M :iy 26, 2010
Ell 4T Electric
2: 99 Peachtree St.
CIiaremont, NC 286'0
Allan: Bruce
F. Ix: 828 - 459 -2510
R!": Mt. View Eye Care
Allied #10026
E-)ar Bruce,
A,;; discussed on the telepl none earlier today the use of type NM cable and plastic to all
devices is acceptable excf l >t in exam rooms 103, 104 & 109. In those rooms only, the
r+ , ceptacles shall have me sll boxes and be feed with either healthcare grade MC cable
of EMT conduit.
li you have any questions :lease do not hesitate to contact us.
ncerely,
L
L, Dean Belk, PE