AQWA Inc.
2604 Willis Court,Wilson, NC 27896
Phone: 252-243-7693—Email:aqwatammysanders@gmail.com
Customer Name: Herrin Date of Inspection: 6/17/2022
Address: Herrin-4104 Wilkerson Drive Claremont,NC 28610 Arrival Time: 7:40:00 AM
System AX ID: AX-140199 Departure Time: 8:50:00 AM
County: Catawba
Permit No.
Inspection and Maintenance Checklist-AX-RT with LPP or P-Manifold or D-BOX
Septic Tank Inspection
Tank At Site Tank 1
Tank 1 Inlet Readings Tank 2 Inlet Readings
0 Scum 10 Sludge Scum Sludge
Tank 1 Outlet Readings Tank 1 Outlet Readings
0 Scum 8 Sludge Scum Sludge
..t I",!. a tit��:�rt�. .., :6. e �t "'iia F +� ,e,�^�t'ai;'k.,F;+...�
Clean Effluent Filter: Cleaned
Check for Influent or Effluent Blockages: No Blockage
Inspect Tank/Riser for Leaks: None Seen
Control Panel Inspection
Check Pump Operates In Manual Mode: Yes
Recirculation Pumps Recirculation Pump 1
Pump 1 Timer Settings Pump 1-Counters and Elapsed Time Meters
0.8 Dose 10 Rest 27815 CT 1732 ETM
Dose Pumps
Pump 1 Timer Settings Pump 1-Counters and Elapsed Time Meters
Demand Dose Demand Rest 50 CT 3 ETM
Verify Conduit Seal: Verified
AX-RT Treatment Pod Inspection
Inspect for Ponding or Bridging: None
Check and Record PSI: 4.5
Verify Orifice Position and Assess for Clogging: Cleaned
Check for Odors: None
Clean,Brush,Flush Lateral: Done
Recheck and Record PSI 4.5
Flush Pod Throroughly: Done
Inspect and Clean Vents: Cleaned
Inspection and Maintenance Checklist-AX-RT with LPP or P-Manifold or DBOX
Recirculation Chamber Inspection
Verify Inlet Flow: No Inflow
Inspect Liquid: Normal Level
Record Scum/Sludge Levels:
Inlet Readings: Outlet Readings:
0 Scum 2 Sludge 0 Scum 0 Sludge
Inspect Tank/Riser for Leakage: None Seen Verify All Floats Work: Operating Properly
Pump Sludge to Septic Tank. Not Needed Verify Audible Alarm Works for High Water float: Works Property
Pull Pump and Clean Screen: Cleaned Verify Neat Wrap of Float and Pump Cords: Checked
Verify No Leaking In Piping or Flex Hoses: None Seen Verify Conduit Seal: Verified
Ultraviolet Disinfection Unit Inspection
Does System Have a UV? Yes
How Many UV Disinfectant Units Present? UV 1
.
After Disconnecting Power,Clean or Replace Bulb As Needed: Cleaned
Flush Housing Thoroughly: Flushed
Return Power and Verify Proper Function: Verified
Dosing Chamber Inspection
Inspect for Tank/Riser Leakage: None Seen
Inspect Liquid: Normal Level
Record Scum/Sludge Levels:
Inlet Readings: Outlet Readings:
Scum Sludge 0 Scum 0 Sludge
Visually Check Liquid Level: Normal Verify Audible Alarm Works for High Water float: Works Properly
Verify No Leaks In Piping or Flex Hoses: None Seen Verify Neat Wrap of Float and Pump Cords: Checked
Inspect Pump Intake: Cleaned Delivery Rate at Start Up: 21
Verify All Floats Work: Operating Properly Verify Conduit Seal: Verified
LPP or P-Manifold or DBOX Inspection
Areas Mowed and Clear of Obstruction: Yes Flush Laterals: Not a LPP
Area Free of Ponding or Surface Effluent: Yes Set and Record Head Pressure: N/A
Curtain Drains,Ditches,Swales Functioning Properly: Yes Check Hardware: Functioning Property
Current Delivery Rate: 20.9 Pump Efficiency: 99
Return Valves and Control Panel to proper settings Done
Control Panel Communication Checked: Panel called in
inspection Notes
35.25-44.75=9.5 x4.4=41.8/2=20.9 gp m
David Parker
Operator Operators Signature
AOWA
The:lea'leader OD
AQWA Inc.
2604 Willis Court,Wilson, NC 27896
Phone: 252-243-7693— Email: agwatammysanders@gmail.com
Customer Name: Herne Date of Inspection: 6/20/2023
Address: Herrin-4104 Wilkerson Drive Claremont,NC 28610 Arrival Time: 10:55:00 AM
System AX ID: AX-140199 Departure Time: 11:50:00AM
County: Catawba
Permit No.
Inspection and Maintenance Checklist-AX-RT with LPP or P-Manifold or D-BOX
Septic Tank Inspection
Tank At Site Tank 1
Tank 1 Inlet Readings lank 2 Inlet Readings
0 Scum 7 Sludge Scum Sludge
Tank 1 Outlet Readings Tank 1 Outlet Readings
0 Scum 6 Sludge Scum Sludge
Clean Effluent Filter: Cleaned
Check for Influent or Effluent Blockages: No Blockage
Inspect Tank/Riser for Leaks: None Seen
Control Panel Inspection
Check Pump Operates In Manual Mode: Yes
Recirculation Pumps Recirculation Pump 1
Pump 1 Timer Settings Pump 1-Counters and Elapsed Time Meters
0.8 Dose 10 Rest 76757 CT 2395.6 ETM
Dose Pumps
Pump 1 Timer Settings Pump 1-Counters and Elapsed Time Meters
On demand Dose On demand Rest 97 CT 5.2 [TM
Verify Conduit Seal. Verified
AX-RT Treatment Pod Inspection
.'�:�x': t`x,RYw"fY .i ire112,2C" •
Inspect for Ponding or Bridging: None
Check and Record PSI: 4.5
Verify Orifice Position and Assess for Clogging: Ok
Check for Odors. None
Clean,Brush,Flush Lateral: Done
Recheck and Record PSI 4.5
Flush Pod Throroughly. Done
Inspect and Clean Vents: Vents Clear
Inspection and Maintenance Checklist-AX-RT with LPP or P-Manifold or DBOX
Recirculation Chamber Inspection
Verify Inlet Flow No Inflow
Inspect Liquid: Normal Level
Record Scum/Sludge Levels:
Inlet Readings: Outlet Readings:
0 Scum 2 Sludge 0 Scum 1 Sludge
Inspect Tank/Riser for Leakage: None Seen Verify All Floats Work: Operating Properly
Pump Sludge to Septic Tank: Not Needed Verify Audible Alarm Works for High Water float: Works Properly
Pull Pump and Clean Screen: Cleaned _ Verify Neat Wrap of Float and Pump Cords: Checked
Verify No Leaking In Piping or Flex Hoses: None Seen Verify Conduit Seal: Verified
Ultraviolet Disinfection Unit Inspection
Does System Have a UV? Yes
How Many UV Disinfectant Units Present? UV 1
After Disconnecting Power,Clean or Replace Bulb As Needed: Cleaned
Flush Housing Thoroughly: Flushed
Return Power and Verify Proper Function: Verified
Dosing Chamber Inspection
Inspect for Tank/Riser Leakage: None Seen
Inspect Liquid: Normal Level
Record Scum/Sludge Levels:
Inlet Readings: Outlet Readings:
Scum Sludge 0 Scum 1 Sludge
Visually Check Liquid Level: Normal Verify Audible Alarm Works for High Water float: Works Properly
Verify No Leaks In Piping or Flex Hoses: None Seen Verify Neat Wrap of Float and Pump Cords: Checked
Inspect Pump Intake: Ok Delivery Rate at Start Up: 21
Verify All Floats Work: Operating Properly Verify Conduit Seal: Verified
LPP or P-Manifold or DBOX Inspection
Areas Mowed and Clear of Obstruction: Yes Flush Laterals: Not a LPP
Area Free of Ponding or Surface Effluent: Yes Set and Record Head Pressure: N/A
Curtain Drains,Ditches,Swales Functioning Properly: Yes Check Hardware: Functioning Properly
Current Delivery Rate: 20.9 Pump Efficiency: 99
Return Valves and Control Panel to proper settings Done
Did not call in while on site.Lantronics has power,status,and link solid
green.The activity is blinking green.Please restore Internet service to
Control Panel Communication Checked: the line to the panel.Site has not called In since May 2023.
Inspection Notes
36-45.5=9.5.4.4=41.8/2=20.9/21=99%
Jeff Cranmer Y
Operator Operators Signature
f `
!AOWA
The°lea leader 0,..L)17,1
AQWA Inc.
2604 Willis Court,Wilson, NC 27896
Phone: 252-243-7693_ Email: aqwatammysanders@gmail.com
Customer Name: Herrin Date of Inspection: 11/14/2023
Address: Herrin-4104 Wilkerson Drive Claremont,NC 28610 Arrival Time: 1:15:00 PM
System AX ID: AX-140199 Departure Time. 2:05:00 PM
County: Catawba
Permit No.
Inspection and Maintenance Checklist-AX-RT with LPP or P-Manifold or D-BOX
Septic Tank Inspection
Tank At Site Tank 1
Tank 1 Inlet Readings Tank 2 Inlet Readings
0 Scum 2 Sludge Scum Sludge
Tank 1 Outlet Readings Tank 1 Outlet Readings
0 Scum 8 Sludge Scum Sludge
Clean Effluent Filter: Cleaned
Check for Influent or Effluent Blockages. No Blockage
Inspect Tank/Riser for Leaks: None Seen
Control Panel Inspection
Check Pump Operates In Manual Mode: Yes
Recirculation Pumps Recirculation Pump 1
Pump 1 Timer Settings Pump 1-Counters and Elapsed Time Meters
0.8 Dose 10 Rest 95245 CT 2845.6 ETM
Dose Pumps
Pump 1 Timer Settings Pump 1-Counters and Elapsed lime Meters
Demand Dose Demand Rest 128 CT 7.6 ETM
Verify Conduit Seal. Verified
AX-RT Treatment Pod Inspection
•
Inspect for Ponding or Bridging. None
Check and Record PSI: 5
Verify Orifice Position and Assess for Clogging: Cleaned
Check for Odors None
Clean,Brush,Flush Lateral: Done
Recheck and Record PSI 5
Flush Pod Throroughly: Done
Inspect and Clean Vents: Cleaned
Inspection and Maintenance Checklist-AX-RT with LPP or P-Manifold or DBOX
Recirculation Chamber Inspection
Verify Inlet Flow: No Inflow
aLAk - 0ri ) i��(
AOWA
The clear leader.
AQWA Inc.
2604 Willis Court,Wilson, NC 27896
Phone: 252-243-7693—Email: aqwatammysanders@gmail.com
Customer Name: Herrin Date of Inspection: 9/29/2025
Address: Herrin-4104 Wilkerson Drive Claremont,NC 28610 Arrival Time: 9:22:00 AM
System AX ID: AX-140199 Departure Time: 10:46:00 AM
County: Catawba
Permit No.
Inspection and Maintenance Checklist-AX-RT with LPP or P-Manifold or D-BOX
Septic Tank Inspection
Tank At Site Tank 1
Tank 1 Inlet Readings Tank 2 Inlet Readings
0 Scum 3 Sludge Scum Sludge
Tank 1 Outlet Readings Tank 1 Outlet Readings
0 Scum 0 Sludge Scum Sludge
Tank Inspection Questions Tank 1 Tank 2
Clean Effluent Filter: Cleaned
Check for Influent or Effluent Blockages: No Blockage
Inspect Tank/Riser for Leaks: None Seen
Control Panel Inspection
Check Pump Operates In Manual Mode: Yes
Recirculation Pumps Recirculation Pump 1
Pump 1 Timer Settings Pump 1-Counters and Elapsed Time Meters
0.8 Dose 20 Rest 61505 CT 3539 ETM
Dose Pumps
Pump 1 Timer Settings Pump 1-Counters and Elapsed Time Meters
Demand Dose Demand Rest 18.2 CT 303 ETM
Verify Conduit Seal: Verified
AX-RT Treatment Pod Inspection
Pod Inspection Pod 1
Inspect for Ponding or Bridging: None
Check and Record PSI:
Verify Orifice Position and Assess for Clogging: Cleaned
Check for Odors: None
Clean,Brush,Flush Lateral: Done
Recheck and Record PSI
Flush Pod Throroughly: Done
Inspect and Clean Vents: Vents Clear
Inspection and Maintenance Checklist-AX-RT with LPP or P-Manifold or DBOX
Recirculation Chamber Inspection
Verify Inlet Flow: No Inflow
Inspect Liquid: Low Level
Record Scum/Sludge Levels:
Inlet Readings: Outlet Readings:
0 Scum 0 Sludge 0 Scum 0 Sludge
Inspect Tank/Riser for Leakage: None Seen Verify All Floats Work: Operating Properly
Pump Sludge to Septic Tank: Not Needed Verify Audible Alarm Works for High Water float: Works Properly
Pull Pump and Clean Screen: Cleaned Verify Neat Wrap of Float and Pump Cords: Checked
Verify No Leaking In Piping or Flex Hoses: None Seen Verify Conduit Seal: Vented
Ultraviolet Disinfection Unit Inspection
Does System Have a UV? Yes
How Many UV Disinfectant Units Present? UV 1
, a,r r-
�n!€,..,w tia'4, `��#S.. .t..� a't '# - �.,x,.
_.. _.� ,.;.
After Disconnecting Power,Clean or Replace Bulb As Needed: Replaced
Flush Housing Thoroughly: Flushed
Return Power and Verify Proper Function: Verified
Dosing Chamber Inspection
Inspect for Tank/Riser Leakage: None Seen Turbidity Reading: 0.00
Inspect Liquid: Normal Level
Record Scum/Sludge Levels:
Inlet Readings: Outlet Readings:
Scum Sludge 0 Scum 0 Sludge
Visually Check Liquid Level: Normal Verify Audible Alarm Works for High Water float: Works Properly
Verify No Leaks In Piping or Flex Hoses: None Seen Verify Neat Wrap of Float and Pump Cords: Checked
Inspect Pump Intake: Ok Delivery Rate at Start Up: 21
Verify All Floats Work: Operating Properly Verify Conduit Seal: Vented
LPP or P-Manifold or DBOX Inspection
Areas Mowed and Clear of Obst action: Yes Flush Laterals: Not a LPP
Area Free of Ponding or Surface Effluent: Yes Set and Record Head Pressure: N/A
Curtain Drains,Ditches,Swales Functioning Prope ly: Yes Check Hardware: Functioning Properly
Current Delivery Rate: 19.8 Pump Efficiency: 94
Return Valves and Control Panel to proper settings Done
Control Panel Communication Checked: Panel called in.
Inspection Notes
36-45=9x4.4=39.6-2=19.8 TR changed recirc rest to 20.0 due to low usage.
Paul Smith
Operator Operators Signature