HomeMy WebLinkAboutCBPR-10-09-2314 Plan Rev comments 12-9-09.tif a mission critical facilities" a A company of P t 1 December 9, 2009 James Lamb Development Assistance Center 76 North Center Street Hickory, NC 28601 Re: Catawba County Plan Review Ref. #CBPR-10-09-2314 Dear Mr. Lamb: { } r This letter is in regard to our telephone conversation of December 8, 2009. Below are our responses to the two outstanding items in reference to obtaining the plumbing permit for this project. I 1. The six 4-inch area drains on the project serving the area wells (ranging in areas from 4,657 to 4,676 square feet), will be revised to 5-inch, to comply with the 4,600 square foot limit of Table 1106.2 of the 2009 North Carolina Plumbing Code. 2. The cold water supply lines serving the two reverse osmosis (1-inch supply line each) and the two deionized water (3/4-inch supply line each) equipment, will be revised to include double check assembly backflow preventers equal to Wilkins Model 350S. I hope the above is satisfactory for resolving this two issues. If you have any questions or concerns, please don't hesitate to contact me. Sincerely, _ Mark Nykowski Senior Plumbing/Fire Protection Designer EYP Mission Critical Facilities 200 West Adams Street Suite 2750 Chicago, 1160606 my owski0hg com