Development Assistance Center 76 North Center Street Hickory, NC 28601 Telephone: 828-323-7556 Fax: 828-323-7474 PLAN REVIEW NOTES REFERENCE# PLN2009-00085 3/11/2009 370216945137 Date
Received: PIN #: Company Name: Company Address: Company Telephone: Architect: Contact Person: Contact Person's Phone: General Contractor: General Contractor's Phone: Type of Occupancy:
STR Type of Work: Fax #: Proposed Use: ADDITIONS NATIONAL WELDERS SUPPLY CO. 704-644-3210 1085 6TH ST CT SE HICKORY NC 28602 PARKS, DANNY 828.754.1653 dparks@wilkie-const.com WILKIE
CONSTRUCTION COMPANY, INC 828-754-6431 828-754-6431 PH1 HKY ZON -Plans Received 3/12/2009 RECD GF HKY ZON -1st Review 3/12/2009 1-Art. 10.11; Fig 10-1 Buffer & screening appears to be
existing. 2-10.7 Dumpster enclosure being relocated . Recommend gates be of a stockade type design. 3-Proposed gas-pack unit; per designer Harold Marvin, will be screened in accordance
with Land Development Code--the duct work from the unit to the attic will be finished to match the metal siding on the building. See revised drawing Sheet # C1. 4-Refer to Engineering
Dept review for pervious surface requirements. 5-All utilities must be placed underground. 6-NOTE: Please call 323-7410 for a Zoning site visit once the project has begun..... APN GF
HKY ZON -Plans Completed 3/12/2009 APN GF Comments: Planning and Zoning Status: Complete -Approved with Notes Zone: I1 Front Yard: 0 Side Street: 0 Side: 0 Rear Yard: 0 Engineering Status:
Comments: HKY ENG -Plans Received 3/12/2009 RECD MM HKY ENG -Plans Completed 3/13/2009 APPV MC Complete -Approved Notice: All revisions to plans must be submitted as one package. Multipage
plans should not be submitted seperately. All sheets should be stapled or otherwise attached for each set submitted! r:\tidemark\forms\hky_bldinsp.rpt 09/09/2009 16:38 Page 1 of 4
PLAN REVIEW NOTES REFERENCE# PLN2009-00085 HKY ENG -1st Review 3/13/2009 APPV MC Building Status: Comments: CCPR-1st Review 3/17/2009 APPV SLD CCPR-Plans Completed 3/17/2009 1st Review
Approved * A review of this project was conducted. Summaries of the comments are in the following notes. * A written response to the comments in the order they appear in this correspondence
as well as appropriate clouded revisions to the plans shall be provided. * This review does not constitute a check of all technical code items and does not prevent the code official
from requiring further additions and /or corrections. * This review also does not relieve the design professional of full responsibility for compliance with all the provisions of the
technical codes and other pertinent laws or ordinances. All utilization equipment either Gas or Electric is required to be Listed or Labeled by a Nationally Recognized Testing Laboratory
approved by the North Carolina Department of Insurance. 1. Nobody shall be allowed to occupy this building or any portion thereof without approval of the Building Services Official.
2. The issuance of a permit or approval of plans or specifications shall not be deemed or construed to be approval of any violation of any of the provisions of the codes. 3. All interior
finishes shall comply with the North Carolina Building Code Table 803.5. 4. Adequacy of emergency exit lighting and signage will be checked in the field for compliance. 5. Identification
signage meeting the requirements of Chapter 4 and 18 of the NC Accessibility Code will be checked in the field for compliance. 6. The integrity of all firestopping and draftstopping
shall be maintained using approved materials and designs per the North Carolina Building Code section 717 using materials listed and labeled by an approved agency and installed per Mfg.
instructions. 7. All electrical service installations shall comply with the 2008 NEC. Special emphasis on articles 230.2, 230.70A, and 230.72 shall apply. 8. Where suspended type ceilings
are installed and form a concealed space, any room without a ceiling shall have the walls terminate tight against the floor or roof deck above for firestopping. Reviewer: Steve Deitz
APPV SLD Complete -Approved Fire Status: Comments: HKY FIR -Plans Received RECD ML Notice: All revisions to plans must be submitted as one package. Multipage plans should not be submitted
seperately. All sheets should be stapled or otherwise attached for each set submitted! r:\tidemark\forms\hky_bldinsp.rpt 09/09/2009 16:38 Page 2 of 4
PLAN REVIEW NOTES REFERENCE# PLN2009-00085 HKY FIR -1st Review 3/13/2009 APN 03/13/2009 1st REVIEW APPROVED WITH NOTES: 1. Plans show that 1 exit is required in the H-3 occupancy. Per
the 2006 NC Fire code Section 1014.2.1, this space is required to have 2 exits for the existing and new fill area. These exits are also required to have panic hardware in hazardous occupancies.
Verify doors and hardware. 2. An Additional fire extinguisher may be required for the new business addition and new fill room. Portable fire extinguishers shall be selected, installed
and maintained in accordance with Section 906 of the 2006 North Carolina Fire Prevention Code and NFPA 10. 3. During construction or demolition, vehicle access for fire fighting shall
be provided to the site. 4. See 06 North Carolina Building Code Chapter 33 Safeguards During Construction and sections of 06 North Carolina Fire Prevention Code Chapter 14 Fire Safety
During Construction and Demolition that would be applicable to this project. 5. In addition, addition, requirements for Cryogenic Fluids and Oxidizers shall comply with Chapters 32 and
40 of the 2006 NC Fire Code and referenced standards. 6. If new door labeled "D-7" is a roll back door, sprinkler protection shall be provided under the door due to door causing an obstruction
to the sprinkler system. 7. "No-Smoking" signs shall be provided in new addition at new entrance door. SPRINKLER COMMENTS 8. Sprinkler contractor shall obtain a permit from the Fire
Prevention Bureau prior to beginning any installation/renovation of the sprinkler/standpipe system. A copy of submittal requirements and applications are available upon request, 828-323-7522
or available on line at http://www.hickorygov.com/fire/fireprevention/preview/9. If sprinkler system is taken out of service see Chapter 9 section 901.7 Systems out of service and following
sub-sections. 10. Sprinkler contractor shall provide new calculations along with density of the sprinkler riser and the commodities the system is protecting. FIRE ALARM COMMENTS 11.
Fire alarm contractor shall obtain a permit from the Fire Prevention Bureau prior to any installation of the fire alarm system. A copy of submittal requirements and applications are
available upon request, 828-323-7522 or available on line at http://www.hickorygov.com/fire/fireprevention/preview/12. If new pull stations along outside walls are exposed to weather
and not protected by the canopy, approved devices for damp locations shall be provided. RWS HKY FIR -Plans Completed 3/13/2009 DONE 03/13/2009 1st REVIEW APPROVED WITH NOTES: 1. Plans
show that 1 exit is required in the H-3 occupancy. Per the 2006 NC Fire code Section 1014.2.1, this space is required to have 2 exits for the existing and new fill area. These exits
are also required to have panic hardware in hazardous occupancies. Verify doors and hardware. 2. An Additional fire extinguisher may be required for the new business addition and new
fill room. Portable fire extinguishers shall be selected, installed and maintained in accordance with with Section 906 of the 2006 North Carolina Fire Prevention Code and NFPA 10. 3.
During construction or demolition, vehicle access for fire fighting shall be provided to the site. 4. See 06 North Carolina Building Code Chapter 33 Safeguards During Construction and
sections of 06 North Carolina Fire Prevention Code Chapter 14 Fire Safety During Construction and Demolition that would be RWS Notice: All revisions to plans must be submitted as one
package. Multipage plans should not be submitted seperately. All sheets should be stapled or otherwise attached for each set submitted! r:\tidemark\forms\hky_bldinsp.rpt 09/09/2009 16:38
Page 3 of 4
PLAN REVIEW NOTES REFERENCE# PLN2009-00085 applicable to this project. 5. In addition, requirements for Cryogenic Fluids and Oxidizers shall comply with Chapters 32 and 40 of the 2006
NC Fire Code and referenced standards. 6. If new door labeled "D-7" is a roll back door, sprinkler protection shall be provided under the door due to door causing an obstruction to the
sprinkler system. 7. "No-Smoking" signs shall be provided in new addition at new entrance door. SPRINKLER COMMENTS 8. Sprinkler contractor shall obtain a permit from the Fire Prevention
Bureau prior to beginning any installation/renovation of the sprinkler/standpipe system. A copy of submittal requirements and applications are available upon request, 828-323-7522 or
available on line at http://www.hickorygov.com/fire/fireprevention/preview/9. If sprinkler system is taken out of service see Chapter 9 section 901.7 Systems out of service and following
sub-sections. 10. Sprinkler contractor shall provide new calculations along with density of the sprinkler riser and the commodities the system is protecting. FIRE ALARM COMMENTS 11.
Fire alarm contractor shall obtain a permit from the Fire Prevention Bureau prior to any installation of the fire alarm system. A copy of submittal requirements and applications are
available upon request, 828-323-7522 or available on line at http://www.hickorygov.com/fire/fireprevention/preview/12. If new pull stations along outside walls are exposed to weather
and not protected by the canopy, approved devices for damp locations shall be provided. Utility Status: Comments: HKY PU -Plans Received 3/12/2009 RECD APM HKY PU -1st Review 3/20/2009
Approved with notes 1. Any existing water and or sewer service shall not be disturbed during construction. 2. Developer respsonsible for protecting utilities during grading/paving for
parking lot. Coordinate with Hickory Public Utilities. APN RM Complete -Approved with Notes Environmental Health Status: Comments: Notice: All revisions to plans must be submitted as
one package. Multipage plans should not be submitted seperately. All sheets should be stapled or otherwise attached for each set submitted! r:\tidemark\forms\hky_bldinsp.rpt 09/09/2009