HomeMy WebLinkAboutCBPR-2-10-3790 Brittain Engr plan rev comments 3-2-10.tif f 1 BRITTAIN ENGINEERING, INC. P.0 BOX 939 828- 328 -1813 HICKORY, NC 28603 FAX 828 - 328 -1814 1 1 3 I I March 2, 2010 Arndt Middle School i Alterations & Addition Catawba County Commercial Building Plan Review Response i ITEM: 17) Sheet P 1 - See architectural for calculation. F 18) Sheet P 1 - See enlarged plans for waste and water in these areas. 19) Sheet P 1 - See enlarged plans for waste and water in these areas. 20) Sheet P2 - See enlarged plans for waste and water in these areas. { 21) Sheet P2 - See enlarged plans for waste and water in these areas. -224-sheet P2 - See enlarged plans for waste and water in these areas. 23) Sheet P3 - Is now sheet P4, See general note regarding return air plenum materials. 24) Sheet P4 - Is now sheet P5, See drawings for penetration details. 25) Sheet P4 - Is now sheet P5, See drawings for penetration details. 26) Sheet P9 - Is now sheet P 10, See revised drawings for pipe sizes. 27) Sheet P9 - Is now sheet P 10, See revised drawings for pipe sizes. 28) Sheet P9 - Is now sheet P10, See revised drawings for pipe sizes. 29) Sheet M2 - Smoke detector is provided for AHU -14. See Sheet M7, (E) Section. 30) Sheet M2 - Fire Damper details are shown on Sheet M -7, (G) Detail & (H) Detail. 31) Sheet M2 - The outside air Louvers and/or Hoods and ductwork are capable of handling 15 CFM of outside air per person in the classrooms per 2009 NCMC, Table 403.3, exception "J ". 32) Sheet M4 - UL Detail for pipe penetrations of 2 hour walls is shown on Sheet M6. 33) Sheet M6 - AHU -15 serves one area and the air distribution system is incapable of spreading smoke beyond this area (per 2009 NCMC, Paragraph 606.2, Exception). Therefore a smoke detector is not provided. 34) Sheet M6 - The outside air Louvers and/or Hoods and ductwork are capable of handling 15 CFM of outside air per person in the classrooms per 2009 NCMC, Table 403.3, exception "J ". I 35) Sheet M7 - Method of Compliance Form. This was moved to Sheet M8. The Zone 8 I shown should have been Zone 4 per the 2009 Energy Conservation Code, however the interior design conditions shown are in compliance and the exterior design conditions are from the ASHRAE FUNDAMENTALS HANDBOOK. z S e k z s S e CONSULTING MECHANICAL AND ELECTRICAL ENGINEERS