Loading...
HomeMy WebLinkAboutCBPR-2-10-3790 Bullard Engr plan rev comments 3-2-10.tif i BULLARD ASSOCIATES E NONEERS 1 Water Thrush Road Telephone: 803 - 631 -1331 Clover, South Carolina 29710 Facsimile: 803 - 631 -1332 Email: baengineers @aol.com March 02, 2010 i CBSA ARCHITECTS Post Office Box 1239 Hickory, North Carolina 28601 I Attn: Ernest K. Sills, AIA Re: ARNDT MIDDLE SCHOOL Hickory, North Carolina Catawba County Plan Review Comments' i Gentlemen: x The following electrical comments have been addressed as follows: k EE 3" f 36) Each power pole has four (4) electrical receptacles and four (4) data outlets. This is shown in Detail B /E5 on the final drawings. 37) The missing #3 was a typographical error, which has been corrected. 38) All recessed panels previously shown in 1 -hour rated walls have been either moved into non- rated walls, or a non -rated wall has been added in front of the rated wall. Currently there are no panelboards recessed into rated walls. P 39) All cables (not run in metallic conduit) and other materials located above ceilings are "plenum" rated. See Note #1, sheet E19. Very truly yours, BULLARD ASSOCIATES ENGINEERS Connor Bullard, P.E. f R