REF - determine bearing wall per site visit for newly created cased opening
-per building inspections and fire inspections request
-per space belonging to Dean Powell at highland park
Brandon Lewis,
I made a site visit t look at conditions around the newly created opening.
There is a steel roof beam (W shape or "I" beam)that caries steel bar joist loads and
transfers that load to steel columns and to footings. This load path from roof down does not
transfer any loads to interior walls so the wall is non-load bearing.
F
The wall is a light gage metal stud wall with studs at approx. 24" on center with 5/8" gyp
board each side.
Call me if you have any questions
Regards,
Ray Campbell, AIA
Architect
Campbell Design PA
Architecture and Interior Design
4511-B North Highway 16
Suite B
Denver, NC 28037 Z '
704-489-1438
Fax: 704-489-1439
Mobile: 828-312-6614
4511 North Highway 16 Suite B Denver, NC 28037 • (704) 489-1438 • Fax (704) 489-1439 • campbelldesign.info
- ~1- oa~Z,°t l1
5pOr, jE
MEN;
CAMPBELL
D E S I G N D EC EP W E
FEB - 4 2010
Hickory City Hall
BUILDING SERVICES DIVISION
76 N. Center St. CATAWBA COUNTY
Hickory, NC 28601 PERMIT CENTER
Brandon Lewis, Lead Plan Review official
828.466.5130 press 01
BLewis@catawbacountync.gov
REF - determine bearing wall per site visit for newly created cased opening
-per building inspections and fire inspections request
-per space belonging to Dean Powell at highland park
Brandon Lewis,
I made a site visit t look at conditions around the newly created opening.
There is a steel roof beam (W shape or "I" beam)that caries steel bar joist loads and
transfers that load to steel columns and to footings. This load path from roof down does not
transfer any loads to interior walls so the wall is non-load bearing.
The wall is a light gage metal stud wall with studs at approx. 24" on center with 5/8" gyp
board each side.
Call me if you have any questions
Regards,
Ray Campbell, AIA