HomeMy WebLinkAboutCBPR-4-10-4937 Architects Response to PR Comments.tif N r ik M GH Phone: (919) 851 -1980 FAX: (919) 851 -1982 mhuslage @bobbitt.com Michael G. Huslage, P.LLC. Architect 600 Germantown Road Raleigh, NC 27607 v May 21, 2010 j Catawba County Permit Plan Review 76 North Center Street Hickory, NC 28601 I RE: Case #: CBPR -4 -10 -4937 t St Stephens Fire Department 4060 Springs Road I Conover, North Carolina Building Review (Steve Deitz 05/04/2010)• i 1 -9. We will comply as stated. 10. "C" drawings included in this submission have been signed and dated by an NC design professional. 11. "Not for Construction" has been removed from the "C" drawings. 12. Stove anticipated to be a GE Profile # ZDP364NDPSS (See attached) 13. Dishwasher is "undercounter" type and ADA compliant for low 34" counter. 14. Hood remote actuation device located on the floor plan, Al as well as sheet M2. 15. Chief Industries metal building manufacturer design parameter provided (See attached) 16 -18. (See letter by En -Tech Engineering) 19. Letter by Chief Industries metal building manufacturer regarding hood provided (See attached) 20 -21. (See letter by En -Tech Engineering) Fire Review (William Bump 04/26/2010) 1. We would like to field locate the fire extinguishers with the Fire Marshal to ensure optimal coverage. 2 -4. (See letter by En -Tech Engineering) 5. A "Knox Box" will be provided and located per the fire department. 6 -11. 1 (See letter by En -Tech Engineering) d Thank you for your help on this project and feel free to contact myself or Brian Griffith with any additional questions or comments you may have. I Sincerely, s i' Michael G. Huslage, AIA Consulting Architect ( i i f E r f ENGINEERING EnTech Engineering, PA PO Box 11527 Goldsboro, NC 27532 919.778.9064 a PME COMMENT RESPONSES ENTECH Project Manager: Rod Brown ENTECH Project No.: 210002 i Response Date: May 19, 2010 3 Agency: County of Catawba Project Name: St Stephens Fire Station Reference No.: BLDC4-10 -6440 f 9 i Note: Included are written PME comment responses with sufficient information, detail and document references such that reviewers can readily check and clear the comments. I t Building Comments - Reviewer: Steve Deitz 16. Hose bibs are provided in each room with a floor drain via wall mounted hose faucet or hose faucet included with mop sink. 17. Note No. 3 added to Sheet M1. 18. Specific hood capacity information will be provided by the hood supplier with required detailed shop drawings. Hood exhaust is not to exceed 800 CFM. Makeup air is provided via gas furnaces. A transfer duct has been added to the kitchen to pull air from the building when hood is in use. 19. Bobbitt Response. 20. Typographical error corrected in Energy Report on Sheet M4. 21. The entire building load is supplied through the transfer switch. This switch is "Service Entrance Rated" which means it will be equipped with a main breaker. This breaker is the service disconnect for the building. Fire Comments - Reviewer: William Bump 1. Bobbitt Response 2. No response necessary. s a 3. Fire sprinkler contractor will submit final design for approval. 4. Fire alarm contractor will submit final design for approval. 5. Bobbitt Response 6. Duct detectors are indicated to be connected to fire alarm system — See Fire Alarm Drawings 7. Hood installer will furnish detailed shop drawings. 8. Hood ansul system & fire sprinkler system are indicated to activate fire alarm system — See Fire Alarm Drawings. 9. Exit sign is shown above the door and the "72" fixture at the Patio are emergency fixtures. 10. The "H1" fixtures in the stairwell are emergency fixtures. 11. Note No. 3 on Sheet FP -3 changed to Catawba County as required. End of Comment Response. t f ,. a 3 a a s i i i i a a a ti B BB/ _ TT . { May 17, 2010 i Catawba County Plan Review 76 North Center Street Hickory, NC 28601 Reference: Project Name: St. Stephens Fire Department Project ID.: BLDC -4-40 -6440 We have reviewed your comments for the referenced project and offer the following responses to 6 issues effecting Site Design: Building Review — CBPR -4 -10 -4937 Reviewer: Steve Deitz i 1 6 review:5 /4/2010 Disapproved 10. All Sheets beginning with 'C', shall be sealed, signed and dated by a Design Professional Licensed in the State of North Carolina x -All Sheets sealed and signed 11. Remove 'Not for Construction' from all sheets that begin with 'C' -Note has been removed from all `C' sheets. Erosion Control Review — ECPR -4 -10 -4938 Reviewer: Toni Norton 1 5 review:4 /28/2010 Approved with Notes Revise note for Temporary ground cover to specify 21 days - Construction Sequence is revised, see sheet C2.0 for details. Environmental Health Review — EHPR- 1- 10 -34 -92 Reviewer: Toni Norton 1S review:1 /19/2010 Approved Zoning — ZON -4 -10 -4939 Reviewer_ : Chris Timberlake 1 5 review:4 /27/2010 Disapproved Utilities — Provide verification from service provided that domestic service is available. - Please find enclosed email from City of Hickory verifying service. Traffic/Transportation — Provide documentation of NCDOT approved driveway permit prior to issuance of Zoning Authorization Permit. - Driveway Permit is pending. We will provide copy when available. Signs — Actual wall and Free standing signs will require separate review and permits, through Permits Center. - Noted. i s i nJe9 '4( NORTH CAROLINA - 600 GERMANTOWN ROAD - RALEIGH, N.C. 27607 - 919 - 851 -1980 - FAX 919 - 851 -1982 SOUTH CAROLINA - 500 LAWAND DR., SUITE 103 - COLUMBIA, S.C. 29210 - 803 - 731 -5550 - FAX 803 - 731 -5580 i i Landscaping — Continue /wrap landscape strip to extend beside parking spaces. Revise perimeter screening plantings to species providing faster maturity and coverage. - Parking landscaping has been extended and perimeter landscaping has been revised; see sheet C -5.0 for details Zoning — Recombination of existing properties must be completed prior to issuance of Zoning Authorization Permit. - Noted. Please call if you have any questions. Sincerely, BOBBITT DESIGN BUILD, INC. Blair P. Pittman, PE i i 3 I S i i i k S- CHIEF INDUSTRIES, INC. 3942 Old West Highway 30 May 14, 2010 P.O. Box 2078 Grand Island, Nebraska 68802 -2078 Re: Chief Quote No. QUOTE #9650402 Phone 308/389 - 7200 -Fax 308/389 -7221 Description: 82'x 132'x 18' Builders Name: Bobbitt Design Build Building Owners Name: St. Stephens Fire Department Jobsite City, State: Conover, NC Gentlemen: Please accept this letter as certification that the Chief components, produced for the above described project to be furnished to Bobbitt Design Build, for St. Stephens Fire Department, Conover, NC, will be designed for the following criteria as specified by Purchaser in the order documents: 2006 MBMA Occupancy Category Essential Facilities Seismic Roof Live Load 20 psf Spectral Response Short Periods (S 28% (Tributary Area Reduction Allowed) Spectral Response 1 s Period (S 10% Collateral Load 7 psf Seismic Importance Factor 1.5 Ground Snow Load (P 15 psf Design Category p Exposure Factor (C.) 1.0 Site Class p Thermal Factor (G) 1.0 Seismic Resisting System Importance Factor (1) 1.2 Longitudinal Direction Flat Roof Snow Load (P 12.6 psf Lateral Steel System (R =3.0) p eral Direction Steel System (13=3.0) Building Enclosure Enclosed Seismic Response Coefficient (C 0.126 Wind Speed 90 mph (GCpi ± 0.18) Spectral Response Parameter Short Period (SoS) 0.294 Exposure Category B Spectral Response Parameter 1 s Period (S 0.160 Importance Factor (1) 1.15 Analysis Procedure ELF Wind Pressure (q) 14.19 psf Base Shear 98,998 lbs. Other Loads: 800 Ibs Kitchen Exhaust Hood and applied in accordance with the North Carolina 2009 Building Code. The design of Chief structural steel components is in accordance with the provisions of the NASPEC 2001 AISI Standard and the 13th Edition of AISC. These Chief components as supplied, when properly erected as furnished, on an adequate foundation, will meet the loading requirements supplied to Chief by Purchaser in accordance with good engineering practices. This certification does not cover field modifications nor does it cover materials furnished by someone other than Chief Industries, Inc.; nor the connection between Chief components and those manufactured or supplied by someone other than Chief Industries, Inc. Chief design and detailing facilities: Grand Island, NE, Lincoln, NE, and Janesville, WI. Chief Fabrication facilities: GrandjMatv*M,� and Rensselaer, IN. CA /� '�• Sincere) SEAL - F. Quenti . Yada, P.E� Np.101$1 a Sr. roject Engineer Chief Industries, Inc. - B� QY /tl , � t� + +e � a L• rj E ZDP364NDPSS (Natural Gas) ZDP364LDPSS (Liquid Propane) ' GE Monogram° 36" Dual -Fuel Professional Range with 4 Burners and Griddl e { Dimensions and Installation Information (in inches) Professional ranges offer a number of choices in size and cooktop configurations. I All Professional Ranges are factory set for natural or liquid 35 -7/8" Width f Counterto p propane gas. The correct model should be ordered for the -- to Cooking installation situation.,���°' Surface Note: Conversion kits are included with the range if the wrong gas type was ordered. High Altitude kit, WB28K10553 for _ operation above 3,000 feet (for Natural and LP gas models), is also available. The kits must be installed by a qualified service , technician at additional cost. 35 -1/4" T ' Installation Information to Before installing, consult installation instructions packed with Heigh H product or online at Monogrom.com for current dimensional Height 3 -1/4" data. to 4 -3/4" A 36" or 42" wide professional vent hood with a minimum 600 = -= - - - - -- CFM is recommended for installation over this r ange. 28 -1/4 - - - -- i Advance Planning Toekick/Ieg Depth Height Refer to dimensional drawings for to r - € appropriate placement and necessary clearances when I ! 12' Minimum i to Adjacent Wall d planning the installation. Mn, 5. • Working areas adjacent to the ,A WARNING: i range should have 18" minimum Installations without a hood require clearance between countertop 48' minimum to combustibles. A custom hood installation with 18. and cabinet bottom. exposed horizontal combustible 13 __ ~_ surfaces must have an Auto -On Maxim — - Min. • Clearance between range and feature. Refer to hood installation - z; side wall or combustible material instructions for specific hood clearances. _ must be at least 12" on each side The surface of the entire back wall ° • Installation must conform with above the range and below the - hood must be covered with a non- _ t -M � local codes. In the absence of local combustible material such as metal 'o _ t codes, the range must comply ceramic tile, brick, marble or other — l stone. j with the National Fuel Gas Code, ANSI Z223.1- 1990. ) Min. = ADDITIONAL CLEARANCES: [ Allow 12' minimum clearance to an adjacent wall on each side. Working areas adjacent to the rangetop should have l For answers to your Monogram ®GE Profile'" or 18 minimum clearance between countertop and GE® appliance questions, visit our website at the bottom of the wall cabinet. ge.com or call GE Answer Center® service, 800.626.2000. Listed by Underwriters Laboratories Imagination at work Specification Created 7/08 130554 'd •t ZDP364NDPSS (Natural Gas) ZDP364LDPSS (Liquid Propane) GE Monogram° 36" Dual -Fuel Professional Range with 4 Burners and Gri Dimensions and Installation Information (in inches) Electrical Requirements Optional Backsplash Accessories Ranges must be supplied with 208/240V, 60Hz, and connected The range requires a 12" minimum clearance to a vertical ! to an individual, properly grounded branch circuit protected combustible surface at the rear. A backsplash is required I by a circuit breaker or time -delay fuse. Install a 30 -amp circuit for installations with less than 12" clearance. The following for 36" ranges. The receptacle must be a NEMA 14 -SOR device backsplash accessories are available, or a custom, non - to accept the four -prong plug on the range. combustible backsplash can be used. Universal Utility Locations Order one with a 36" -wide range backsplash ZX12B36PSS -12" backsplash ZXADJ636PSS- 30 " -36" adjustable- height backsplash with E' warming shelf i f 4 -5/8" I I i 13 -3/8" 11 -3/8" 6 -1/2" r mss 2" 2" 36" Locate gas and Side View with a Backsplash electric as shown - , °� — - - -► 12" Min. to combustibles or 0' to I Gas Supply ' if — i' a non - combustible material above 13A - ►! I� i the cooking surface • The natural gas models are designed to — -- operate at 5" water column pressure. For proper operation, the pressure of 3os - * - ► the natural gas supplied to the regulator 3 -3/,6• must be between 7" and 13" water column. _4 - -�- - -- �av�•T° - -- -- -� - -- to • The LP models are designed to operate ;= E* of ew" �1_ 0" Clearance of 10" water column pressure. For P ane l s""°'° - I to a back or side wall below proper operation, the pressure of the. LP a&ii+ _ the cooking n_,rr T° gas supplied to the regulator must be W, surface F DO* for between 11" and 13" water column. — — -- aav, ` For answers to your Monogrom®GE Profile" or T °rmmaooa GE® appliance questions, visit our website at ' - -- T°RodOfH xh - - ge.com or call GE Answer Center® service, ' - — -- - '&'/ - - - - -.I With avarr oar O 800.626.20001 Usted by L Underwriters Laboratories � imagination at work 411M Specification Created 7/08 130554 r ZBD1870NSS GE Monogram ®18" Dishwasher Features and Benefits • Integrated Design - Offers a. stainless steel door and slim tubular handle • Hidden, Integrated Electronic Controls - Allow easy activation of wash cycles: heavy wash, normal wash, light wash, china and rinse only • Five -Level Wash System - Provides effective, yet quiet cleaning power j • ENERGY STAR® Qualification - As an ENERGY / STAR® partner GE has determined that the Monogram" 18" dishwasher meets the ENERGY STAR guidelines for energy efficiency and water conservation • Pearlescent Gray, Nylon- Coated Racks with Ball- Tipped Tines - Provide plenty of space and t loading flexibility • StemSafe'" Shelf - Allows for odd - shaped items and delicate stemware • Model ZBD1870NSS - Stainless steel I e I P p g § � . yy E For answers to your Monogram ® GE Profile" or GE® appliance questions, visit our website at #` ge.com or call GE Answer Center® service, 800.626.2000. z Listed by Underwriters z imagination at work Laboratories r Specification Created 6/08 150049 ZBD187ONSS GE Monogr9 m° 18" Dishwasher Dimensions and Installation Information (in Inches) • The dishwasher must be installed so that the drain hose is no more than 10 feet in length for proper drainage. • The dishwasher must be full encl sed on the top, sides 34'm35• 2,V and back, and must not support any part of the enclosure. Underside of Min m" � CLEARANCES: ' I Cabinets When installed into a corner, allow 2" Square min. clearance 6 and between dishwasher and adjacent cabinet,wall or other s j 174T Min. Plumb appliances. Allow 25 -5/8" min. clearance from the front of the dishwasher for door opening. Floor MUST be Even with J flaom F1oa j 32 -1/Y Admtalk Countertop to 35' t Dishwasher a 22 -1/2' Max. 17 -1/2' ADA- Compliant ZBD1870NSS: 25 -5/8" Installation below 34" -high countertops A reduced - height installation (32 -112" min.) beneath a Clearance for Door 34" countertop can be accomplished by removing the Opening 2" Minimum front leveling legs. The rear legs should be screwed in flush with the bottom support, as shipped. The front of the dishwasher must. be shimmed to level it. Water and electrical must be routed through the back wall. Installation Information: I Before installing, consult installation instructions packed Electrical Requirements with product, or available at Monogrom.com, for current dimensional data. The dishwasher must be supplied with 120V, 60Hz, and s connected to an individual properly grounded branch circuit protected by a 15- or 20 -amp circuit breaker or time -delay fuse. i [[ F t b For answers to your Monogram ®GE Profile`" or GE® appliance questions, visit our website at ge.com or call GE Answer Center® service, 800.626.2000. AAAW�k U Listed by As an ENERGY STAR• rw Underiters ®partner GE has determined ® Laboratories ' that this product meets the imagination at work zn ENERGY STAR guidelines F for energy efficiency. Specification Created 6/08 150049