HomeMy WebLinkAboutELEC-12-09-3633 FES Rpt on 3 ph transfmr 4-7-10.tif ii5 Y 3
FES REPORT
/N, TUVRheinland "
File Number: 310708.001
Equipment: 225 WA Variable Reactance Transformer and DC supply System Precisely Right.
Model: SC-1 16-M
Client SC-1 16-M
FIELD EVALUATION REPORT
Product type: 225 WA 3 Phase Variable Reactance Transformer and
DC supply System
Model number: SC-1 16-M
Serial number: SC-1 16-M
CLIENT:
Solomon Engineering
340 9th Street
Hickory NC, 28602
AUTHORITY HAVING JURISDICTION:
Catawba County Building Department - Inspections Department
Hickory City Hall
North Center Street
Hickory, North Carolina 28601
828 - 465 -8399
Permit number: ELEC - 12 -09 -3633
FINAL INSTALLATION SITE:
Solomon Engineering
340 9th Street
Hickory NC, 28602
TRNA file Number: 31070849.001
TRNA field label number(s): 031623
Evaluated by: Scott Kendall Reviewed by: Craig hunter
Date: 04 -01 -2010 Date: 04 -07 -2010
Title: Senior Engineer Title: Project Engineer
Field Evaluation Services Group Field Evaluation Services Group
Email: skendall @us.tuv.com Email: chunter @us.tuv.com
QF130501 Page 1 of 9 Revision 2
I
FES REPORT TUVRheinland`"'
File Number: 310708.001 Precisely Right.
Equipment: 225 WA Variable Reactance Transformer and DC supply System
Model: SCA 16-M
Client: SCA 16-M
SCOPE OF EVALUATION:
On April 01, 2010 TUV Rheinland of North America has been retained to conduct a Field Evaluation of the
subject equipment residing at the facility as stated under the heading "Final Installation Site" on page (1). This
evaluation may consist of a Preliminary Product Evaluation and Final Installation Evaluation for Electrical Fire
and Shock Hazards. The Final Product and Installation Evaluation was completed on April 01, 2010
GENERAL CONDITIONS OF ACCEPTANCE:
This test report contains only findings and results regarding the indicated equipment for installation at the
particular final installation location. It is not intended as an endorsement of the equipment, nor an approval of €:
similar or identical equipment at another location. If this equipment is modified, changed or moved to another
location after the date of inspection the evaluation and Label is considered Void. Re- inspection shall be
required.
TRNA's label indicating the equipment as compliant does not relieve the owner /manufacturer of its responsibility
i
for the safe operation of the equipment.
This evaluation does not include evaluation of the suitable operation of the unit and does not include emission
tests or locations defined as hazardous by the National Electrical Code (NEC).
INSPECTION PROCEDURES: d
1. Component List:
The following safety relevant components were inspected for suitability of electrical rating and NRTL' approval.
Discrepancies noted during evaluation are noted in the section detailing "Modifications for Compliance ".
• Circuit breakers • Power cords • Receptacles h
• Fuses • Interconnecting cords • Cables and wires
• Pushbuttons • Interlocks • Disconnect switches
• Relays • Motors • EMO's
• Transformers • Motor overload • Power supplies
• Interlocks • Motor contactors • Motor controllers
• Internal wires • Lamps
i
i
2. Construction Evaluation:
The equipments design was visually inspected with particular attention to the following areas:
I
• Use of listed components • Guarding of live parts
• Proper motor protection • Guarding of moving parts
• Proper transformer protection • Damaged components
• Proper conductor protection • Accessibility of moving parts
• Proper wire bending spaces • Environmental conditions
• Ground and bonding • Pinching, crushing, failing }
• Accessibility of live parts hazards ='
• Wiring ampacity • Sharp edges
• Wiring methods Suitability of enclosures
• Suitability of material • Availability of suitable markings
• Suitability of power connection
i
1 NRTL: Nationally Recognized Testing Laboratory, e.g. TUV Rheinland of North America, Inc., UL, ETL, etc. R
OF130501 Page 2 of 9 Revision 2
FES REPORT ,► TOVRheinland
File Number: 310708.001 Precisely Right.
Equipment: 225 kVA Variable Reactance Transformer and DC supply System
Model: SC-1 16-M
Client: SC-1 16-M
In detail, the following inspections were performed:
(a) Grounding and Bonding:
Exposed non - current carrying parts of the equipment were inspected for effective grounding
and bonding in accordance with applicable provisions of the standards referenced in this report.
(b) Guarding of Live and Moving Parts:
All internal components were inspected for installation in a suitable enclosure and effective
guarding in accordance with applicable provisions of the standards.
Moving parts are inspected to contain suitable guards against pinching, crushing or other
mechanical injury.
(c) Overcurrent, Short Circuit and Overload Protection:
Overcurrent, short circuit and overload protection installed in this equipment was evaluated for
compliance to relevant standards. They were identified to be NRTL listed and of proper size
and location.
(d) Internal Wiring:
Internal wiring and wiring methods were evaluated for compliance with relevant standards.
Wiring was verified to be, properly sized and rated, with a temperature rating suitable for the
installed application.
(e) Electrical Testing
Various electrical tests were performed to verify the suitability of operation and safety of the
unit. Selection of tests, are dependent on the type of equipment and relevant standard's
requirements. Test data sheets are attached to this report.
(f) Environmental Suitability:
The suitability of the equipment within its environmental context was evaluated. Outdoor type
equipment was evaluated for suitability for exposure to rain, dust, humidity, splashing etc.
Enclosures were required to be NEMA rated and suitable for their relevant application
(g) Installation of the Unit:
It was verified that the equipment / fixture is installed in accordance with the manufacturer's
installation instructions. Furthermore, installation requirements as per the National Electric
Code (NEC) such as working areas, power connection, etc. and corrective measures were also
evaluated.
QF130501 Page 3 of 9 Revision 2
FES REPORT .�► TUVRheinland'
File Number: 310708.001 Precisely Right.
Equipment: 225 OVA Variable Reactance Transformer and DC supply System
° Model: SC-1 16-M
Client: SC -116 -M
Product Description
a
The equipment is: A 460 VAC 60 Hz three phase 225 WA water cooled transformer with an integral
DC power supply to supply the machine control power.
Equipment Omitted from the Evaluation: None
The system consists of:
• Three transformer assemblies (one per phase)
• DC power supply
i
} Standard(s)
i
The product was evaluated and tested for general compliance to the following applicable code(s),
{ safety and electrical standard(s):
i
• NFPA 70 — 2008, "National Electrical Code" (NEC)
i
Terms and Conditions of Acceptability
I
Installation Instructions: Accepted Declined Not available
Drawings: Accepted Declined J Not available g
Markings: Accepted Declined Not available
Initial review date: Aril 01 2010
Next review: N/A f
Final review date: Aril 01, 2010
f
S
A
Comments: Construction evaluation and OEM document review only.
i
i
r
5
d
R
E'
S
OF130501 Page 4 of 9 Revision 2
FES REPORT TOVRheinland
File Number: 310708.001 Precisely Right.
Equipment: 225 kVA Variable Reactance Transformer and DC supply System
Model: SC-1 16-M
Client: SC- 116 -M
Field Evaluation Test Data
Product Compliance Testing
Evaluation Parameters:
Total number of similar units: None
Rated voltage: 460 ®VAC ❑ V DC
Rated current: 225 See Nameplate data section of this report
WA
Rated frequency: 60 Hz
Control voltage: 60 1 ®VAC ❑ V DC
Alternate voltages: N/A ❑ V AC ❑ V DC
Largest motor: N/A HP kW
AIC mains switch): 13 kA
Hazardous location: ❑ Yes
E No
Area classification: i.e. Ordinar
Location: i.e. Indoors, Type 1
Evaluation Type: E Equipment Evaluation for Electrical Fire and Shock Hazard
❑ Includes Mechanical Hazards
Test Parameters:
1- -1- 1- -1- 1- -1- No voltage measurements were made
Voltage: N/A N/A N/A the transformer was not connected to
P(A) P B P(C) Utility power.
Current (amps, max): N/A N/A N/A
Insulation resistance: >550 w2 ❑ 500 V DC E 1,000 V DC
Dielectric withstand test (alternate): N/A kV ❑ AC ❑ DC
Ground continuity: <.25 mo
Leakage current (max): N/A mA
Branch circuit protection: 350A A ® Hardwired ❑ Cord Connected
Enclosure class: ® NEMA Type 1 ❑ NEMA Type 3
❑NEMA Type 2 ❑NEMA Type 4
E- Stops /Interlocks: E Pass ❑ Fail E N/A
Rain test: ❑ Pass ❑ Fail E N/A
GFCI test: ❑ Pass ❑ Fail E N/A
Additional tests: N/A
Note: Leakage current tests not required when equipment is hardwired.
Notes:
Client has documentation on file validated the use of an existing NRTL Listed insulation system.
Additionally the client has a KEMA produced technical file of third party testing of this and similar
systems produced by Hunterdon Transformer company performed to validate compliance to the
applicable IEC standards relative to this equipment.
QF130501 Page 5 of 9 Revision 2
i
4
5
FES REPORT TUVRheinland'"
File Number: 310708.001 Precisely Right.
:3 Equipment: 225 WA Variable Reactance Transformer and DC supply System
! Model: SC-1 16-M
Client: SC -116 -M
Test Equipment:
Device Manufacturer Model Serial Number Calibration Due
Fluke 1587 insulation resistance multi -meter Fluke 1587 92470095 05/28/2010
Fluke i400 AC current clamp Fluke 1400 91230484 05/28/2010
Nameplate data:
Hunterdon Transformer Co.
Manufacturer: Flemington NJ, USA
225 kVA 3 Phase Variable Reactance Transformer and DC
TO supply System
{ Model number: SC-116 -M
Serial number: SCA 16-M
XFMR Max. Primary voltage: 460 VAC 60 Hz Delta 3 phase
XFMR Max. Primary current: 163 A
XFMR Rated secondary voltage: 60 VAC 60 Hz
XFMR Max. secondary current: 1250 A
XFMR Rated kVA: 225 kVA
Main diagram number: SC -116 -M
DC supply input control voltage: 460 VAC single phase
DC supply input control current: 10A
I
DC supply output voltage: 115 VDC p
i
DC supply output current: 120 A
:
Enclosure Type rating: Type 1
Approximate Weight: 3600 lbs.
Cooling: Water cooled - See main diagram
Section 1_ of _1_, see diagram No. SC-1 16-M for interconnections
t
QF130501 Page 6 of 9 Revision 2-
FES REPORT L = TOVRheinland
File Number: 310708.001 Precisely Right.
Equipment: 225 WA Variable Reactance Transformer and DC supply System
Model: SCA 16 -M
Client: SCA 16 -M
Photo(s): 225 kVA 3 Phase Variable Reactance Transformer and DC supply System
225 kVA 3 Phase Variable
Reactance Transformer
and DO supply ;Systo'l
N11, wi disconnect location
;R
QF130501 Page 7 of 9 Revision 2
5
FES REPORT ,� TOVRheinland'
File Number: 310708.001 Precisely Right.
Equipment: 225 WA Variable Reactance Transformer and DC supply System
Model: SCA 16-M
Client: SCA 16-M
,I
� I
s
a
S
i
I i
( 1
( t
{ fi
1
i
C
{
i
1
C
p
g €
E
f
r
S
C
S
r
B
k
QF130501 Page 8 of 9 Revision 2
FES REPORT TUVRheinland
File Number: 310708.001 Precisely Right.
Equipment: 225 WA Variable Reactance Transformer and DC supply System
Model: SC-1 16-M
Client: SC-1 16-M
rr n ..
Cautionary markings:
4!� M ARN ING
Ai HAZARDOUS
VOLTAGE,
Disconnect power
before servicing.
End of report