and Pump Cords: Checked
Inspect Pump Intake: Ok Delivery Rate at Start Up: 6
Verify All Floats Work. Operating Properly Verify Conduit Seal: Verified
Drip irrigation System Area Inspection
Areas Mowed and Clear of Obstruction: Yes
Area Free of Ponding or Surface Effluent: Yes
Curtain Drains,Ditches,Swales Functioning Properly: Yes
Return Valves and Control Panel to proper settings Done
Control Panel Communication Checked: Panel called in.
Inspection Notes
f -
Paul Smith
Operator Operators Signature
aAQWAM AQWA Inc.
The clew Irrder
2604 Willis Court, Wilson, NC 27896
Phone: 252-243-7693 — Email: aqwatammysanders@gmail.com
Customer Name: Shenoy System: SSD
Inspector: Paul Smith Date of Inspection: November 2,2022
Arrival Time: Departure Time:
Drip Irrigation Maintenance Checklist
Current Readings
Pump Filter Flush Zone Flush Zone 1 Zone 2 Zone 3 Zone 4
Counter 609 604 8 308 305
Timer 58.6 3.2 0.3 54.21 54.54
Flow Meter: 31190
Previous Inspection Readings Date of Previous Inspection: 8116/2022
Pump Filter Flush Zone Flush Zone 1 Zone 2 Zone 3 Zone 4
Counter 470 465 4 239 235
Timer 40.6 2.5 0.2 39.46 39.48
Flow Meter: 22580
Elapsed Calculations Elapsed Days: 78
Pump Filter Flush Zone Flush Zone 1 Zone 2 Zone 3 Zone 4
Counter 139 139 2 69 70 --
Timer 18 0.7 0.1 14.75 15.06 --
Total Flow Since Last Visit: 8610 Number of Days: 78 Average Daily Flow: 110.3846154
Spin Filter: Cleaned Filtrate Return Line: Yes Slightly Open
Zone Testing
Zone 1 Zone 2 Zone 3 Zone 4
Pre Filter(PSI) 58 58
Post Filter(PSI) 58 58
Dose Rate(GPM) 6.3 6.1
Supply PSI 50 48
Return PSI 48 48
Flush Rate GPM 11.9 12.6
Flush Supply PSI 20 20
Flush Return PSI 0 0
Inspection Comments
Inspectors Signature
AO A1A AQWA Inc. ' ' /2/51) 1
The clear leader.
2604 Willis Court, Wilson, NC 27896
Phone: 252-243-7693— Email: aqwatammysanders@gmail.com
Customer Name: Shenoy System: SSD
Inspector: Jeff Cranmer Date of Inspection: June 20,2023
Arrival Time: Departure Time:
Drip Irrigation Maintenance Checklist
Current Readings
Pump Filter Flush Zone Flush Zone 1 Zone 2 Zone 3 Zone 4
Counter 963 956 8 485 482
Timer 104.8 5 0.4 92,38 92.38 ,
Flow Meter: 52570
Previous Inspection Readings Date of Previous Inspection: 11/212022
Pump Filter Flush Zone Flush Zone 1 Zone 2 Zone 3 Zone 4
Counter 609 604 6 308 305
Timer 58.6 3.2 0.3 54.21 54.54
Flow Meter: 31190
Elapsed Calculations Elapsed Days: 230
Pump Filter Flush Zone Flush Zone 1 Zone 2 Zone 3 Zone 4
Counter 354 352 2 177 177
Timer 46.2 1.8 0.1 38.17 37.84
Total Flow Since Last Visit: 21380 Number of Days: 230 Average Daily Flow: 92.95652174
Spin Filter: Cleaned Filtrate Return Line: Yes Closed
Zone Testing
Zone 1 Zone 2 Zone 3 Zone 4
Pre Filter(PSI) 65 65
Post Filter(PSI) 65 65
Dose Rate(GPM) 5.9 5.8
Supply PSI 45 45
Return PSI 45 45 -.
Flush Rate GPM 14.8 16.4
Flush Supply PSI 30 20 ■-
Flush Return PSI 0 0
Inspection Comments
Repaired 2 leaks in zone#2.
Inspector's Signature
eAo A
The clear leader.
AQWA Inc.
2604 Willis Court,Wilson, NC 27896
Phone: 252-243-7693—Email: aqwatammysanders@gmail.com
Customer Name: Shenoy Date of Inspection: 6/20/2023
Address: Shenoy-4260 4th Street Lane NW,Hickory,NC 28601 Arrival Time: 12:35:00 PM
System AX ID: AX-153461 Departure Time: 2:10:00 PM
County: Catawba
Permit No.
Inspection and Maintenance Checklist-AX-RT Sub Surface or Surface Drip Dispersal
Septic Tank Inspection
Tank At Site Tank 1
Tank 1 Inlet Readings Tank 2 Inlet Readings
0 Scum 6 Sludge Scum Sludge
Tank 1 Outlet Readings Tank 1 Outlet Readings
0 Scum 4 Sludge Scum Sludge
.
Clean Effluent Filter: Cleaned
Check for Influent or Effluent Blockages: No Blockage
Inspect Tank/Riser for Leaks: None Seen
Control Panel Inspection
Check Pump Operates In Manual Mode. Yes
Recirculation Pumps
Pump 1 Timer Settings Pump 1-Counters and Elapsed Time Meters
0.8 Dose 10 Rest 58416 CT 792.2 ETM
Dose Pumps
Pump 1 Timer Settings Pump 1-Counters and Elapsed Time Meters
8 Dose 80 Rest 963 CT 104.8 ETM
Venfy Conduit Seal: Verified
AX-RT Treatment Pod Inspection
�a��'"RKA,.-..<,�..'.'X".
Inspect for Ponding or Bridging. None
Check and Record PSI: 4.5
Verify Orifice Position and Assess for Clogging: Ok
Check for Odors: None
Clean,Brush,Flush Lateral: Done
Recheck and Record PSI 4.5
Flush Pod Throroughly: Done
Inspect and Clean Vents: Vents Clear
Inspection and Maintenance Checklist-AX-RT Sub Surface or Surface Drip Dispersal
Recirculation Chamber Inspection
Verify Inlet Flow: No Inflow
Inspect Liquid: Normal Level
Record Scum/Sludge Levels:
Inlet Readings: Outlet Readings:
0 Scum 3 Sludge 0 Scum 2 Sludge
Inspect Tank/Riser for Leakage: None Seen Verify All Floats Work: Operating Properly
Pump Sludge to Septic Tank: Not Needed Verify Audible Alarm Works for High Water float: Works Properly
Pull Pump and Clean Screen: Cleaned Verify Neat Wrap of Float and Pump Cords: Checked
Verify No Leaking In Piping or Flex Hoses: Repairs Needed,See Notes Verify Conduit Seal: Verified
Ultraviolet Disinfection Unit Inspection
Does System Have a UV? Yes
How Many UV Disinfectant Units Present? UV
After Disconnecting Power,Clean or Replace Bulb As Needed: Cleaned
Flush Housing Thoroughly: Flushed
Retum Power and Verify Proper Function: Verified
Dosing Chamber Inspection
Inspect for Tank/Riser Leakage: None Seen
Inspect Liquid: Normal Level
Record Scum/Sludge Levels:
Inlet Readings: Outlet Readings:
0 Scum 4 Sludge 0 Scum 5 Sludge
Visually Check Liquid Level: Normal Verify Audible Alarm Works for High Water float: Works Properly
Verify No Leaks In Piping or Flex Hoses: None Seen Verify Neat Wrap of Float and Pump Cords: Checked
Inspect Pump Intake: Ok Delivery Rate at Start Up: 6
Verify All Floats Work: Operating Properly Verify Conduit Seal: Verified
Drip Irrigation System Area Inspection
Areas Mowed and Clear of Obstruction Yes
Area Free of Ponding or Surface Effluent: Yes
Curtain Drains,Ditches,Swales Functioning Properly: Yes
Return Valves and Control Panel to proper settings Done
Control Panel Communication Checked: Called in
Inspection Notes
On the recirc pump assembly that goes to filtrate line out of rt had a
split female threaded coupling.Could not repair due to not having a orenco
union(the filtrate return was shut off so capped line to stop leak)pics
in gmail.Will need to return with part for repair.
Jeff Cranmer �f
Operator Operators Signature
Ooo\9 - 13\�o t
•AQWA
The clear leader.
AQWA Inc.
2604 Willis Court,Wilson,NC 27896
Phone:252-243-7693—Email:aqwatammysanders@gmail.com
Customer Name: Shenoy Date of Inspection: 4/1/2025
Address: Shenoy-4260 4th Street Lane NW,Hickory,NC 28601 Arrival Time: 2:15:00 PM
System AX ID: AX-153461 Departure Time: 5:20:00 PM
County: Catawba
Permit No.
Inspection and Maintenance.Checklist-AX-RT Sub Surface or Surface Drip Dispersal
Septic Tank Inspection
Tank At Site Tank 1
Tank 1 Inlet Readings Tank Inlet Readings
0 Scum 4 Sludge Scum Sludge
Tank 1 Outlet Readings Tank 1 Outlet Readings
0 Scum 4 Sludge Scum Sludge
Tank Inspection Questions Tank i Tank 2
Clean Effluent Filter: Cleaned
Check for Influent or Effluent Blockages: No Blockage
Inspect Tank/Riser for Leaks: None Seen
Control Panel Inspection
Check Pump Operates In Manual,Mode: Yes
Recirculation Pumps
Pump 1 Timer Settings Pump 1-Counters and Elapsed Time Meters
0.8 Dose 10 Rest 38160 CT 1896.2 ETM
Dose Pumps
Pump 1 Timer Settings Pump 1-Counters and Elapsed Time Meters
8 Dose 80 Rest 1851 CT 209.3 ETM
Verify Conduit Seal: Verified
AX-RT Treatment Pod Inspection
Pod Inspection Pod 1
Inspect for Ponding or Bridging: None
Check and Record PSI: 4.5
Verify Orifice Position and Assess for Clogging: Ok
Check for Odors: Ok
Clean,Brush,Flush Lateral: Done
Recheck and Record PSI 4.5
Flush Pod Throroughly: Done
Inspect and Clean Vents: Vents Clear
Inspection and Maintenance Checklist-AX-RT Sub Surface or Surface Drip Dispersal
Recirculation Chamber Inspection
Verify Inlet Flow: No Inflow
Inspect Liquid: Normal Level
Record Scum/Sludge Levels:
Inlet Readings: Outlet Readings:
0 Scum 2 Sludge 0 Scum 1 Sludge
Inspect Tank/Riser for Leakage: None Seen Verify All Floats Work: Operating Properly
Pump Sludge to Septic Tank: Not Needed Verify Audible Alarm Works for High Water float: Works Properly
Pull Pump and Clean Screen: Cleaned Verify Neat Wrap of Float and Pump Cords: Checked
Verify No Leaking In Piping or Flex Hoses: None Seen Verify Conduit Seal: Verified
Ultraviolet Disinfection Unit Inspection
Does System Have a UV? Yes
How Many UV Disinfectant Units Present? UV 1
UV Disinfectant Unit Inspection UV 1 UV2
After Disconnecting Power,Clean or Replace Bulb As Needed: Cleaned
Flush Housing Thoroughly: Flushed
Return Power and Verify Proper Function: Verified
Dosing Chamber Inspection
Inspect for Tank/Riser Leakage: None Seen
Inspect Liquid: Normal Level
Record Scum/Sludge Levels:
Inlet Readings: Outlet Readings:
0 Scum 3 Sludge 0 Scum 4 Sludge
Visually Check Liquid Level: Normal Verify Audible Alarm Works for High Water float: Works Properly
Verify No Leaks In Piping or Flex Hoses: None Seen Verify Neat Wrap of Float and Pump Cords: Checked
Inspect Pump Intake: Ok Delivery Rate at Start Up: 6
Verify All Floats Work: Operating Properly Verify Conduit Seal: Verified
Turbidity: 2.70
Drip Irrigation System Area Inspection
Areas Mowed and Clear of Obstruction: Needs Mowing
Area Free of Ponding or Surface Effluent: Surfacing
Curtain Drains,Ditches,Swales Functioning Properly: Yes
Return Valves and Control Panel to proper settings Done
Control Panel Communication Checked: Called in
Inspection Notes
Surfacing water came from leaks found in zone 1 and 2.Leaks fixed,refer
to drip inspection for more info.
Christopher Sanders QA(1.7?
Operator Operators Signature
I
eAaWA AQWA Inc.
The clear leader.
2604 Willis Court,Wilson, NC 27896
Phone: 252-243-7693— Email: aqwatammysanders@gmail.com
Customer Name: Shenoy System: SSD
Inspector: Christopher Sanders Date of Inspection: April 1,2025
Arrival Time: Departure Time:
Drip Irrigation Maintenance Checklist
Current Readings
1
I Pump Filter Flush Zone Flush Zone 1 Zone 2, Zone 3 Zone 4
Counter 1851 1838 14 930 926
Timer 209.3 9.7 0.7 186.55 177.09 --
Flow Meter: 113190
Previous Inspection Readings Date of Previous Inspection: 10/24/2024
Pump Filter Flush Zone Flush Zone 1 Zone 2 Zone 3' Zone 4
Counter 1662 1660 12 841 837
Timer 176.6 8.8 0.6 168.53 161.51
Flow Meter: 100660
Elapsed Calculations Elapsed Days: 159
Pump Filter Flush Zone Flush Zone 1 Zone 2 Zone 3 Zone 4
Counter 189 178 2 89 89
Timer 32.7 0.9 0.1 18.02 15.58 --
Total Flow Since Last Visit: 12530 Number of Days: 159 Average Daily Flow: 78.80503145
Spin Filter: Replaced Filtrate Return Line: Yes Slightly Open
Zone Testing
Zone 1 Zone 2 - Zone 3 Zone 4 i
'Pre Filter(PSI) � - - 59 -----60 ---
Post'Filter(PSI) 51 52
Dose Rate(GPM) 5.7 4.8
Supply PSI 25 32
Return PSI 25 30
Flush Rate GPM 8.7 12.8
Flush Supply PSI 20 20
flush Return PSI ! 0 0
Inspection Comments _
During zone 1 field test,noticed high dose rate of 7.5gpm.Walked field
r
and found water shooting*out of a torn dripper tubing section.When I found
the leak,I also noticed ruts in the ground.Something heavy with wheels
has been across the two zones at this site.Drip field is not supposed to
have anything heavier than a lawnmower on it.Field has not been managed
either,overgrown grass mounds are all over zones although sod or
groundcover fails to exist in much of the field.Several sections of
dripper tubing are exposed in these zones and all dripper tubing should be
a minimum of 6"below grade.Grass was not planted and erosion has exposed
roughly 20 areas of tubing in these zones.Zone two had two leaks at the
bottom of zone next to lake.Runoff from these leaks could have made it to
the lake.Good topsoil needs to be added to exposed tubing areas of 6"
depth.Design engineer needs to approve the dirt that is brought in to
avoid field failure.Materials used on zone 1 leak was two screw black
couplings for dripper tubing.Zone 2 leaks were fixed using one black screw
coupling a piece.Total of four couplings used on all three leaks.
Additional time beyond prepaid maintenance spent repairing damaged lines.
The field is noncompliant with regulatory rules and in permit violation.
Pictures emailed.
?X
Inspector's Signature
eAa A
The clear leader.
AQWA Inc.
1908 Baldree Rd S,Wilson, NC 27893
Phone: 252-243-7693—Email: aqwatammysanders@gmail.com
Customer Name: Shenoy Date of Inspection: 7/16/2025
Address: Shenoy-4260 4th Street Lane NW,Hickory,NC 28601 Arrival Time: 7:30:00 AM
System AX ID: AX-153461 Departure Time: 10:30:00 AM
County: Catawba
Permit No.
Inspection and Maintenance Checklist-AX-RT Sub Surface or Surface Drip Dispersal
Septic Tank Inspection
Tank At Site Tank 1
Tank 1 Inlet Readings Tank 2 Inlet Readings
0 Scum 6 Sludge Scum Sludge
Tank 1 Outlet Readings Tank 1 Outlet Readings
0 Scum 4 Sludge Scum Sludge
Tank Inspection Ques ':
Clean Effluent Filter: Cleaned
Check for Influent or Effluent Blockages: No Blockage
Inspect Tank/Riser for Leaks: None Seen
Control Panel Inspection
Check Pump Operates In Manual Mode: Yes
Recirculation Pumps
Pump 1 Timer Settings Pump 1-Counters and Elapsed Time Meters
0.2 Dose 8 Rest 54889 CT 1962.4 ETM
Dose Pumps
Pump 1 Timer Settings Pump 1-Counters and Elapsed Time Meters
8 Dose 80 Rest 1981 CT 209.9 ETM
Verify Conduit Seal: Verified
AX-RT Treatment Pod Inspection
Pod Inspection Pod 1
Inspect for Ponding or Bridging: None
Check and Record Drawdown Inches Arrival: 4.5
Verify Orifice Position and Assess for Clogging: Cleaned
Check for Odors: None
Clean,Brush,Flush Lateral: Done
Recheck and Record Drawdown Inches Departure: 4.5
Flush Pod Throroughly: Done
Inspect and Clean Vents: Cleaned
Inspection and Maintenance Checklist-AX-RT Sub Surface or Surface Drip Dispersal
Recirculation Chamber Inspection
Verify Inlet Flow: No Inflow
Inspect Liquid: Normal Level
Record Scum/Sludge Levels:
Inlet Readings: Outlet Readings
0 Scum 1 Sludge 0 Scum 1 Sludge
Inspect Tank/Riser for Leakage: None Seen Verify All Floats Work: Operating Properly
Pump Sludge to Septic Tank: Not Needed Verify Audible Alarm Works for High Water float: Works Properly
Pull Pump and Clean Screen: Cleaned Verify Neat Wrap of Float and Pump Cords: Checked
Verify No Leaking In Piping or Flex Hoses: None Seen Verify Conduit Seal: Verified
Ultraviolet Disinfection Unit Inspection
Does System Have a UV? Yes
How Many UV Disinfectant Units Present? UV 1
UV Disinfectant Unit Inspection UV 1 UV2
After Disconnecting Power,Clean or Replace Bulb As Needed: Replaced
Flush Housing Thoroughly: Flushed
Return Power and Verify Proper Function: Verified
Dosing Chamber Inspection
Inspect for Tank/Riser Leakage: None Seen
Inspect Liquid: Normal Level
Record Scum/Sludge Levels:
Inlet Readings: Outlet Readings:
0 Scum 1 Sludge 0 Scum 1 Sludge
Visually Check Liquid Level: Normal Verify Audible Alarm Works for High Water float: See Notes
Verify No Leaks In Piping or Flex Hoses: None Seen Verify Neat Wrap of Float and Pump Cords: Checked
Inspect Pump Intake: Ok Delivery Rate at Start Up: 6
Verify All Floats Work: Malfunctioning Floats Verify Conduit Seal: Verified
Turbidity: 0.00
Drip Irrigation System Area Inspection
Areas Mowed and Clear of Obstruction: Needs Mowing
Area Free of Ponding or Surface Effluent: Surfacing
Curtain Drains,Ditches,Swales Functioning Properly: Yes
Return Valves and Control Panel to proper settings Done
Control Panel Communication Checked: Panel called in.
Inspection Notes
Filtrate return line dogged,cleared line.Dose pump high level/alarm
float not working properly,replaced with a blue collar float with 10 ft
electrical wire.Dripper tubing in field in about 20 sections are above
ground surfacing,not covered with soil.See previous reports regarding
this issue.
'11211-0i
Paul Smith
Operator Operators Signature
AQWAM AQWA Inc.
Thn clear leader
1908 Baldree Road S, Wilson, NC 27893
Phone: 252-243-7693- Email: aqwatammysanders@gmail.com
Customer Name: Shenoy System: SSD
Inspector: Paul Smith Date of Inspection: July 16,2025
Arrival Time: 7:30:00 AM Departure Time: 10:30:00 AM
Drip Irrigation Maintenance Checklist
Current Readings
Pump Filter Flush Zone Flush Zone 1 Zone 2 Zone 3 Zone 4
Counter 1981 1965 17 1003 999
Timer 209.9 10.4 0.8 198.55 192.42
Flow Meter: 121510
Previous Inspection Readings Date of Previous Inspection: 4/1/2025
Pump Filter Flush Zone Flush Zone 1 Zone 2 Zone 3 Zone 4
Counter 1851 1838 14 930 926
Timer 209.3 9.7 0.7 186.55 177.09
Flow Meter: 113190
Elapsed Calculations Elapsed Days: 106
Pump Filter Flush Zone Flush Zone 1 Zone 2 Zone 3 Zone 4
Counter 130 127 3 73 73
Timer 0.6 0.7 0.1 12 15.33
Total Flow Since Last Visit: 8320 Number of Days: 106 Average Daily Flow: 78.49056604
Spin Filter: Clogged,Replaced Filtrate Return Line: Yes Slightly Open
Zone Testing
Zone 1 Zone 2 Zone 3 Zone 4
Pre Filter(PSI) 64 64 -_
Post Filter(PSI) 65 65
Dose Rate(GPM) 6 6.1
Supply PSI 50 35
Return PSI 48 34 ■- ,
Flush Rate GPM 10.1 11.2
Flush Supply PSI 22 18
Flush Return PSI 0 0
Inspection Comments
Removed plug from green cap on spin filter due to pressure deforming
filter.Spin filter has green cap no plug. Filtrate return line clogged,
cleared line.There are still about 20 sections of dripper tubing that are
on top of the ground and need soil cover.See previous report details about
this.
Inspector's Signature